6ES5 420-4UA13
Siemens 6ES5 420-4UA13 – 32-Channel 24 V DC Digital Input Module
Siemens 6ES5 420-4UA13 is a 32-channel, 24 V DC, non-isolated digital input module for S5-135U/155U systems in the SIMATIC S5 range. Rated input current is 8.5 mA. It passes the states of pushbuttons, limit switches and field contacts to the PLC.
Logic 0 range: −33 to 5 V; logic 1 range: 13 to 33 V. Check these levels and the reference connection when selecting a sensor. Confirm the positive output signal of an inductive sensor or photoelectric sensor; do not assume that an NPN output can be connected in the same way.
Front connector and common reference
On the 42-way front connection, pin 1 is F+ and pin 42 is L−. The four input bytes use pins 4–11, 13–20, 25–32 and 34–41, respectively. When disconnecting S5 cables and connectors, record terminal numbers separately from PLC addresses. Do not assign a function to an unused pin by guesswork.
The non-floating inputs share the system reference. Check the power supply’s L−/M return and the reference wiring shown in the cabinet drawings. For a sensor powered from another supply, finding the positive voltage alone is insufficient; verify its return path as well.
System power and F+ enable input
The 4UA13 draws a typical 80 mA from the 5 V system bus. The F+ enable input is rated at 24 V DC / 5 mA. With jumper X20 inserted, the enable input is active; this is the factory setting. An open jumper disables the enable input. Review the machine’s wiring before changing the existing setting.
If all inputs disappear together, check the common reference, F+ circuit and front connector seating first. A single-channel fault and a supply or enable fault affecting the whole module need different checks.
Input speed and machine response
Maximum input frequency is 100 Hz; typical delay is 3 ms, with a stated range of 1.4–5 ms. CPU scan time and program execution add to the overall machine response. Assess suitable S5 function modules for short pulses or high-speed counting.
Addressing and troubleshooting
The 32 inputs occupy four bytes. The start address is set on the module’s addressing switch. For example, a start address of 64 maps to I64.0…I67.7; this is not a fixed address. When reviewing the Siemens S5 PLC architecture and PLC troubleshooting procedure, compare the hardware setting, wire labels and program addresses together.
For a module in an expansion rack, include the S5 interface modules and inter-rack connection in the checks. If data is passed to another station, trace its path through the S5 communications modules separately. A correct field signal and correct use of that signal by the application are separate checks.
Related order numbers and revision differences
The 6ES5 420-4UA11, 6ES5 420-4UA12 and 6ES5 420-4UA14 are different complete order numbers. In particular, do not apply the 4UA14’s typical 30 mA on the 5 V bus to the 4UA13. Compare the full code, hardware revision, address setting and front connector before replacement.
Where isolation or different input functions are required, review the individual connection arrangements of the 6ES5 430-4UA13 and 6ES5 432-4UA12. “32 inputs, 24 V” alone does not establish unconditional interchangeability.
The 420-4UA13 reads field information. Loads require suitable S5 digital output modules; the 6ES5 441-4UA13 and 6ES5 451-4UA13 belong to that separate group. Include both the input/output function and complete order number in a spare-parts request.
Editor’s Note
Start with the common L−/M return. A voltage reading at the sensor is useful, but measure it against the module’s reference too. A loose return connection can make healthy inputs look faulty.
Work through all thirty-two channels. Confirm that each input switches on, switches off and changes the correct PLC bit. Do not stop after the first eight channels; the remaining three bytes deserve the same check.
If every input disappears at once, check before ordering a replacement. Inspect the F+ connection, existing X20 setting and front connector. Avoid hiding an enable fault by changing the jumper at random; establish the cause first.
Before fitting a spare, photograph the addressing switch and front connector. An otherwise suitable module at a different address can leave the program reading the wrong inputs. Recording the old setting takes far less time than reconstructing it later.
For a used module, inspect the label and contacts before judging the cover. Confirm the 4UA13 suffix, connector condition, corrosion or overheating marks, and a 32-channel test result. If its behaviour changes after warming up, record that in the test report too.
OtomasyonAVM resources and PDFs
+ Siemens S5 digital input modules and the SIMATIC S5 main directory: related models and system pages.
+ OtomasyonAVM shared S5 PDF archive: system and wiring documents. Use the correct revision column for the 420-4UA13.
Related topics
+ About Siemens S5 PLC · S5 cables and connectors · PLC input troubleshooting.
Browse SIMATIC S5
S5 digital input modules | SIMATIC S5 | Siemens S5 PLC | Siemens second-hand main page
Siemens and external references
+ Siemens S5-135U/155U system manual – English: C79000-G8576-C199-07; §8.4.1, printed pages 8-30–8-31, PDF pages 344–345. 420-4UA13 specifications, front connection and X20 description; §8.2.1 for address setting.
+ CSA certificate 1232105 published by Siemens – English: exact 6ES5 420-4UA13 entry with 32 inputs, 24 V and non-floating construction.