GD300-02

INVT GD300-02 Through-Wall Variable Frequency Drive

The INVT Goodrive300-02 is an AC motor drive with a flange that places the heatsink through the cabinet wall. This arrangement is particularly useful in textile plants, where it helps separate the electronics from process air carrying cotton fibre, dust and oil. INVT lists the range at 7.5–55 kW with a three-phase 380 V (−15%)–440 V (+10%) input class.

Frame size, output current and cooling

Section 3.6 of the manual lists GD300-02-7R5G-4 at 7.5 kW / 18.5 A, GD300-02-022G-4 at 22 kW / 45 A and GD300-02-055G-4 at 55 kW / 115 A. These are rated output currents. G identifies the constant-torque duty class and -4 the three-phase voltage class. Consider motor nameplate current, load cycle and the heating effect of the carrier frequency when sizing the drive.

When replacing a drive, check the cabinet cut-out, flange holes, seal and external air duct against the frame drawing. The manual specifies upright mounting and an independent external air duct. Derate above 40 °C ambient temperature. On systems with a shared DC bus, verify the power connections and any braking equipment against the wiring diagram.

Motor setup, command sources and software

The manual covers induction and permanent-magnet synchronous motors. When checking the V/f and sensorless vector control options, confirm the motor’s rated frequency, the configured base frequency and the applicable motor auto-tuning method.

Record the run-command source separately from the frequency reference. For terminal control, include any three-wire control, sink/source input arrangement and preset speeds in the backup. Record the PID control settings if the machine uses process feedback.

For serial communications, see Chapter 10 for RS-485 and Modbus RTU. Compare the INVT Modbus address examples with the model’s register table. To read parameters from a PC, start with INVT VFD Software and check the complete model code and connection type in the software.

Related topics and fault records

For startup or stopping problems, record the ramp times, any S-curve setting and the current limit. Select the braking resistor and braking unit using the frame’s wiring diagram. OH1 is a rectifier module overheat fault and OH2 an inverter module overheat fault. Chapter 8 of the model manual complements the general VFD fault guide and INVT fault codes.

Editor’s Note

When sourcing a spare, photograph the whole nameplate and the back of the cabinet. Finding a different flange pattern at fitting time can cost a shift.

If the drive trips on heat, look for lint in the external duct, gaps in the seal and a fan that has stopped.

Before clearing a fault, record the code, motor current and what the machine was doing. A drive that runs cold and trips halfway through production has already given you a clue.

Before a factory reset, reopen the parameter backup and make sure you can read it.

On a shared-bus system, have qualified personnel verify isolation of all energy sources and safe DC bus voltage before working inside the cabinet.

Manuals and related INVT pages

INVT VFD Documents · INVT User Manuals · INVT VFD drives · Goodrive350 · INVT brand home

Manufacturer PDFs · GD300-02 user manual V2.4 (English) · INVT industrial automation catalogue V2.0 (English). See Section 4.2.3 for mounting, Appendix C.3 for frame dimensions and Section 8.5 for faults. If you are considering a GD350-02 as a replacement, compare its own frame drawing and terminal diagram.