6ES5 375-0LA21
Siemens 6ES5 375-0LA21 SIMATIC S5 375 EPROM Memory Submodule
The Siemens 6ES5 375-0LA21 is a memory submodule for SIMATIC S5 with 16 KB (2 × 8 KB) of EPROM storage. Siemens specifies BYTE organization and programming number 12. The module retains its contents when power is off. Use a suitable UV eraser to clear the EPROM before writing it again.
The submodule stores the control program in a supported PLC, or serial port settings and message text in a CP 521 SI. Siemens lists this exact order number in the S5-115H memory table for the CPU 942H and in its S5-115F and S5-95F manuals. The host CPU or CP determines which files and data belong on the module.
How does the 0LA21 differ from similar submodules?
The 6ES5 375-0LA15 is an 8 KB EPROM with programming number 11. The 6ES5 375-0LA41 is a 32 KB EPROM with programming number 17. The 6ES5 375-1LA21 is a CMOS EPROM with the same 16 KB capacity. The Siemens CP 521 SI table assigns it programming number 412. Use the full order number on the label when setting up the programmer.
The 6ES5 375-0LC41 is a 16 KB electrically erasable EEPROM, while the 6ES5 375-0LD21 is a 16 KB RAM submodule. Each type has its own programming, erasing and retention requirements.
How do you check CPU or CP compatibility?
Start with the full S5 CPU order number and its memory table. For a S5-115U CPU 943 or a S5-100U CPU 103, check the manual for that CPU. The 16 KB submodule capacity and the CPU’s working memory capacity are separate specifications.
The manual that also covers the CP 521 SI 8MA22 lists the 0LA21 among the older EPROMs it can use. On the CP, DB1 holds serial settings and DB2–DB63 can hold printer messages. These blocks belong to the S5 communications processor application and are maintained separately from the CPU control program.
The S5-115H manual requires the same order number for the memory submodules in both CPUs. On an S5-95F or S5-115F, follow the relevant safety manual for replacement and commissioning.
How is the EPROM prepared?
Back up the running program or CP data with the STEP 5 project. Select BYTE / 12 on the compatible PG and EPROM programming hardware. When reusing a programmed module, run a blank check after UV erasure. After writing, read back the contents and verify them against the source file.
Use an S5 connection cable, such as the 734-2 PG cable, to make an online backup from the PLC. Siemens lists the PG 635, PG 675, PG 685, PG 695 and PG 750 for EPROM programming. Write the EPROM in the programmer’s memory socket or with the appropriate adapter.
Editor’s note
Photograph the full label. The 0LA21 and 1LA21 have the same capacity and are easy to confuse. Record the order number and the programming number selected on the PG.
Read the contents before erasing. The old EPROM may be the only surviving copy of the machine program. Save the readback with the machine name and date.
Check the data blocks separately. Parameters and counter values that changed while the S5 PLC was running may differ from the old EPROM image. Record the current values needed for the replacement.
Switch off the host before inserting or removing the module. Check the orientation against the slot markings. On first power-up, follow the host manual to verify loading and operating status.
Ask for the spare’s test record. The full order number, blank-check result and post-write verification show which checks the module has passed.
OtomasyonAVM resources and PDFs
SIMATIC S5 memory submodules · Siemens S5 hardware and STEP 5 guide
OtomasyonAVM S5 system manuals and PDF archive
Related topics
6ES5 375-0LA15 8 KB EPROM · 6ES5 375-0LA41 32 KB EPROM · S5-115H CPU 942H · CP 521 SI 6ES5 521-8MA21
S5 navigation
Siemens S5 PLC · SIMATIC S5 · S5 memory cards
External references
Siemens S5-115H system manual, memory submodules, Table 1-1 (English PDF)
Siemens CP 521 SI manual, EPROMs and programming numbers, Table 2-2 (English PDF)
Siemens S5-95F manual, EPROM submodules, Table 2-8 (English PDF) · Siemens S5-115F system manual, memory accessories, Section 2.3 (English PDF)