what is DC bus chokes?

Controlling current changes inside the drive
A DC-link choke, also called a DC bus choke or DC reactor, is an inductor connected in series with the DC intermediate circuit of a variable-frequency drive. It limits the rate of change of current. In a suitable drive design, it can reduce rectifier current peaks and mains current harmonics. It is not a general-purpose noise filter for the motor cable.
Locate it between the rectifier and inverter
The rectifier supplies the DC intermediate circuit from the AC mains. A choke may be placed in the positive or negative DC leg, or split between both. The DC-link capacitor is connected across the DC+ and DC− rails, rather than in series. The following IGBT inverter stage produces the PWM motor output; the choke does not replace this stage or feed the AC motor directly with DC.
External installation requires dedicated choke connections provided by the drive manufacturer. Brake terminals or an accessible common DC bus do not, on their own, establish that an external choke can be fitted.
Inductance changes the current slope
For an ideal inductor, vL = L × di/dt. With the same voltage across it, a larger inductance gives a slower current change. Here vL is the voltage difference between the inductor terminals, not the total DC-bus voltage. A choke resists a rapid change in current rather than blocking all current.
The upper diagram shows a typical drive arrangement. Below it, the same 10 V across the inductor produces a change of 10 A in 1 ms with 1 mH, or 2.5 A with 4 mH. These ideal examples explain the principle; they are not component-sizing results for a particular drive.
Why a DC choke can improve mains current
A capacitor-fed rectifier can draw short, high current pulses from the supply. Added DC-link inductance can limit the peaks and spread conduction over a wider interval. This can reduce THDi and individual harmonic components. The result depends on operating load, supply impedance, inductance and the complete drive circuit.
That does not make the choke equivalent to every harmonic-filter system. It cannot eliminate all harmonics or prove installation-wide compliance from one drive-terminal reading. Reduced distortion can improve true power factor, but the choke is not a power-factor-correction capacitor.
Ripple control and EMC need separate assessments
The choke and capacitor contribute to managing DC-link current and voltage ripple. Capacitor stress depends on the circuit and operating conditions, including supply unbalance. Do not assume that the choke removes all capacitor ripple current or every variation in bus voltage.
An EMI filter, EMC filter, RFI filter or zero-phase reactor addresses different interference requirements. Some split DC-choke arrangements can also help reduce high-frequency emissions, but this is not a universal property of every DC reactor. Sensor resets and communication faults require investigation of the noise source and coupling path.
Distinguish three different reactor locations
An AC line reactor sits ahead of the rectifier on the supply phases. A DC choke sits on its DC side and should not be assumed to provide the same rectifier protection against mains overvoltage. Its bus-voltage drop may be smaller than that of a comparable line-reactor solution, but voltage drop and losses are not zero.
An output reactor or motor-output filter serves its specified function between the inverter and motor. Do not connect a DC-link choke to U, V and W. It is not a substitute for measures addressing output dV/dt or carrier-frequency effects.
A useful specification includes more than millihenries
Check continuous and overload current, inductance under DC bias, saturation, insulation, winding resistance and thermal limits. As the core approaches saturation, its ability to limit current changes can fall. Lower winding resistance reduces copper loss; the component still dissipates heat.
More inductance is not automatically better. An oversized choice can increase losses and size, affect bus voltage and alter dynamic behaviour. Use the drive manufacturer’s compatible accessory specification, rather than selecting a choke from its mH value alone.
External terminals and factory links are model-specific
For example, some Mitsubishi drives connect a DC reactor between P1 and P/+, with the factory link removed as instructed. Do not apply those terminal names or procedures to other drives without verification. Brake-resistor and braking-unit connections serve different purposes. DC-link capacitors can retain voltage after isolation; observe the manual’s discharge time and verify absence of voltage before changing connections.
References
Schneider Electric: DC-choke circuit placement
Schneider Electric: AC reactors and DC chokes
Schneider Electric: advantages and limitations
Schneider Electric: unbalanced supply