Delta DVP02TUR-S

Delta DVP02TUR-S — Two-Channel Temperature Control Module with Relay Outputs

The Delta DVP02TUR-S is a DVP Slim temperature control module with two universal inputs and four relay outputs. Each channel can be set up separately. An extruder can use a K-type thermocouple in one zone and a Pt100 in another, with separate heating and alarm outputs for each zone. The module runs the temperature loops while the PLC can monitor readings and manage setpoints.

Inputs, outputs and mounting

Inputs. CH1 and CH2 accept J, K, R, S, T, E, N, B, U, L, TXK (L), C and PL II thermocouples. Resistance temperature sensor options include Pt100, JPt100, Pt1000, Ni100, Ni120, Ni1000, Cu50, Cu100 and LG-Ni1000. Delta provides two- and three-wire diagrams for Pt100, JPt100 and Pt1000. Voltage and current ranges are 0–5 V, 0–10 V, 0–50 mV, −100 to +100 mV, 0–20 mA and 4–20 mA. Select the input type and temperature unit separately for each channel. See Pt100 vs thermocouple when choosing a sensor.

Relay outputs. CH1 uses OUT1 and OUT2 with common C0. CH2 uses OUT3 and OUT4 with common C1. Delta specifies 2 A per output and 3 A per common for resistive loads. The module manual specifies a contact voltage below 250 V AC or up to 30 V DC. Check the relay life curves for inductive loads.

Power and mounting. Use an external 24 V DC power supply. The supply range is 20.4–28.8 V DC. The housing measures approximately 25.2 × 90 × 60 mm, has removable terminal blocks and mounts on a 35 mm DIN rail. Both input channels are in the same isolation group.

PLC configuration, software and cable

Connect the module to the right-side expansion bus of a compatible DVP Slim CPU. Open the ladder program in the CPU-supported version of WPLSoft or ISPSoft. Use FROM to read module registers and TO to write them. For example, to connect to DVP-SS2 COM1 RS-232, use UC-PRG020-12A with a USB port or UC-MS020-01A with a PC serial port. For other CPUs, select the cable for the host’s PLC programming port.

Control registers. CR#0 returns model ID H034F. CR#2 and CR#3 hold the measured values PV for CH1 and CH2. CR#4 and CR#5 hold their setpoints SV. Write K0 to CR#10 to select the basic settings page for CH1 or K10 for CH2. On that page, CR#11 selects the input type, CR#16 selects the control mode and CR#17 and CR#18 assign output functions. CR#43 reports errors.

PC setup with TKSoft. Mount the DVP02TUR-S on the right side of a DVP02TK-S unit such as the DVP02TKR-S. Connect the PC to the TK unit’s RS-485 port through a USB-to-RS-485 converter such as the Delta IFD6500. Create a TK connection in COMMGR. In TKSoft, select the driver and station, then use Scan to find the TUR module. The TK unit holds the station address and serial settings.

Heating, cooling and alarm applications

The module supports automatic PID, manual PID, programmed PID and ON/OFF control. Each channel’s two outputs can be assigned to heating, cooling or alarm duties. On a packaging machine, each sealing jaw can have a heater output and a high-temperature alarm. On an oven, verify the sensor feedback signal before enabling the load and tuning the temperature loop.

Use a suitably rated contactor or solid-state relay to switch heater current in an oven, mould or dryer. For fast SSR cycling, drive the SSR from a suitable electronic output. See how temperature controllers work, PID control and PID control with a PLC for more on the control settings.

Editor’s Note

When buying used, ask for photos of the full model label, removable terminals and side bus connector. TUR and TUN housings look similar.

Check both inputs with a known sensor or simulator. A wrong thermocouple type, reversed polarity or incorrect Pt100 wiring can produce a plausible but inaccurate reading.

With heater power disabled, test OUT1–OUT4 individually. Use a suitable test load and a multimeter to verify each relay contact against its C0 or C1 common terminal.

If readings jump when a contactor closes or a drive starts, route sensor cables away from power wiring. Check the shield connection, grounding and sources of electromagnetic interference.

Set the switching cycle for the load and required contact life. Fit suitable circuit protection and an independent high-temperature cutout for the heater supply.

Back up the sensor types, setpoints, PID settings and alarm values before removal. On the replacement, test with heater power disabled and confirm the output response to a disconnected sensor.

Related topics and models

The DVP02TUN-S has four NPN transistor outputs. The DVP02TUL-S has two analog outputs. The DVP02TKR-S is the TK relay-output model with RS-485. For four measurement channels, see the DVP04PT-S RTD module and DVP04TC-S thermocouple module. See Derell temperature controllers for standalone units.

Delta DVP Slim temperature modules · DVP expansion modules · Delta DVP PLC series · Used Delta PLCs · Delta Automation

Manuals and wiring diagrams

Delta DVP PLC files

External references · Delta DVP module manual, chapter 9 · DVP02TUR-S instruction sheet in English and Turkish · Delta PLC and HMI cable selection guide