6ES5 431-4UA12

Siemens 6ES5 431-4UA12 — 16-Channel 24–60 V DC Isolated Digital Input Module

The Siemens 6ES5 431-4UA12 is a 16-channel, 24–60 V DC digital input module for the SIMATIC S5 U range. Its inputs are arranged in 16 individually isolated groups of one channel. This compact U module is used with S5-135U, S5-150U and S5-155U systems and their U-range expansion units.

It evaluates 24, 48 and 60 V DC field signals from relays, contactor auxiliary contacts or suitable sensors. Each channel has its own +/− terminal pair. For PNP/NPN sensor wiring, assess the output circuit together with the channel's return connection.

Input thresholds, current and response time

The specified ranges are −33 to +8 V for signal “0” and +13 to +72 V for signal “1”. Rated input current is 4.5–7.5 mA over 24–60 V DC. Take multimeter readings across the relevant channel's +/− terminals; voltages between the defined thresholds must not be treated as a definite logic state.

Maximum input frequency is 100 Hz. Typical delay is 3 ms, with a specified range of 1.4–5 ms. Account separately for PLC input/output processing and the program cycle. The 100% coincidence factor permits all inputs to be active simultaneously.

Channel wiring and two-wire sensors

The manufacturer's drawing assigns the first input's positive terminal to pin 4 and negative terminal to pin 5; the second input uses pins 6 and 7. To preserve isolation, do not join separate channel returns without reviewing the project wiring.

The manual specifies a 22–72 V supply range for two-wire BERO sensor circuits. Check the sensor's own voltage rating, OFF-state current and ON-state voltage drop too; this range does not establish compatibility with every two-wire sensor.

Front connector and cable length

The module uses a 42-pin front connection. The manual lists the 20 mm crimp 6ES5 497-4UA12 for fan-cooled arrangements and the 40 mm screw-terminal 6ES5 497-4UB12. Select the front plug and wiring to suit the S5 rack arrangement. Disconnect system and field supplies before working on the module or front plug.

Permissible signal cable length is 400 m maximum unshielded or 1000 m maximum shielded. Assess grounding, shield termination and interference conditions separately.

Enable circuit and addressing

The enable terminals are F+ at pin 1 and F− at pin 2, rated 24–60 V DC. With jumper X20 inserted, the enable input is active, which is the factory setting. With the jumper open, the enable function is inactive. During debugging, review the existing project arrangement and jumper position before making changes.

The module's switch sets its starting address. 16 inputs occupy two consecutive bytes; for example, a start of 80 (0x50) allocates IB 80–81, leaving 82 as the next free start. Do not assume the physical slot number is the software address.

Differences from related models

The 430-4UA12 has 32 inputs in one isolated group. The 432-4UA12 has 32 inputs in four groups of eight, with group-signal/interrupt functionality. Verify channel count, voltage class and terminal assignment before selecting a replacement.

Editor's note

The detail to remember is that each input has its own return terminal. Before copying a common-negative bridge from another board, match the channel pairs against the wiring diagram.

The field circuit may use 24, 48 or 60 V. Measure across the channel's own +/− terminals; the cabinet supply reading alone does not tell you what reaches the input.

If every input becomes troublesome together, give the board a fair check first. Inspect F+/F− and the X20 position; changing a jumper to hide the symptom will make the next fault harder to trace.

When checking a used board, test all 16 channels in both logic states. Compare each LED with the bit read in STEP 5, and distinguish a poor contact from an electronic fault.

Before fitting a spare, photograph the order code, address switches and front-plug wiring and add them to the S5 maintenance record. Recording the two-byte allocation now can save plenty of work next time.

OtomasyonAVM resources and PDFs

+ Siemens S5 main page · 6ES5 431-4UA12 model page · OtomasyonAVM S5 PDF archive.

+ The exact model's technical table and wiring drawing appear in S5-135U/155U System Manual, §8.4.3, pages 8-34–8-35. The corresponding U Periphery section is on pages 37–38. Both documents are in English.

Related topics

+ 430-4UA12 · 432-4UA12 · 434-4UA12 · 497-4UA12 · 497-4UB12. Similar codes do not establish replacement compatibility.

Browse SIMATIC S5

+ S5 digital input modules · SIMATIC S5 central controllers · Siemens S5 · Used Siemens equipment.

Siemens and external references

+ Siemens S5-135U/155U System Manual — English, external archive copy: C79000-G8576-C199-07, §8.4.3, pages 8-34–8-35 / PDF pages 348–349; exact UA12 technical table and wiring.

+ Siemens U Periphery — English, external archive copy: 6ES5 998-0PC22, §5.3, pages 37–38 / PDF pages 240–241; UA11/UA12 table. Addressing: pages 25–27; front connector selection: page 28.