6ES5 436-7LC11

Siemens 6ES5 436-7LC11 — 8-Channel 230 V UC Digital Input Module

The Siemens 6ES5 436-7LC11 is an 8-channel, 230 V UC (AC/DC) digital input module in the SIMATIC S5 family. The inputs use optocouplers and are galvanically isolated in groups of one. Siemens ST 50 lists the module for S5-115U/H/F systems.

When monitoring field signals from relay or contactor auxiliary contacts, check the circuit's voltage class and wiring diagram. This model accepts 230 V AC and DC signals; the specified frequency for AC operation is 47–63 Hz.

Signal thresholds and input current

The defined ranges are 0–100 V for signal “0” and 170–264 V for signal “1”. Compare multimeter readings with these thresholds. Typical ON-state input current is 16 mA AC or 2.2 mA DC.

Response times and two-wire sensors

Response time is 2–13 ms for 0→1 and 10–25 ms for 1→0. Allow for these delays in the PLC input/output evaluation and program. The manufacturer permits two-wire BERO sensors; include the table's 5 mA quiescent-current information when selecting a sensor.

Isolation and phase restriction

Individual input isolation does not permit different supply phases. The footnote for this exact model explicitly states that connecting different phases is not permissible. Match each input pair to the existing L1/L+ and N/M wiring diagram.

Front connector and cabling

The 46-pin front-connection options include the screw-terminal 6ES5 490-7LB21 and crimp-terminal 6ES5 490-7LA11. Check the front plug and wiring alongside the S5 rack arrangement. Disconnect PLC and field supplies before working on the module or front plug.

The manufacturer table specifies cable lengths of 1000 m shielded and 600 m unshielded. Assess routing, grounding and electrical interference together.

Fault finding and related models

During debugging, check the field signal, input return connection and project address in sequence. The 436-7LA11 has 16 inputs isolated in groups of four; the 436-7LB11 has 16 inputs in groups of two. The 435-7LC11 has eight inputs but is rated 115 V UC. Verify the complete code and wiring arrangement before replacement.

Editor's note

Keep both details in mind: there are eight individually isolated inputs, and different phases must not be mixed. Read the isolation specification together with the manual's phase restriction.

If an input behaves intermittently, first compare its voltage with the signal thresholds. A reading between 100 and 170 V should not be casually treated as a defined “0” or “1”.

AC and DC share the UC designation, but their input currents differ. With a two-wire sensor, take time to check OFF-state current and the actual signal voltage.

Inspect the spare board's front plug too. Confirm each L1/L+ and N/M return pairing instead of copying a neighbouring channel's connection from memory.

When checking a used board, test all eight inputs with both rising and falling signals. Keep the results with the S5 system information to make the next maintenance visit easier.

OtomasyonAVM resources and PDFs

+ Siemens S5 pages and the OtomasyonAVM S5 PDF archive.

+ S5-115H manual — our PDF copy, English: exact 436-7LC11 table on 17-22/PDF page 454.

+ The exact model's technical table and terminal drawing appear in S5-115U Manual, page 15-30. Model and connector ordering information appears in Siemens ST 50, page 3/32. Both documents are in English.

Related topics

+ 436-7LA11 · 436-7LB11 · 435-7LC11 · 490-7LB21 · 490-7LA11.

Browse SIMATIC S5

+ S5 digital input modules · SIMATIC S5 central controllers · Siemens S5 · Used Siemens equipment.

Siemens and external references

+ Siemens S5-115U Manual — EWA 4NEB 811 6130-02b: English, page 15-30/PDF page 558; exact LC11 table, terminal drawing and prohibition on different phases.

+ Siemens ST 50 Catalog — 1998: English, page 3/32/PDF page 118; S5-115U/H/F coverage and 490 front connectors. An externally archived manufacturer catalog.