Delta DVP-F2DA
Delta DVP-F2DA – 2-Channel 12-Bit Analog Output Card
Delta DVP-F2DA is a two-channel analog output card for the function card slot of a compatible Delta DVP PLC. Each channel provides a 0–10 V DC or 0–20 mA output. Typical applications include sending a speed reference to an inverter or a command to a proportional valve driver.
Delta documents the card for DVP-EH, DVP-EH2 and DVP-EH3. Its programming manual also describes the card registers for supported DVP-SV2 CPUs. Confirm the exact host model and function card slot before ordering. The DVP-F2AD provides two analog inputs. The DVP-F2DA sends the PLC’s digital command to field equipment as an analog signal.
Output ranges and terminals
For CH0, use V0+ for voltage or I0+ for current. For CH1, use V1+ for voltage or I1+ for current. Both channels share analog COM. Use the terminal that matches the receiving input and connect the return to COM. The voltage receiver must present at least 1 kΩ. Total current-loop load must be 500 Ω or less.
The manufacturer’s command range for the 12-bit output is 0–4000. The nominal step is 2.5 mV for voltage or 5 µA for current. If the receiver expects 4–20 mA, scale the command to 800–4000 on the 0–20 mA output. A command of 800 gives 4 mA and 4000 gives 20 mA. Define the lower limit and fault command in the control project.
Select the drive’s analog input as its reference source and match the analog signal range in the drive parameters. Scale the controller percentage to the output command in a PID application. A potentiometer or a 0–10 V sensor uses a voltage input, and a 4–20 mA sensor uses a current input. Use suitable analog input and control hardware for feedback from a pressure sensor or other measurement device.
Programming, registers and cable
PLC programming takes place in the host using WPLSoft or ISPSoft, depending on CPU support. In the ladder program, D1116 → CH0 and D1117 → CH1 hold the output commands. For example, MOV K2000 D1116 produces nominal 5 V or 10 mA on CH0, according to the terminal used. The card sheet gives D1118 as the update interval in milliseconds, with a setting of K5 or higher. Check its function in the CPU manual. On CPUs that support D1149, a value of 9 identifies DVP-F2DA.
For standard EH3 and the SV2 CPUs listed in the cable guide, use UC-PRG020-12A between a PC USB port and the CPU’s COM1 RS-232 port. A PC with a serial port can use UC-MS020-01A. For EH/EH2, verify the cable and port against the exact CPU code. In panels using industrial communication or RS-485, label the analog reference wiring separately.
Related topics and cards
To reduce electromagnetic interference, route analog wiring away from motor wiring and relay coil cables. Follow the panel design for shield termination and protective grounding. When testing an analog speed command, check the drive run enable and emergency stop circuit separately.
DVP-F2AD is an analog input card. DVP02DA-E2, DVP04DA-H2 and DVP04DA-H3 are analog output modules for other series or mounting arrangements. Compare both the channel count and the CPU connection type. For a new panel, Derell PLCs and smart relays can also be considered as a separate control option.
Editor’s Note
On a used unit, inspect the F2DA label, card connector and V/I/COM terminal markings. The F2AD markings can look similar.
Isolate the CPU supply before inserting the card into the correct slot. After power-up, verify that the programming software detects it.
Test both channels at 0, 2000 and 4000. Measure voltage with a multimeter. Measure current in series with a suitable load, or check for 0, 2.5 and 5 V across a 250 Ω resistor.
If the unloaded voltage is correct but drops when the receiver is connected, check the input impedance, COM wiring and selected V/I terminal.
If the output changes unexpectedly, look for another instruction writing to D1116 or D1117.
For a 4–20 mA reference, test the 800 lower limit and the output behavior when the PLC stops and restarts.
PDF documents and series links
See our Delta DVP PLC files page for installation, terminal drawings and programming examples. Look for DVP-F2DA in the function card sheet and Analog Function in the programming manual.
DVP-F2DA · Function cards · DVP expansion modules · DVP PLC series · Used Delta PLCs · Delta Automation
External references
Delta DVP-EH Function Card, 2024 · Delta DVP-PLC Programming Manual · Delta PLC/HMI Cable Selection Guide