6ES5 410-0AA12
Siemens 6ES5 410-0AA12 – 28-Output, 24 V DC Module for S5-010W
The 6ES5 410-0AA12 is a solid-state digital output module for the SIMATIC S5 S5-010W. It combines 24 outputs rated at 24 V DC / 0.8 A and four outputs rated at 24 V DC / 2 A, giving 28 outputs in total. Part of the S5 digital output range, it switches DC field loads under CPU control.
The permissible load supply range is 20–30 V DC. The two output classes have different current ratings and protection arrangements. Size the power supply for the actual load distribution. Placement in our S5-90/110 module category does not establish interchangeability with S5-90U or S5-110 hardware.
Protection of the 0.8 A and 2 A outputs
Each of the 24 outputs rated at 0.8 A has electronic short-circuit protection. The four 2 A outputs use FF 2.5 A / 250 V extra-fast fuses, designated FF 2.5/250 G in the Siemens manual. Find the load or wiring fault before replacing a fuse; a slow-blow fuse with the same current rating is not equivalent.
When selecting an interface relay or contactor, check the coil's continuous current and inrush. Do not transfer a 2 A channel's load to a 0.8 A output. Short-circuit protection does not replace correct load selection.
Simultaneity and inductive loads
The Siemens technical table specifies 50% simultaneity for the 0.8 A outputs and 100% for the 2 A outputs. In particular, do not load all 24 of the 0.8 A outputs at rated current simultaneously. Do not treat this percentage as a PWM duty-cycle specification.
The manual's descriptive section specifies a maximum switching frequency of 1 Hz for inductive loads at rated current. Check the coil's operating rate accordingly. The technical table gives a maximum off-state residual current of 1 mA; check the off-state response of low-current electronic loads.
S5-010W mounting and 48-pole front connection
Select the module for the S5-010W's own housing and slot arrangement. Field power and signals pass through a 48-pole front connection. Compare the wiring assembly, connector locks and grounding/M reference with the project and equipment diagram. Pole count alone is insufficient for choosing a connector from another S5 family.
Coding jumpers and output addresses
The address area is selected by coding jumpers on the card. In Siemens' first coding option, the 2 A outputs use A1.0–A1.3 and the 0.8 A outputs use A2.0–A4.7. Other jumper settings change the addresses. Match the PLC program to the existing card's actual setting.
Check the 400-0AA11 input/timer module and any digital input feedback against the project too. During troubleshooting, consider the output address, current class and field supply together. The system uses the 500-7AA11 PG interface for its programming connection.
Comparing similar ordering codes
The 410-0AA41 is a different S5-010W card with 16 outputs rated at 2 A. The 410-7AA11, 450-8MB11 and 417-7AA21 have different system requirements, ratings or output technologies. The “410” designation or a 24 V rating alone is insufficient for replacement selection. Compare the complete code, jumper setting and front-wiring photograph. Disconnect system and load supplies before removal or installation.
Editor’s note
The output count is easy to misunderstand on this card. There are 24 outputs rated at 0.8 A alongside the four 2 A outputs. Mention both groups when requesting a spare; describing it only as a four-output card can send the search in the wrong direction.
If an output does not work, establish which group it belongs to first. Checking a fuse on the 2 A side is different from checking electronic protection on the 0.8 A side. That small distinction can save time during fault-finding.
Do not fit a larger fuse just to see whether the circuit will run. Check the coil, wiring and channel selection first. The FF fuse's speed characteristic matters as well as its current rating.
Photograph the jumpers and wiring before removing the old card. Even a healthy replacement of the same model will operate the wrong addresses if its coding differs. Keeping the original settings makes installation easier.
Where practical, have all 24 lower-current outputs and all four 2 A outputs checked with suitable loads. Inspect the connector, locks and fuse holders too. One working channel does not establish that the whole card is healthy.
OtomasyonAVM resources and PDFs
+ Our S5-90 PDF page: other S5 documentation. The technical source for this model is the S5-010W manual below.
+ S5 digital output modules · S5-90/110 module category · S5 cable types
Related topics
+ 410-0AA41 · 410-7AA11 · 450-8MB11 · 417-7AA21: output classes and system comparisons.
+ 400-0AA11 input/timer module · 500-7AA11 PG interface · PLC troubleshooting
Browse SIMATIC S5
S5 digital output modules · S5 racks · Siemens S5 PLC · Used Siemens equipment
Siemens and external references
+ Siemens S5-010W Operating Instructions – German, GWA 4NEB 807 1021-01a: exact-code description, printed p. 6 / PDF 8; specifications, p. 10 / PDF 12; front connections, p. 12 / PDF 14; jumpers and fuse locations, p. 18 / PDF 20; address table, p. 19 / PDF 21; spare-parts list, p. 24 / PDF 26.