6ES5 905-3RB11
Siemens 6ES5 905-3RB11 CPU 905 — S5-105R, 500 Program Elements
Siemens 6ES5 905-3RB11 is the CPU 905 central processing unit for the S5-105R, with capacity for 500 contacts/program elements. This CPU belongs to SIMATIC S5 and serves relay-style Ladder Diagram applications. Use the 105R’s 605R/655R programmer arrangement for programming and maintenance.
500 contacts does not mean 500 KB or 500 program rungs. 905-3RB21 is a different version with capacity for 1000 contacts. Compare the complete order code, occupied program space and fitted memory submodule before replacing a unit advertised simply as “CPU 905”.
Ladder logic, timing and counting
Relay logic, latching, timing and counting functions are evaluated within the program. The CPU provides 32 timers and 16 counters. Compare time values, counter states and initial conditions with the installed program, then verify the machine sequence after processor replacement.
The 105R programming manual specifies up to 64 PBs, each containing up to 16 rungs. A rung accommodates up to seven contact elements and one output element. Assess these structural limits separately from the CPU’s 500-contact capacity; maximum PB count is not a measure of available program memory.
EPROM, EEPROM and program retention
The CPU can use suitable EPROM or EEPROM memory submodules. Siemens’ spare-parts list includes the 375-0LA11 EPROM. Record the fitted module’s complete code and program label, and identify whether it is included in the delivery.
The 105R contains no battery. Do not treat internal program retention as indefinite storage. Preserve a readable program backup before power-interruption testing, and do not assume that a long-stored CPU still contains its previous program. Record the existing contents before removing memory.
605R/655R connection and operating states
Select the programming interface and connecting cable for the 105R arrangement. Check program access, diagnostics and connections using the appropriate 605R/655R equipment. A familiar programmer name or similar connector alone does not establish suitability.
The programming manual describes single-scan testing in HOLD mode. Check output enable status and machine safety conditions during testing. Back up the existing program first, and ensure a diagnostic trial does not remain as an unintended production-program change.
I/O addressing and supply
The CPU supports addressing of up to 64 inputs and 64 outputs, with I/O locations numbered 0–7. This does not mean 64 physical inputs and 64 physical outputs are fitted to the CPU. Check the installed digital I/O modules, inputs and outputs.
Confirm the voltage type of peripherals such as 488-3LA11 from their own labels. Signal levels, output loading and connector arrangements cannot be inferred from the CPU code. Assess the power supply and rack against the installed 105R housing and wiring.
The technical table specifies 5.0 V / 700 mA for the CPU. Distinguish this internal supply requirement from the controller’s mains input. For an older Siemens S5 system, record program access, actual I/O exchange and the result after a power interruption as separate acceptance-test findings.
Editor’s note
This CPU has capacity for 500 contacts/program elements. An offer claiming “500 KB” needs correction. Reading the program and checking occupied space is more useful than discovering a capacity problem during replacement.
Do not look for a battery in the 105R; its retention arrangement is different. Establish whether a long-stored unit still contains a program, then test actual retention after preserving a backup.
Check the 605R/655R programmer arrangement. Siemens programmers are not universally interchangeable, so establish suitable connections before declaring the CPU’s interface faulty.
A green RUN light is insufficient. Siemens notes that RUN is possible even with erased program memory. Verify program presence, input readings and the correct output sequence separately.
Ask for photographs of the CPU label and memory submodule. The test record should identify the 105R housing, programmer and I/O boards used, so delivery information reflects the scope actually tested.
OtomasyonAVM resources and PDFs
+ 6ES5 905-3RB11 product and information page, S5 CPU pages and Siemens S5 models.
+ OtomasyonAVM SIMATIC S5 PDF archive. Consult both the 105R operating and programming instructions for this order code.
Related topics
+ 905-3RB21, 375-0LA11 EPROM, 488-3LA11 I/O module, Ladder Diagram and S5 memory submodules. CPUs and peripherals perform different functions and are not interchangeable parts.
Browse SIMATIC S5
S5 CPU | SIMATIC S5 | Digital I/O | Siemens second-hand homepage
Siemens and external references
+ Siemens S5-105R Operating Instructions, GWA 4NEB 810 0220-02, English — printed page 5.3 / PDF page 23: exact-code CPU table; PDF page 16: absence of a battery; PDF page 12: RUN/STOP/HOLD; PDF page 29: spare-parts list.
+ Siemens S5-105R Programming Instructions, GWA 4NEB 810 0221-02, English — section 1.1, printed page 1.2 / PDF page 3: PB and rung structure; section 3: program testing; section 4: saving programs to memory submodules.