6ES5 470-4UB11

Siemens 6ES5 470-4UB11 | SIMATIC S5 470 Analog Output Module, 8 × ±10 V

The Siemens 6ES5 470-4UB11 is an eight-channel analog output module in the compact U peripheral range of SIMATIC S5. It converts digital commands into ±10 V voltage signals in S5-135U and S5-155U systems. The eight-channel output group is galvanically isolated and the channels share a common MANA reference. Minimum load resistance is 3.3 kΩ and the delay from data transfer to analog output is 1 ms maximum.

The module supplies a bipolar analog voltage command to a drive or analog controller with a compatible setpoint input. Positive and negative program values determine output polarity. Related versions include the 6ES5 470-4UA11 for ±10 V and 0–20 mA, and the 6ES5 470-4UC11 for 1–5 V and 4–20 mA. Match the receiving device’s signal type to the complete module order number.

Load limits and power supplies

The voltage output requires a load resistance of at least 3.3 kΩ. Siemens specifies a maximum voltage-output current of 3 mA and a capacitive load, including cable capacitance, of less than 100 nF. The operating error limit is ±0.6% over 0–60 °C. Connecting receiving devices in parallel reduces the combined load resistance.

The analog section uses a 24 V DC field supply with a permissible range of 20–30 V DC, including ripple. The logic section takes 5 V ±5% from the system bus. In a panel fitted with a PS 955-3LC13 or PS 955-3NC12, check the rack logic supply and the module’s 24 V field circuit separately.

Front connector and channel terminals

Field wiring connects through a 42-contact front connector. When selecting S5 cables and connectors, check the termination method and mechanical width together. The 6ES5 497-4UA12 is a crimp connector option and the 6ES5 497-4UB31 uses screw terminals.

Pin 1 is F+ and pin 2 is F− for the module enable circuit. The field supply connects to 3 (L+) and 21 (L−). Pin 42 is the MANA analog return. Channel 0 uses 4 (QV0), 5 (S+0) and 6 (S−0). Channel 7 uses 38 (QV7), 39 (S+7) and 40 (S−7).

For four-wire operation, connect the load between QV and MANA and run the S+/S− sense wires to the load terminals. Where line voltage drop is negligible, two-wire operation is possible with QV–S+ and S−–MANA jumpers at the front connector. Fit these jumpers on unused voltage channels as well.

Addressing and digital output values

The start address is selected with the module’s six-position address switch. In a system using, for example, a CPU 928A or CPU 928B, compare the setting with the existing STEP 5 project and rack layout record. The module occupies 16 bytes. Each channel’s word address is start address + 2 × channel number. With a start address of 144, channel 7 uses word address 158.

Output values use a 12-bit two’s-complement representation. In the nominal scaling range, −1024 units produce −10 V, zero produces 0 V and +1024 units produce +10 V. When examining the program, trace both the scaling calculation and the write to the corresponding peripheral word.

Replacement checks for the 4UB12 and 4UB13

The 6ES5 470-4UB12 and 6ES5 470-4UB13 have the same nominal eight ±10 V output range. During replacement, check the address switch, connector coding and enable wiring. Siemens describes the enable jumper on 4U.12 versions separately in the U Periphery manual. Match this setting to the exact hardware revision.

Editor’s note

Read the complete label. Record the full 6ES5 470-4UB11 order number and hardware revision when selecting a spare. Check the connector and revision alongside the ±10 V front marking.

Photograph the address switch. Record its positions and the start address before replacement. Compare the replacement module’s address setting even when it occupies the same slot.

Measure the enable supply. If the module fails to respond to the program, check the 24 V enable voltage across F+/F−, followed by the L+/L− field supply. Check that the front connector is fully seated.

Measure at the receiving device. During a controlled test, check 0 V and suitable positive and negative commands with the load connected. If readings differ between the module and receiver, inspect the S+/S− wires, jumpers and load resistance.

Trace feedback separately. If the measurement returns through an analog input channel, for example on a 6ES5 460-4UA12 or 6ES5 465-4UA12, verify the 470 command voltage first and then examine the feedback path.

OtomasyonAVM resources and PDFs

+ Siemens SIMATIC S5 systems and module overview

+ SIMATIC S5 analog input and output modules

+ OtomasyonAVM shared SIMATIC S5 PDF archive

Related topics

+ 6ES5 470-4UB12 eight-channel ±10 V analog output

+ 6ES5 470-4UB13 eight-channel ±10 V analog output

+ 6ES5 470-4UC11 1–5 V and 4–20 mA analog output

Category navigation

+ SIMATIC S5-135U central controller · SIMATIC S5-155U CPU 948 · S5 analog modules

Siemens and external references

+ Siemens SIMATIC S5 U Periphery — 6ES5 470-4UB11 specifications and pin assignment, archived manufacturer manual

+ Siemens U Periphery — 470-4UB voltage output sense wiring and jumpers