Siemens 6ES5 456-4UA11 – 16-Channel AC Digital Output Module

Siemens 6ES5 456-4UA11 is a 16-channel triac AC digital output module for the SIMATIC S5 U range. Rated load supply is 115–240 V AC at 47–63 Hz, with an allowable range of 88–264 V AC. This S5 digital output module provides two galvanically isolated groups of eight outputs.

The output stage uses triacs for switching. Wire it for its specified AC output circuit rather than treating it as a dry relay contact. Its output construction differs from relay modules such as the 458-4UA11. Select the load and group connections from the exact UA11 diagram.

Channel current and four-output group limits

For resistive and inductive loads, fan-cooled operation allows 40 mA–2 A per channel and 6 A maximum per four outputs. Without a fan, the limits are 40 mA–1 A per channel and 4 A per four outputs. Check current at both channel and fuse-group level.

Four channels carrying 2 A each total 8 A, exceeding the fan-cooled group limit of 6 A. Base the load calculation on outputs that operate simultaneously. Lamp loads have a separate 2.5 A total limit per four outputs.

Fusing, leakage current and load checks

There is one 6.3 A fast fuse per four outputs. If a fuse opens, investigate the load and field wiring first. Short-circuit protection is conditional on the fuse; fitting a higher-rated fuse does not resolve the fault.

The specified off-state leakage is 5 mA maximum. This matters with very small loads and high-impedance measuring instruments. Assess switching with a suitable AC test load; an unloaded voltage reading alone is insufficient to diagnose a failed output.

Front connector, F+/F− and field wiring

The F+/F− enable circuit uses a jumper in the front connector. Check connector seating, the jumper and channel terminals against the diagram. Preserve the two groups’ supply arrangement when replacing S5 cables and connectors.

Inspect grounding and shield connections against the panel drawings. Include load wiring, loose connections and cable routing when investigating electromagnetic interference. Isolate the AC load supply and verify absence of voltage before wiring or removal.

S5 installation and address checks

Check the U-format card against the actual central or expansion unit, rack and slot arrangement in the Siemens S5 system. Its digital section draws 100 mA typical from the 5 V system rail; assess this separately from AC load current when reviewing the power supply.

In an expansion unit, also inspect the interface module and bus connections. The card’s address switch must match the output addresses in the PLC program. During troubleshooting, check the program command, front connector and actual load current separately.

UA11 and UA12 revision differences

The manuals provide shared rating tables for 6ES5 456-4UA12 and UA11, but enable-mode selection using X20 applies to UA12. Do not transfer that jumper procedure to UA11. Check the full order number, hardware revision, front connection and existing panel drawings before selecting a replacement.

Editor’s note

Start with the complete label. This card has triac AC outputs, so treating it as a relay-contact card leads to the wrong wiring assumptions. Take a moment to compare the existing connections with the diagram before moving the connector.

The 2 A marking is only part of the picture. Is the fan running, is airflow clear, and how many loads share the group? Check these before applying the full load. A stopped fan can put an otherwise sound card under excessive thermal stress.

If four outputs stop together, pause before condemning the whole card. Check the group supply and fuse first. If the fuse opens again, find the load-side cause before continuing to replace it.

An off-state voltage reading can be misleading. Consider leakage current and the connected load, then verify operation with a suitable test load. This is particularly relevant to small indicators and electronic inputs.

When buying a used Siemens card, look beyond illuminated LEDs. Check all sixteen channels under load, group fuses, connector condition and heating. Use the exact model’s instructions, and keep the UA12 jumper procedure separate from UA11 testing.

OtomasyonAVM resources and PDFs

+ S5 digital output modules · About Siemens S5 PLC

+ Siemens S5 shared PDF archive and operating manuals. For the exact UA11 version, use the U Periphery technical table headed 456-4UA11 / 456-4UA12.

Related topics

+ 6ES5 456-4UA12: revision and enable-jumper comparison.

+ 6ES5 458-4UA11: a relay-output module with different output construction; do not assume direct interchangeability.

+ What is a triac? · What is a fuse?

Browse SIMATIC S5

+ S5 digital output modules · S5 racks · SIMATIC S5

+ Siemens S5 PLC · Siemens second-hand equipment

Siemens and external references

+ Siemens U Periphery – English; 6ES5 998-0PC22, Release 01. B8576312-06, §5.14; printed pages 64–65 / PDF pages 267–268 cover the exact UA11 and UA12 ratings and wiring. Enable operation is explained in §1.3.5 / PDF page 217.

+ Siemens S5-135U/155U System Manual – English; C79000-G8576-C199-07. §8.4.14, printed pages 8-58–8-59 / PDF pages 372–373 provide UA12 revision comparison data, rather than an exact-code replacement for the UA11 instructions.