Delta AH32AN02P-5A
Delta AH32AN02P-5A 32-channel PNP digital output module
The Delta AH32AN02P-5A is a digital output module for the Delta AH500 PLC with 32 sourcing PNP transistor outputs. The removable terminal block has two output groups, 0.0–0.15 and 1.0–1.15. An active output supplies positive voltage to its load. Typical applications include driving 24 V DC control inputs within the rated current limits.
Load limits and UP/ZP wiring
The model-specific wiring diagram specifies 12–24 V DC for the outputs. Resistive load limits are 0.1 A per output and 1 A per common. Add the current drawn by loads sharing a common that can be on at the same time. For coil loads, use a driver interface whose input current is within the module’s output rating.
For the 24 V DC auxiliary supply, UP = +24 V and ZP = 0 V. Connect each load between its PNP output terminal and the group’s 0 V return. Check the UP/ZP connections for both groups against the model’s wiring diagram. See Delta AH power supplies for supply options.
Model variants and ISPSoft addressing
The AH32AN02T-5A uses sinking NPN outputs and a removable terminal block. The sourcing AH32AN02P-5B uses DB37, while the AH32AN02P-5C uses a latch connector. Check the full ordering code and connector type before replacing a module.
In Delta ISPSoft, use HWCONFIG to check the slot and starting Y address. The module occupies two consecutive 16-bit output groups. If the starting address is Y2.0, for example, the groups are Y2.0–Y2.15 and Y3.0–Y3.15.
Wiring diagram and PDF
Delta AH500 Hardware and Operation Manual · AH32AN02P-5A wiring diagram · English PDF · page 219, section 4.7.17. See PDF page 67 for current limits and page 301 for output addressing. Other documents are available in the Delta AH PLC PDF archive.
Editor’s Note
When buying a used card, read the full AH32AN02P-5A code and check that the removable terminal block is included.
Look for discoloration, loose screws or heat damage around UP/ZP.
Bench-test both sides of the terminal block separately with a resistive load of known current.
If the output LED is on and the load stays off, measure the group’s UP/ZP supply and the load’s 0 V return first.
Before replacing the card, record the starting Y address and the total current of loads that can run together.
Related topics
PNP output options include the AH16AN01P-5A and AH64AN02P-5C. NPN options include the AH16AN01T-5A, AH32AN02T-5B, AH32AN02T-5C and AH64AN02T-5C. For relay outputs, see the AH16AN01R-5A. For 32 digital inputs, see the AH32AM10N-5A.
AH expansion modules · Delta PLC accessories · Delta PLC software · Delta PLC · Second-hand Delta products
External reference · Delta AH500 Hardware and Operation Manual