6ES5 921-3UA11

Siemens 6ES5 921-3UA11 – S5-135U CPU 921 S processor

Siemens 6ES5 921-3UA11 is the CPU 921 S processor for SIMATIC S5-135U. This central processing unit in the Siemens S5 PLC family is designed primarily for binary signal processing and sequential control. It supports up to 64 Kbytes of plug-in user RAM or EPROM, alongside approximately 7.4 Kbytes of integrated DB-RAM.

Typical applications include conveyor sequencing, machine interlocks and step control in existing S5-135U installations. Field signals connect through separate I/O modules; sensor PNP/NPN requirements and operating voltages depend on those modules.

Programming and processing characteristics

The programming language is STEP 5, using LAD, CSF/FBD or STL representations. Siemens' comparison table gives an average of 1.3 ms for 1 K binary instructions and 45 ms for 1 K word load/transfer instructions. These are comparison figures; the complete machine scan depends on program content and system activity.

The CPU supports 2048 flag bits, 128 timers and 128 software counters. Software counters should not be treated as dedicated high-speed encoder input channels. A PLC programming backup should preserve program and data blocks together.

RAM, EPROM and data memory

The user program resides in a front-mounted 376 EPROM or 377 RAM submodule. Maximum capacity is 32 Kwords × 16 bits = 64 Kbytes. This does not mean every used CPU includes a 64 Kbyte memory submodule; check the installed S5 memory module label.

The integrated 7.4 Kbyte DB-RAM is a separate data area from the plug-in program memory. Battery condition and backup arrangements matter when retaining RAM data during a power interruption. Additional modules and memory submodules serve different purposes, so establish exactly which parts a listing includes.

Rack positions and multiprocessing

CPU 921 supports single-processor operation or S5-135U configurations with up to four CPUs. In the manual's layout, a single CPU occupies slot 11; multiprocessing uses positions 11, 27, 43 and 59, populated consecutively from 11. These positions refer to the specified S5-135U rack and should not be transferred to another rack family without checking.

A suitable 923A coordinator or 923C coordinator manages bus access during multiprocessing. Each CPU's I/O and IPC flag assignments must be defined through DB1 address lists. CPU 921 does not support the special multiprocessor communication functions for transferring entire data blocks through the 923C; installing the coordinator does not add that support.

Addresses for digital inputs, digital outputs and analog signals must match the program. Check interface modules and expansion racks as part of the existing system configuration.

Programmer connection and version distinction

The front panel provides a 15-pin serial PG connection, specified at 9600 bit/s. Use the appropriate S5 programming cable and programmer setup. Keep the PG connection distinct from interfaces provided by separate communication modules.

There is an important difference between 3UA11 and 3UA12: the manual describes online PG access through the 923C, without moving the cable between CPUs, for 6ES5 921-3UA12. Do not automatically assign that feature to 3UA11. The general designation “CPU 921” is insufficient for selecting a replacement.

Supply and mechanical specifications

The CPU receives 5 V DC ±5% through the rack and has a typical current consumption of 3 A. Dimensions are 20.32 × 233.4 × 160 mm, with an approximate weight of 0.5 kg. Include memory and other modules when assessing PLC power supply capacity.

The protection rating is IP00 and the permitted operating temperature is 0–55 °C. Check cabinet ventilation, connector condition and grounding when investigating unstable operation in an ageing installation.

Indicators and comparison with other processors

The front panel shows RUN/STOP states and QVZ, ADF, ZYK and BASP indications. QVZ identifies missing peripheral acknowledgement, ADF an addressing problem, ZYK an exceeded cycle time and BASP disabled output commands. During fault finding, assess the stopping conditions together with programmer diagnostics.

6ES5 922-3UA11 is the R processor intended for word processing and computation; it is a different processor. 6ES5 928-3UA11 belongs to the separate CPU 928 family. Verify program and system compatibility before considering either as replacement hardware. Further background is available in About Siemens S5 PLC.

Editor's note

Start with a readable photograph of the complete 3UA11 label. A seller's general “921” description is not enough to establish 3UA12 features, particularly PG access through the coordinator.

If the front memory socket is empty, do not assume the working program is already inside the CPU. Ask for the RAM or EPROM order number, its capacity and confirmation that it is included.

Back up the program and data blocks before removing hardware, and record DB1 assignments in a multiprocessor installation. OVERALL RESET erases and initializes all RAM areas; preserve a usable backup before considering it.

A flashing STOP indicator does not by itself prove CPU failure. Examine memory, battery backup and restart conditions. For QVZ or ADF, check the affected module's supply, address and rack position as well.

A RUN indicator is only part of a useful test. Check PG access, cyclic execution of a known program and the relevant I/O behaviour in a suitable test setup. Test multiprocessing separately if that is how the unit will be used.

When buying used Siemens equipment, request complete labels and a test record. Disconnect rack power before removing or inserting the CPU or memory submodule, and inspect rear connectors, handles and evidence of earlier repairs.

OtomasyonAVM resources

Browse the 6ES5 921-3UA11 model page, used Siemens S5 models, S5 processors and memory modules. The Siemens manual covering this version is provided in the external reference section.

Related topics and models

+ 6ES5 921-3UA12: another S processor version; check the distinction in PG access through the 923C.

+ 6ES5 922-3UA11: the R processor with an emphasis on word processing.

+ 6ES5 923-3UA11: the 923A coordinator used in multiprocessor systems.

+ 6ES5 923-3UC11: the 923C coordinator; available functions depend on the CPU version.

+ 6ES5 928-3UA11: a comparison with the separate CPU 928 family. These links do not establish replacement compatibility.

Navigation

S5 CPUs · Memory · Racks · Cables · Interfaces · Communication · Used Siemens equipment

Manufacturer document and external reference

+ Siemens S5-135U CPU 921/922 Manual – 6ES5 998-0UL22, English: product identification on PDF page 3; capacity and comparison on 14–15; CPU 921 application and 3UA12 distinction on 126; memory on 128–129; specifications on 131; slots and DB1 on 132; indicators and reset on 133–137. These are physical PDF page numbers.