6ES5 470-8MD11

Siemens 6ES5 470-8MD11 SIMATIC S5 470 Analog Output Module

The Siemens 6ES5 470-8MD11 is a SIMATIC S5 analog output module for the S5-100U. It converts CPU commands to voltage references on two galvanically isolated 1–5 V DC outputs. The load circuit requires 24 V DC. Product records for this order number also list ET 100U. Siemens’ contemporary system manual also lists the module for external analog outputs on the S5-90U and S5-95U.

Typical applications include sending an analog reference signal to a valve positioner or a process controller with a matching 1–5 V analog input. The closely related 6ES5 470-8MC11 in the 470 range provides a 4–20 mA current output.

Load supply and channel wiring

Connect +24 V DC to terminal 1 (L+) and 0 V to terminal 2 (M) from the S5 load power supply.

+ Channel 0 – 4 QV voltage output, 6 MANA analog return, 3 S+ and 5 S− sense terminals.

+ Channel 1 – 8 QV voltage output, 10 MANA analog return, 7 S+ and 9 S− sense terminals.

In a four-wire field connection, run QV and MANA to the positive and negative load terminals. Run separate S+ and S− sense leads to those same terminals. The module senses voltage at the load and can compensate for a drop of up to 3 V per lead, as specified in the Siemens manual.

Siemens permits local sensing where the resistance of the output and return leads is negligible relative to the load. On each channel in use, jumper S+ to QV and S− to MANA. Leave unused outputs open.

STEP 5 addressing and 1–5 V scaling

In an S5-100U system with a CPU 103, analog I/O modules use slots 0–7. The 1–5 V range is fixed in hardware. Each channel has its own output word. In slot 3, for example, channel 0 uses QW 88 and channel 1 uses QW 90. Check the installed slot, channel addresses and scaling block together in the STEP 5 project.

The nominal scale is 0 → 1 V, 512 → 3 V and 1024 → 5 V. These are scale units. In the Siemens output word format, with the four low bits set to zero, the corresponding words are KH 0000, KH 2000 and KH 4000.

Choosing a spare in the 470 range

The 6ES5 470-8MA11 provides ±10 V and the 6ES5 470-8MB11 provides ±20 mA. Compare the voltage and current ranges on the labels. The 6ES5 470-8MD12 is also a 1–5 V model. Match the full order number, installed system and wiring diagram when selecting a spare.

Editor’s note

Record the full 470-8MD11 code and slot number before removing the module. Check the actual configuration within the S5 CPU family. In a compact S5-95U installation, trace the onboard analog output and the expansion module to their respective addresses.

If neither channel responds, measure the 24 V DC supply across terminals 1 and 2 first. If a PS 931 feeds the circuit, trace the fuse and distribution terminals as well.

If one channel reads low, compare the voltage at QV and MANA with the voltage at the receiving input. A lower reading at the receiver calls for a check of that channel’s S+ and S− wiring and field terminals.

Photograph the terminals before disconnecting the wiring. The 700-8MA11 screw-terminal bus unit and the 700-8MA21 crimp-contact bus unit have different contact points to inspect.

With the machine in a safe test state, check low, midscale and full-scale commands. Measure 1, 3 and 5 V at the receiving terminals. A zero scale command corresponds to the nominal lower limit of 1 V.

OtomasyonAVM resources and PDFs

SIMATIC S5 analog modules · S5-100U CPU 103

SIMATIC S5 PDF archive – system manuals

Related topics

6ES5 470-8MC11 – 4–20 mA output · 6ES5 470-8MA11 – ±10 V output · 6ES5 470-8MD12 – 1–5 V output · Analog current signals

S5 navigation

Siemens S5 PLC › SIMATIC S5 › S5-90/110 modules › S5 analog modules

Siemens and other external references

Siemens S5-100U Closed-Loop Control – 470 output ranges, §2.4

Siemens S5-100U CPU 100/102/103 manual – wiring in Figure 3.43 and addressing in §5.3 (Russian)

Siemens S5-90U/S5-95U System Manual – analog output wiring and word format, §12.5 (manual excerpt)

Standard Exchange Industry product record – 6ES5 470-8MD11 and ET 100U