6ES5 928-3UA11

Siemens 6ES5 928-3UA11 CPU 928 — SIMATIC S5 Central Processing Unit

Siemens 6ES5 928-3UA11 is the CPU 928 central processing unit used in S5-135U systems. It executes STEP 5 programs in the SIMATIC S5 family, supporting control applications combining bit and word operations. Assess this S5 CPU by its complete order code and operating-system version.

928-3UA12, 928-3UA21 and the CPU 928B models 928-3UB11, 928-3UB12 and 928-3UB21 are different versions. The shared “928” designation does not establish unchanged program, memory or communication compatibility. Compare the installed label, program and peripherals before selecting a replacement.

Program limits specific to 3UA11

Siemens’ CPU 928 comparison specifies a maximum block nesting depth of 30 and a maximum permitted scan time of 4000 ms for 3UA11. The same section gives 62 and 6000 ms for 3UA12; those are not this order code’s specifications. 4000 ms is neither a normal operating scan time nor a recommended monitoring setting.

For a program transferred from another CPU, examine the call structure, instructions and error-handling blocks. Operation on a later version does not establish identical operation on 3UA11. Record the intended CPU version, particularly on older installations where the processor may previously have been replaced.

Memory, rack and power-supply checks

Record the exact user memory submodule code and whether it is RAM or EPROM. Check program storage, data blocks and retention separately; one advertised KB figure does not describe all three. Identify the memory supplied with the CPU and whether a program is present.

Test with a suitable S5 rack and power supply. Inspect module seating, rear connectors, supply indicators and battery condition. Back up the program and current data blocks before interrupting power or removing memory. Illuminated CPU indicators alone do not establish program retention.

PG connection and HMI compatibility

Use a PG cable suitable for the TTY interface; connector resemblance does not make an ordinary RS-232 cable suitable. Record existing communication connections, converters and software settings. Evaluate programmer access separately from operator-panel compatibility.

Siemens ST 80 · 2009 excludes 6ES5 928-3UA11 from the AS511 connection specified for WinCC flexible Runtime and from the described PROFIBUS DP + HMI connections through IM 308C/CP 5431. This limitation concerns those catalogue connection options. Assess an existing panel or another communication solution against its own driver and documentation.

Function modules and installation testing

Check the standard FB version used with position-control and function modules. Siemens’ IP 241 manual specifies a special cold-restart condition before the standard FB call when using CPU 928-3UA11 operating system V1.0. This application-specific note is not a universal setting for every CPU program.

Compare digital inputs, digital outputs and analog modules with their programmed addresses. Read special-module fault states separately. For an older Siemens S5 installation, verify actual I/O exchange and communication with connected equipment as well as successful entry into RUN.

Editor’s note

The 3UA11 suffix matters. Before buying a “928 CPU”, check the complete code. Assuming the program and communication features of a later version can complicate the replacement.

Keep the 30-level nesting limit and 4000 ms maximum in view when examining a transferred program. Establish CPU version and program structure first; increasing the monitoring time is not a substitute for diagnosing a stop.

Back up the program and current data blocks before shutting down a system with a battery warning. A fitted memory submodule alone does not establish protection of all operating values.

If the panel does not communicate, check its driver and connection route before condemning the CPU. Siemens’ HMI table contains an explicit exception for this exact order code.

Ask for photographs of the label, memory receptacle and connectors. Establish which rack was used to read the program, which functions were tested and whether memory is included. Illuminated LEDs and operation on a machine are different test results.

OtomasyonAVM resources and PDFs

+ 6ES5 928-3UA11 product and information page, S5 CPU pages and Siemens S5 models.

+ OtomasyonAVM SIMATIC S5 PDF archive. Check the order code on CPU 928 documents; do not apply entire 3UA12 tables to 3UA11.

Related topics

+ 928-3UA12, 928-3UA21, 928-3UB11, 928-3UB12, 928-3UB21 and S5 memory submodules. These links support version comparison, rather than establish direct replacement compatibility.

Browse SIMATIC S5

S5 CPU  |  SIMATIC S5  |  Programming cables  |  Siemens second-hand homepage

Siemens and external references

+ Siemens S5-135U / CPU 928 manual, Russian — CPU 928 programming section C79000-B8500-C633-01, printed page 1-8 / PDF page 108: explicit 3UA11/3UA12 comparison. The document cover identifies 3UA12.

+ Siemens ST 80 · 2009, English — third-party archive copy — printed pages 2/149–2/150: SIMATIC S5 connections and the exact 3UA11 exception.

+ Siemens Digital Position Decoder IP 241 with FB 156/157/158, 6ES5 998-0KD21, English — section 9, printed page 9-10 / PDF page 130: application-specific startup condition for CPU 928-3UA11 V1.0.