Goodrive310 is a variable-frequency drive family for AC induction motors and permanent-magnet synchronous motors. It uses sensorless vector control in an open-loop configuration. Does the machine need to carry a product at a steady speed, or manage torque as the load changes? Understanding speed and torque control makes drive selection and commissioning easier.

Read the full model code

In GD310-022G-4-UL, 022 indicates 22 kW, G denotes a constant-torque load, 4 indicates the three-phase 380–480 V class, and UL identifies the UL variant in the catalogue. The same catalogue lists three-phase 200–240 V for -2 and three-phase 520–600 V for -6. When choosing a replacement, check the full code, the drive’s rated output current and the motor’s nameplate current together. Consider both rated power and the other drive selection criteria.

Commissioning, control and software

Record the motor type and nameplate data first, including rated frequency, voltage and current. INVT documents static and rotating motor autotuning for the GD310. Use the matching manual to select a method for the motor and check whether the machine can safely rotate.

In the GD310-UL manual, P00.01 selects the keypad, terminals or communications as the run command source. The frequency reference source is selected separately. For external control, use the machine schematic and the drive terminal drawing together to check three-wire control and sink/source input logic.

The drive range uses Modbus RTU over RS-485. The P14 group in the GD310-UL manual covers the station address, baud rate and data format. The catalogue also identifies optional communications cards. When using an INVT PLC or INVT HMI, check which port and protocol the installed board supports.

INVT’s GD310 catalogue shows INVT Studio for reading and saving parameters and monitoring operating values. Check the full model code, drive firmware and PC software version before connecting. See INVT VFD Software for software information and the manufacturer’s PC connection note for general RS-485 guidance.

Where to start when a fault appears

On GD310-UL drives, P07.27–P07.32 show the active fault and the previous five records. Note the display code and whether it appeared during acceleration, steady running or deceleration. OV2, for example, indicates overvoltage during deceleration. The deceleration ramp, regenerative energy from the load and DC bus data can help with the initial diagnosis. Check the code in chapter 8 of the GD310-UL manual. The INVT fault code index leads to other drive families.

Editor’s Note

At the bench, start with a photo of both nameplates. Keep the full drive code and the motor’s current and voltage ratings handy.

A lit keypad and a stopped machine are reason to check the command sources. Find out where the run signal and the speed demand come from.

If a fault appears during deceleration, check the dynamic braking arrangement, the chopper type and the permitted braking resistor value in the matching manual before connecting a resistor.

When buying a used GD310, ask for a parameter backup and, where available, a test result with a suitable motor. If there is a fault, record the history before clearing it.

Save the existing settings before a factory reset. If work inside the panel is needed, a qualified electrician should isolate the supply and verify the DC bus voltage.

Related topics

Reading inverter faults · Current limiting · S-curve ramps · Flying start · Slip compensation

INVT GD200A · INVT GD350 · INVT commissioning videos

PDFs and technical documents

Visit INVT VFD Documents and INVT User Manuals for the OtomasyonAVM archive.

Manufacturer PDFs · GD310-UL Operation Manual (English, 259 PDF pages, -UL variant) · GD20 and GD310 combined catalogue (English, V6.0, Goodrive310 section)

INVT category path · INVT brand home › User manuals › INVT VFD drives