6ES5 420-4UA12
6ES5 420-4UA12 – SIMATIC S5 32-Channel 24 V DC Compact U Digital Input Module
Siemens 6ES5 420-4UA12 is a 32-channel, 24 V DC digital input module without galvanic isolation for U-series I/O installations in S5-135U, S5-150U and S5-155U systems. Within the S5 digital input module range, it features a compact U housing, four input bytes and an F+ enable input. Assess the field and system references together when using this Siemens S5 module.
It transfers signals from pushbuttons, limit switches, compatible sensors and contactor auxiliary contacts to the PLC. Compare the 4UA12 enable jumper and address switch with the existing machine configuration before installing a spare.
Input levels and electrical loading
Rated voltage is 24 V DC. Specified levels are −33 to +5 V for logic 0 and +13 to +33 V for logic 1. Do not use the intervening range as a stable operating level. Match the power supply and NPN/PNP output configuration to these thresholds and the common input reference.
Rated input current is 8.5 mA; typical input resistance is 2.8 kΩ. When selecting an inductive sensor or photocell, assess the output level under load and off-state leakage as well as its nominal voltage.
Input delay and signal frequency
Maximum input frequency is 100 Hz. Delay is typically 3 ms, within a 1.4–5 ms range. This alone does not establish that the PLC program will capture every short pulse. During troubleshooting, consider pulse duration, CPU scan time and how the program reads the input.
F+ enable input and X20 jumper
Front-connector pin 1 is the F+ enable input. Its rated voltage is 24 V DC and rated current is 5 mA. The connection drawing states that the 4UA12 enable input is active with the X20 jumper inserted, which is the factory setting. Keep this jumper setting separate from address selection.
Loss of the enable signal or removal of the front connector can affect acknowledgement-timeout / QVZ behaviour. The resulting input-data value depends on the CPU and enable configuration; do not assume that every input will read zero. Check the SIMATIC S5 project’s fault response against the installed hardware.
Front connector and channel order
On the 42-pin front connection, the four input bytes use signal pins 4–11, 13–20, 25–32 and 34–41, respectively. Each byte has eight channels; green LEDs indicate input status. Compare S5 cables and connectors with this channel order. Do not use pins shown as unconnected for improvised L+ or M bridges.
The module is non-isolated, so assess field L−/M, system reference potential and the grounding arrangement together. Dividing the channel numbering into four bytes does not create four galvanically isolated groups.
Address switch and four-byte allocation
The starting address is selected with the module’s address switch and is independent of its slot number. For example, selecting decimal 20 = 14h allocates bytes 20, 21, 22 and 23, giving input bits I20.0–I23.7. Distinguish the physical position in the S5 rack from the program address.
Supply, cable length and dimensions
The digital section draws typically 80 mA from the 5 V system supply. Dimensions are 20 × 255 × 195 mm; approximate weight is 0.4 kg. Inspect front-connector seating, the lower locking mechanism and rear bus contacts together.
Permissible field-cable length is up to 600 m unshielded or 1000 m shielded. Also assess voltage drop, shield termination and interference. These length limits do not establish identical signal quality for every cable route.
Comparison with related order codes
When comparing 6ES5 420-4UA13 or 6ES5 420-4UA14 as spares, check the enable configuration, address setting and hardware revision. The specifications on this page come from the earlier U Periphery table explicitly covering the complete 4UA12 code.
For 6ES5 430-4UA12 and 6ES5 431-4UA12, compare isolation, channel count, voltage configuration and front connections separately. A similar U-format housing or order code is insufficient to establish direct interchangeability.
Editor’s note
Read the complete label on this S5 module: 420-4UA12, 32 inputs, non-isolated U format. “420 input card” leaves too much room for a mismatch. Check the front connector, housing and both sides of the board.
Before replacement, photograph the address switch and X20 enable jumper. A used module with the same order code may arrive configured for another machine. Recording the original settings can prevent an unnecessary search through the program later.
If all channels disappear or a QVZ fault occurs, start with F+, front-connector seating and the common reference. Do not change the enable jumper simply to make the symptom disappear. First establish how the machine uses the enable circuit.
If an input LED is on but the program bit does not change, verify that you are watching the correct four-byte range. An unchanged slot position does not prove that the address setting is correct. Check the address switch, then the channel label, then the program bit.
When buying a used Siemens module, ask for all 32 channels to be tested in both logic states. Inspect terminals and pins for oxidation, the front connector for distortion and rear contacts for wear. Isolate power before replacement; clear wiring and configuration checks help prevent a healthy module being mistaken for a faulty one.
OtomasyonAVM resources and PDFs
+ S5 digital input modules · S5 cables and connectors · S5 racks.
+ Siemens S5 shared PDF archive. The exact 420-4UA12 table and connection drawing are in the English U Periphery manual, 6ES5 998-0PC22, Release 01, §5.1, printed pages 33–34 / PDF pages 236–237.
Related topics
+ 420-4UA13 · 420-4UA14 · 430-4UA12 · 431-4UA12.
+ NPN versus PNP · PLC troubleshooting · S5 digital output modules.