6ES5 103-8MA01
Siemens 6ES5 103-8MA01 SIMATIC S5-100U CPU 103
The Siemens 6ES5 103-8MA01 is a CPU 103 for the SIMATIC S5-100U, with a 24 V DC input, internal RAM for 10,240 STEP 5 statements, 128 timers and 128 counters. Its built-in supply provides +9 V for the peripheral bus and +5.2 V for the programmer interface.
The CPU runs the machine program and exchanges data with I/O modules through the S5-100U bus units. It reads sensor states from digital inputs and sends the program’s commands to the digital outputs. Trace the CPU’s 24 V feed and the output modules’ field supply separately on the cabinet drawing.
I/O capacity and module selection
The published CPU 103 limits are 256 digital and 32 analog I/O points, with inputs and outputs counted together in each group. For a 470-8MA11 analog output, a 451-8MA11 digital output or another S5 analog module, check the slot, signal type and address against the installed module’s full order number.
What changes with the 8MA02?
The Siemens system manual documents the integrated real-time clock, time-controlled processing with OB13 and interrupt-driven processing from CPU 103 version 8MA02 onward. The 8MA03 has a separate order number. Siemens’ compatibility listing for the 482-8MA13 16-input/16-output module excludes the CPU 103 8MA01.
The range also includes the CPU 100 8MA01 and CPU 102 8MA01. When sourcing a spare, match the CPU type and full suffix, then review which STEP 5 blocks the machine program uses.
Program memory and closed-loop control
The internal RAM and removable S5 memory submodule are separate storage areas. Siemens’ S5-100U closed-loop control information sheet lists CPU software release Z02 for both 8MA01 and 8MA02 with version 1.0 of the standard function blocks. The sheet compares the package’s submodule to the 375-0LA15 EPROM. If using a PG 615, check the programming arrangement in that sheet.
The 24 V supply
External S5 power supplies such as the PS 930 and PS 931 can feed the 24 V line. The CPU’s internal +9 V output feeds the bus. If the 24 V line dips at start-up, use the drawing to trace the branches supplying the CPU and the field loads.
Editor’s note
Record the full CPU number and hardware revision. Keep the 103-8MA01 order number, the hardware revision if marked and the blocks used by the program in the same service record.
Photograph the I/O order before disassembly. Record the bus units, module positions and S5 cables and connectors. If a module is moved, check the address the program uses.
Record RUN/STOP status when the fault occurs. If the Siemens S5 PLC stops, note the LEDs and when the event started. Maintenance staff can then check the 24 V input and the programmer’s diagnostic information.
Identify the backup and memory submodule separately. Before shutdown, check that the STEP 5 backup opens. Record the battery status and the order number on the installed EPROM or EEPROM.
Ask for a test in a working setup when buying used. Request a record of start-up on 24 V, RUN/STOP indications, programmer access and a sample I/O test. Use the S5 maintenance guide alongside the CPU manual.
OtomasyonAVM resources and PDFs
S5-100U CPU 103 8MA02 hardware page · 700-8MA11 S5-100U bus unit · SIMATIC S5 hardware overview and manuals
Related topics
S5-100U CPU 102 8MA01 · 375-0LA15 EPROM submodule · PS 931 24 V DC cabinet power supply
S5 navigation
Siemens S5 PLC · SIMATIC S5 · S5 digital inputs · S5 digital outputs
External references
ADEGIS technical record for the 6ES5 103-8MA01
Siemens S5-100U system manual (English PDF). See section 6.4.2 for I/O compatibility, sections 7.4.4 and 7.4.5 for program processing, and Chapter 12 for the integrated clock.
Siemens S5-100U Closed-Loop Control, 8MA01/8MA02 software release table (English PDF)