Delta DVP02TKR-S
Delta DVP02TKR-S | Temperature control module with 2 inputs and 4 relay outputs
The Delta DVP02TKR-S is an RS-485 remote temperature control module in the Delta DVP Slim temperature module family. It measures temperature or process signals on two channels. The four mechanical relay outputs can handle heating, cooling or alarm functions according to the channel settings. Typical applications include dryers, plastics machinery and industrial ovens with separately monitored heating zones.
Inputs, supply and relay outputs
The nominal supply voltage is 24 VDC (20.4–28.8 VDC). The module has removable terminal blocks and DIN rail mounting. Its two universal inputs accept thermocouples, RTDs such as Pt100 and Pt1000, 0–5 V and 0–10 V analog voltage, and 0–20 mA and 4–20 mA analog current. Temperature readings have 0.1 °C increments. Standard voltage and current input resolution is 16 bits.
The four relay contacts are grouped in pairs. OUT1 and OUT2 share C0, while OUT3 and OUT4 share C1. The instruction sheet lists load voltages of 240 VAC or 24 VDC. For resistive loads, the limits are 2 A per point and 3 A total per common. For inductive loads, check Delta’s load and relay contact life curves. Use a suitably rated contactor or solid-state relay for higher-power heaters and match its drive circuit to the module output.
TKSoft, COMMGR and RS-485 connection
Use TKSoft (TK Wizard) and Delta COMMGR to configure the module from a PC. Connect the PC’s USB port to the module through a USB-to-RS-485 converter such as the Delta IFD6500 and suitable RS-485 wiring. Create a TK connection in COMMGR and run auto-detection. In TKSoft, select that driver and the station number, then select Scan to find the module. Use WPLSoft or ISPSoft for the program of the compatible DVP CPU communicating with the module. Select the CPU programming cable for the exact CPU model.
The module supports Modbus ASCII and RTU. The default is ASCII, 9,600 bit/s, 7E1, station 1. Match the master’s serial settings to the module. The register for RS-485 parameters is 0x0F09, the ASCII/RTU setting is 0x0F0B, and the station number is 0x0F0C. When setting up PLC or HMI communications, start by reading CH1 PV at 0x0002 and CH2 PV at 0x0003. The setpoints CH1 SV at 0x0004 and CH2 SV at 0x0005 are readable and writable. These are Delta’s hexadecimal addresses. Check the driver’s address base and temperature scaling.
Sensor selection and temperature control
Verify each temperature sensor type and wiring scheme before commissioning. Pt100 sensors and thermocouples use different measurement principles. Follow the two- or three-wire diagram for the Pt100 and check the thermocouple type and polarity. With a 4–20 mA transmitter, set the analog input mode and scaling to match the transmitter. Route sensor wiring away from power cables and terminate the shield according to the cabinet’s grounding scheme.
For PID control, verify the measured value (PV) before setting the target (SV), heating or cooling direction, and output cycle. Short cycles shorten mechanical relay contact life. When designing PLC-based PID control, establish which device issues commands and how heating will stop if communication is lost.
Editor’s Note
When buying a used unit, check that the label reads DVP02TKR-S and that all removable terminal blocks are present.
On the bench, connect a known sensor or calibrator and verify the PV separately on both inputs.
A clicking relay can still have a bad contact. Check that all four outputs make and break with a suitable test load.
If the remote station does not respond, start troubleshooting with the supply, RS-485 terminals, station address, ASCII/RTU mode and parity.
Test the response to a disconnected sensor and an over-temperature condition under safe test conditions before enabling the heater. Use an independent high-limit controller where the process requires one.