6ES5 905-3RB21

Siemens 6ES5 905-3RB21 — S5-105R-B CPU 905, 1000 program elements

Siemens 6ES5 905-3RB21 is the CPU 905 central processing unit with a capacity of 1000 contacts/program elements for the S5-105R-B system. This Siemens S5 central processor handles small automation tasks based on relay-control logic. 1000 contacts describes program capacity, not physical terminals.

6ES5 905-3RB11 has a capacity of 500 program elements. Compare program size and the fitted memory submodule when assessing RB11 against RB21.

Programming: PG 605R / PG 655R and ladder diagrams

S5-105R is programmed with a PG 605R or PG 655R using KOP/LAD ladder diagrams. Plan PLC programming around equipment suitable for this system. Ladder logic follows the contact-and-coil relationships familiar from relay control circuits.

The programming manual defines up to 64 program blocks, PB 0–63, with up to 16 rungs per block. Block and rung limits are separate from the processor’s total capacity of 1000 program elements.

Resources include 16 counters, 32 timers, 48 flags and four sequence cascades. When reviewing timer logic, record both the preset and time base. Trace set and reset conditions through the complete program when examining latching functions.

I/O capacity and addressing

The system can address up to 64 inputs and 64 outputs, and the 105R-B has eight I/O slots. Actual channel counts depend on the fitted combined I/O boards. Match digital inputs and digital outputs to their program addresses, slot numbers and cabinet labels.

The first address component identifies the slot: I 0.5 is input 5 in slot 0, while Q 7.6 is output 6 in slot 7. Check the voltage version of peripheral boards such as 6ES5 488-3LA11; a shared family designation does not establish a shared field voltage.

Internal program memory and backup

The CPU can execute a program from internal memory; EPROM or EEPROM submodules provide long-term storage. Select S5 memory submodules by their suitability for 105R and the required capacity. When examining the listed 6ES5 375-0LA11 EPROM submodule, verify its contents and the CPU capacity as well.

S5-105R contains no battery. Internal program retention after power-down is nevertheless limited. Do not assume a processor left on a shelf still holds its program. Keep a readable backup and a record of suitable external memory. Preserve existing contents before inserting memory or clearing a program.

Power, installation and programmer connection

The technical table specifies 5 V / 700 mA for the CPU. Inspect the S5 housing and rack arrangement and power supply against the system drawings. The mains rating belongs to the power supply and must not be interpreted as a direct processor connection.

Disconnect the 105R completely from its supply before removing or inserting the CPU. Record the programmer type and cable/connector arrangement. The adapter used to write EPROMs is separate supporting equipment.

RUN, STOP, HOLD and test scope

The system has RUN, STOP and HOLD modes. HOLD permits single-scan investigation through the programmer. Test functions that enable outputs can operate connected contactors or valves, so account for their actual response.

For PLC debugging, record the programmer’s PC DIAGNOSTIC message together with LED states. RUN is also possible with erased program memory. A green indicator alone does not establish that the application program is present or the machine is ready.

Editor’s note

Start with a clear label showing 905-3RB21 and its 1000-element capacity. In S5 maintenance, similar appearance is not enough to dismiss the capacity difference from RB11. Record which CPU and memory the existing program uses.

Do not begin by looking for a replacement battery: this system has none. Establish whether the program is readable and backed up. Do not plan production around the assumed contents of a processor that has been unpowered for a long time.

A demonstrated connection with PG 605R or PG 655R is useful evidence. Ask to see the program displayed and relevant inputs monitored, rather than only watching the equipment power up.

Treat a green RUN light carefully because erased memory can still permit RUN. Separate bench checks from tests using the machine application. Identify the program used and the inputs and outputs actually checked.

Photograph the memory-submodule number and program label before insertion. Do not experiment with erase or store commands; writing the wrong contents could lose the last available working program.

When buying used Siemens equipment, assess the CPU, memory, programmer and test record separately. Control the loads before output tests, and distinguish 24 V DC peripheral wiring from mains-voltage versions.

OtomasyonAVM resources and documentation

+ 6ES5 905-3RB21 model page · Second-hand Siemens S5 models · About Siemens S5 PLCs.

The S5-105R operating and programming manuals are linked in the Siemens references below.

Related topics and equipment

+ 6ES5 905-3RB11: the 500-program-element CPU version, for capacity comparison.

+ 6ES5 488-3LA11: a 105R peripheral board. 6ES5 375-0LA11: an EPROM memory submodule.

+ 6ES5 345-0LA11: EPROM programming adapter. These components have different system roles and are not interchangeable.

Browse SIMATIC S5

SIMATIC S5 processors · S5 memory submodules · S5 I/O boards · S5 cables and connectors · Second-hand Siemens products

Siemens and external references

+ Siemens S5-105R Operating Instructions — GWA 4NEB 810 0220-02, English PDF. Sections 2–3: connection and operation; Section 5.3: technical comparison of 905-3RB11 and RB21.

+ Siemens S5-105R Betriebsanleitung — German PDF. System, maintenance and spare-parts information.

+ Siemens S5-105R Programmieranleitung — GWA 4NEB 810 0221-01, German PDF. Ladder program structure, timer/counter functions, testing and program backup.