The Siemens 6ES5 375-0LD21 is a writable 16 KB (16,384-byte) RAM submodule in the SIMATIC S5 375 memory range. The S5-115U manual lists it as byte-organized memory for CPU 941 and CPU 942. The CP 521 BASIC manual gives the same capacity as 2 × 8 KB.
In a compatible CPU, the submodule can hold the STEP 5 application and support program testing during commissioning. It uses volatile RAM, so retaining the contents through a power outage depends on the host device’s memory backup supply.
Use in the S5-115U, S5-115H and S5-115F
Table 2-8 of the S5-115U manual marks the 0LD21 for the CPU 941-7UB11 and CPU 942-7UB11. The same manual explains that the CPU 943 and CPU 944 provide their RAM capacity internally. Match a spare to the full order number on the installed CPU.
The S5-115H manual also lists the 0LD21 for the redundant system built around the CPU 942H. Siemens specifies matching memory submodule order numbers in both CPUs. The S5-115F manual lists the 0LD21 in its test-mode table and provides a separate memory table for safety operation.
What it stores in a CP 521 BASIC
The CP 521 BASIC, one of the S5 communications processors, can use the submodule to store a BASIC program or initialization parameters. Keep a separate copy of the BASIC program and the serial settings alongside the CPU’s STEP 5 backup.
Siemens used the CP 521 name for several processors. The CP 521 SI 6ES5 521-8MA22 has its own memory compatibility table. Check the front label for the BASIC designation and the full processor order number.
Program retention through a power outage
On the S5-115U, the backup battery is on the power supply side. The CP 521 BASIC has its own backup battery. If the machine loses its program after a power outage, begin fault diagnosis by checking the battery indication and memory backup status on the relevant device. Use the device manual to identify the correct replacement lithium battery.
Back up a running CPU using a compatible SIMATIC S5 programmer and PG cable. Before removing the submodule, open the saved project and verify that its blocks can be read. The EPROM programming number field is blank in the 0LD21 table entry.
Capacity and memory type across related models
The 6ES5 375-0LD11 is the 8 KB RAM version and the 6ES5 375-0LD31 is the 32 KB RAM version. The S5-115U table marks that 32 KB RAM submodule for the CPU 942 only. The 375-1LA21 EPROM and 375-0LC41 EEPROM both hold 16 KB and retain their contents without power. Each uses its own programming method.
Editor’s note
Record both labels. Photograph the 6ES5 375-0LD21 label and the full order number of the CPU or communications processor that holds it.
Back up the program before removal. Save the copy read from the running machine with the machine name and date. Open that copy and check its blocks before relying on it in the workshop.
Record what happens after a power outage. If the program disappears only when power is lost, the battery indication and the memory backup circuit are the first places to check.
Compare both sides of a redundant system. On an S5-115H, read the memory label on each CPU. Confirm the full order numbers even when the capacities match.
Ask what a used module was tested for. Check whether a compatible device recognized the module and whether the test covered both writing and reading. Keep any test file separate from the machine’s program backup.
OtomasyonAVM resources and PDFs
S5-115H system manual, Table 1-1 · OtomasyonAVM S5 PDF archive · About the Siemens S5 PLC
Related topics
S5 memory submodules · How EPROM works · CP 521 BASIC
Site navigation
Siemens Automation › Siemens S5 PLC › S5 memory cards
External references
Siemens 6ES5375-0LD21 data sheet – 16 KB RAM (PDF)
Siemens S5-115U manual – memory and CPU compatibility, Table 2-8 (PDF)
Siemens CP 521 BASIC manual – memory submodules, Table 2-2 (PDF)
Siemens S5-115F manual – test-mode memory submodules, Table 2-4 (PDF)