6ES5 524-3UA15
Siemens 6ES5 524-3UA15 SIMATIC S5 CP 524 Serial Communications Processor
The Siemens 6ES5 524-3UA15 is a single-port CP 524 serial communications processor for S5-115U/H, S5-135U (excluding the S processor), and S5-155U systems. It provides a point-to-point link between a SIMATIC S5 PLC and a connected device. The plug-in 752 submodule determines the electrical interface. Selectable line rates range from 110 to 19,200 bit/s, with a 9,600 bit/s limit on 20 mA TTY.
In service, this S5 communications module exchanges data with another PLC, an industrial computer, or a compatible serial peripheral. On links using RK 512 or 3964/3964R, the COM 525 project and the program on the EPROM determine how the link operates. Siemens lists the CP 544 and CP 544B as later models. The CP 524 has one device port, while the CP 544 family has two.
How do you identify the interface and select the cable?
Read the label on the 752 interface submodule in the lower front-panel slot. Siemens lists the 6ES5 752-0AA43 for RS-422-A/RS-485 and the 6ES5 752-0AA12 for 20 mA TTY. For V.24/V.28 (RS-232C), the English ST 50 edition lists 6ES5 752-0AA22 and the German edition lists 6ES5 752-0AA23. Check the installed part number against the wiring diagram when replacing the submodule.
RS-422-A uses separate differential pairs for transmit and receive. The two-wire, half-duplex multipoint RS-485 arrangement documented by Siemens requires suitable special driver software. The 752 submodule determines the electrical interface, and the loaded driver determines the protocol.
Select the S5 serial cable for the devices and pin assignments at both ends. The 6ES5 726-1BF00 is a CP-to-CP 20 mA TTY example, and the 6ES5 726-8BC00 is a V.24 example. For TTY, also check which end supplies the current loop.
How do COM 525, the EPROM, and STEP 5 work together?
The CP program is configured in COM 525 under S5-DOS and programmed onto the 373 series EPROM submodule in the upper slot. Siemens lists 6ES5 373-1AA41 at 32 KB, 6ES5 373-1AA61 at 64 KB, and 6ES5 373-1AA81 at 128 KB.
SYNCHRON initializes CPU-to-CP communication at startup. The SSNR in STEP 5 must match the interface number set by the board’s jumpers. Data exchange uses SEND, RECEIVE, and FETCH where the application calls for it. Match the protocol, line rate, character format, and parity at both ends.
What does the rack installation require?
The CP 524 occupies one module slot and requires forced ventilation according to Siemens ST 50. Check the permitted slots against the full S5 rack order number. In an S5-115U, slot and adapter casing requirements depend on the CR 700-2, CR 700-3, or ER 701-3 arrangement. For an S5-135U/155U central rack, use that system’s slot table.
Editor’s note
Read the 3UA15 suffix on the label when sourcing a spare. If you are comparing it with a nearby part number such as the CP 524 3UA13, record the base module, 752 submodule, and EPROM numbers separately.
Back up the COM 525 project and any special driver file before removal. Match the EPROM to its part number and application label.
Record the address jumper positions, rack slot, and the device at the far end of the cable. Switch off rack power before inserting or removing the CP, interface submodule, or EPROM.
If the serial link fails to respond, check the RUN/STOP position, the 752 submodule, and the settings at the far end. Once the CPU and CP are synchronized, check SYSTAT and the STEP 5 status word for error details.
If the cabinet also contains a CP 525-2 3UA21, check which CP the saved program belongs to. Both use COM 525. Match the interface and EPROM arrangement to the installed model.
OtomasyonAVM resources and PDFs
For related hardware, browse the S5 communications modules and the Siemens S5 PLC overview.
For rack and system documentation, see the SIMATIC S5-115 PDF archive and the SIMATIC S5-115H system manual (English PDF).
Related topics
6ES5 524-3UA13 CP 524, 6ES5 525-3UA21 CP 525-2, and 6ES5 544-3UB11 CP 544B.