Delta DVP08SM10N
Delta DVP08SM10N – 8 AC Digital Input Expansion Module
Delta DVP08SM10N adds 8 AC digital inputs to compatible Delta DVP Slim PLCs. It mounts on the right side of the CPU and provides 8 inputs and 0 outputs. Inputs X0–X7 use a single COM terminal. See DVP Slim digital modules for other models in the family.
AC input range and module power
The field inputs operate at 85–132 V AC, 50/60 Hz. Delta specifies 9.2 mA per input at 110 V AC / 60 Hz. The input thresholds are above 79 V AC for ON and below 30 V AC for OFF. Response times are under 15 ms from OFF to ON and under 20 ms from ON to OFF.
The host CPU supplies 24 V DC to the module electronics. Apply the AC field signal between the selected X input and COM. Keep 230 V AC mains off the input terminals. Treat the CPU and other DC devices as a separate 24 V DC supply circuit. The optocoupler detects the input, and the channel LED indicates its ON state.
Panel wiring and input checks
In a panel with a 110 V AC control circuit, a suitably rated limit switch or auxiliary contact can report position or operating status. Delta's diagram places the contact between the AC control source and the selected X input. The source return goes to COM. Check the control transformer secondary voltage and the circuit fuse against the panel diagram. Use the same AC control circuit for channels sharing COM.
If a solid-state relay (SSR) replaces a mechanical relay contact, account for off-state leakage. When the input stays ON without a command, check the voltage from X to COM and the switching device's leakage current. Routing control wiring away from motor and power cables helps reduce electromagnetic interference.
Addressing, software and cable
X0–X7 are local terminal labels. As the first digital input expansion on a DVP-SS2, X0–X7 map to PLC addresses X20–X27. Preceding modules can change the starting address. During commissioning, monitor the X address in the ladder program while operating the field contact.
Use WPLSoft or ISPSoft to load the program into the supported host CPU. For the DVP-SS2 COM1 RS-232 port, use UC-PRG020-12A for USB or UC-MS020-01A for a PC with a native serial port. Install the USB cable driver and select the assigned COM number. Configure the COMMGR channel for ISPSoft.
Related models
DVP08SM11N provides eight 24 V DC inputs. DVP16SM11N provides 16 DC inputs, and DVP32SM11N provides 32. DVP08SP11R combines four DC inputs with four relay outputs. In a 24 V DC sensor panel, check the NPN/PNP wiring and S/S common arrangement for the selected DC input module.
Editor's Note
On a used module, verify the 08SM10N label and COM marking. Check for loose terminals or signs of overheating before applying power.
Disconnect the machine wiring and use a protected bench circuit. Verify the 24 V DC CPU supply and AC control source separately.
If an input fails to respond, use a suitably rated multimeter to check the AC voltage from X to COM. If all channels stay off, check the shared COM and control-circuit fuse first.
Test each channel individually. Check that the terminal LED and the monitored CPU X address change together.
If a channel stays ON with the contact open, inspect the field wiring, SSR leakage and residual input voltage. Record the existing wiring and working X addresses before replacing the unit.