Delta DVP02TUL-S

Delta DVP02TUL-S – Temperature control module with 2 inputs and 2 analog outputs

The Delta DVP02TUL-S is a right-side expansion module in the DVP Slim temperature module range. It has two universal inputs and two analog outputs. It reads thermocouples, RTDs and analog signals. It supports built-in PID control, manual output and analog output proportional to the measured value. The nominal supply is 24 V DC with a range of 20.4–28.8 V DC.

Sensor and analog output selection

Configure each input independently. Supported temperature sensors include Pt100 and Pt1000 RTDs, type J, type K and the other thermocouples in Delta's table. Celsius readings have a 0.1 °C increment. Analog inputs support 0–5 V, 0–10 V, 0–20 mA, 4–20 mA and the mV ranges listed in the manual. Standard voltage and current inputs have 16-bit resolution.

OUT1 and OUT2 are 12-bit analog outputs. Each channel can use 0–10 V, 0–20 mA or 4–20 mA. Use VO–AG for voltage output and IO–AG for current output. Delta specifies a load of 1 kΩ–2 MΩ for 0–10 V and up to 550 Ω for current output.

PLC compatibility, software and programming cable

Delta's programming manual lists the module as right-side ID H014F for DVP-SS2, DVP-SA2, DVP-SX2 and DVP-SE CPUs. Edit the host PLC program in WPLSoft or in a version of ISPSoft that supports the CPU and project. In ISPSoft, select the CPU connection through COMMGR. For the DVP-SS2 COM1 RS-232 port, use the UC-PRG020-12A with a USB port on the PC or the UC-MS020-01A with a serial port. For the USB cable, install its driver and select the resulting COM port. Check the exact CPU and port against the cable guide for other models.

CR addresses and 4–20 mA example

In the ladder program, CR#0 returns the model ID. CR#2 and CR#3 return the measured values (PV) for CH1 and CH2. For the first special module, FROM K0 K2 D100 K2 reads the two PVs into D100 and D101. In Celsius mode, 253 = 25.3 °C. CR#11 selects the input type and CR#37 selects the output range. Use K0 for 0–10 V, K1 for 0–20 mA or K2 for 4–20 mA. First select the basic setup page in CR#10, K0 for CH1 or K10 for CH2.

Use the proportional PV output to send a measurement to another device. If 0–100 °C is mapped to 4–20 mA, 50 °C → 12 mA. In PID temperature control, the output carries the demand needed to reach the setpoint. Decide whether the receiving device needs the temperature reading or the control demand.

On a long Pt100 run, a suitable three-wire connection reduces the effect of lead resistance. Check the type and polarity of thermocouples. Route sensor wiring away from motor and drive cables to reduce the effect of electromagnetic interference on readings.

Editor's Note

When buying used, read the full label. TUL-S has analog outputs, TUR-S has relay outputs and TUN-S has NPN transistor outputs.

Ask for photos of the removable terminal blocks and side expansion connector. Check the 24 V DC supply before testing.

Test both inputs in turn with the same known-good probe. If the reading is wrong, check the sensor type and wiring, then read the CR#43 error bits.

Test the current output on the bench with a multimeter and a suitable load. Checking 4, 12 and 20 mA shows both endpoints and the midpoint in 4–20 mA mode.

Back up the current settings before replacing the module. Put the controlled equipment into a safe test state before switching between manual output and PID control.