6ES5 535-3LB11
Siemens 6ES5 535-3LB11 SIMATIC S5 CP 535 SINEC H1 Communications Processor
The Siemens 6ES5 535-3LB11 is a CP 535 communications processor for the SIMATIC S5-135U and S5-150U. It connects the PLC to a SINEC H1 industrial network. Siemens specifies a 10 Mbit/s data rate for the H1 triax network.
In a SIMATIC S5 installation, the CP 535 carries data between the CPU program and other stations. Siemens lists SEND/RECEIVE, FETCH/WRITE and PG/OP access for programming devices and operator panels in the CP 535 family. Before replacing a card in an S5-135U or S5-150U cabinet, record the full order numbers of the central rack, CPU and fitted CP.
How do the 3LB11, 3LB12 and 3MA12 differ?
The parts list identifies the 3LB11 as a SINEC H1 processor for the S5-135U and S5-150U. It lists the 535-3LB12 without the 15 V module and the 535-3MA12 with it. When replacing a 3LB11, confirm the cabinet’s supply arrangement and which parts come with the spare.
The CP 530 is for SINEC L1. The CP 544B handles serial point-to-point communication. Match the full order number, the network type and the jobs configured in the machine program when sourcing a spare.
Why does the rack’s 15 V supply matter?
Siemens’ S5-135U CPU 921/922 manual calls for a 15 V power supply submodule when the CP 535 is used with the listed supplies, including the 955-3LF12 and 955-3LC14. This instruction applies to the rack and supply arrangements in that manual. For a different rack fitted with a CPU 928 or CPU 928A, use the slot and supply drawings for the installed configuration.
The H1 segment and COM 535 settings
In Siemens’ H1 example, the CP connects to the triax segment through a 727-1BD20 drop cable and a bus coupler. The example uses the 3MA12. For a cabinet fitted with a 3LB11, follow the installation drawing to identify the S5 cables, coupler, segment termination and any other interface modules.
The Siemens COM 535 example records the local and remote Ethernet addresses, TSAP IDs, active/passive role and job number (ANR) for each connection. Compare the job numbers in the CPU’s communications function blocks with the CP project. An individual H1 connection can fail while the Siemens S5 PLC stays in RUN. Identify the affected station and job before changing the configuration.
Editor’s note
Photograph the label and slot number together. Record the order number, hardware revision and any fitted supply submodule.
Keep the CPU and CP backups separate. Check that the STEP 5 program and COM 535 connection project both open. Record the order number of the CPU’s S5 memory submodule as well.
Determine which stations are affected. If one station is unreachable, check its address and the connection’s TSAP pair. If several stations on the same segment are unreachable, have the shared cable and couplers checked first.
Trace the 15 V supply on the drawing. Before replacing the card, have maintenance staff verify the supply submodule and the feed through the backplane.
Ask for a data transfer test when buying used. Request a record that identifies the rack, CP order number, partner station and a working SEND/RECEIVE job. Use the S5 maintenance guide alongside the installation’s H1 drawing.
OtomasyonAVM resources and PDFs
S5-135U central rack · S5-150U central controller · SIMATIC S5 hardware overview and manuals
Related topics
CP 535 3LB12, without the 15 V module · CP 535 3MA12, with the 15 V module · SINEC H1 727-1BD20 drop cable
S5 navigation
Siemens S5 PLC · SIMATIC S5 · S5 communications modules · S5 cables
External references
ADEGIS SIMATIC S5 parts list, exact 535-3LB11 entry (PDF)
Siemens SINEC H1 functions and example configuration (English PDF)
Siemens SIMATIC NET triax network manual, SINEC H1 technical data (German PDF)
Siemens COM 552 manual, CP 535 configuration example, section 2.3.5 (German PDF)
Siemens S5-135U CPU 921/922 manual, 15 V supply note (English PDF)