6ES5 955-3LC13
Siemens 6ES5 955-3LC13 SIMATIC S5 power supply, 115/230 V AC input, 5.1 V DC / 18 A output
The Siemens 6ES5 955-3LC13 is a twin-fan 955-series rack power supply for SIMATIC S5. It has a selectable 115 or 230 V AC input, a 5.1 V DC, 18 A main output and a 24 V DC, 0.8 A auxiliary output. Siemens lists this exact order number for the 6ES5 185-3UA11 EG 185U expansion unit. The 3LC13 also appears in the S5-135U spare-parts list.
The supply powers the module electronics in the S5 rack. The 6ES5 955-3NC12, listed in the same EG 185U table, also supplies 18 A on the main rail and takes 24 V DC. The AC-fed 6ES5 955-3LF11 belongs to the 40 A class. Check the input type and main output rating together when identifying a spare.
Input current and output tolerances
The EG 185U data table specifies a line-voltage tolerance of −19% to +10% and a frequency range of 48–63 Hz. At rated load, the supply draws 1.2 A at 230 V or 2.4 A at 115 V. The unit’s S10/S11 voltage selector sets the input range.
The 5.1 V main rail has a voltage tolerance of ±0.5%. The 24 V auxiliary output is specified at −15% to +25%. Siemens lists a separate 15 V add-on module, 6ES5 956-0AA11, in the EG 185U spare-parts list. If the rack carries a CP 535 or other S5 communications modules, record how the 15 V supply is provided.
Minimum 5 V load for bench testing
Siemens specifies a minimum load of 1 A on the 5 V rail for reliable startup, operation of the 24 V section and fan supply. When testing the 24 V output or fan operation on a bench, record the load applied to the 5 V rail with the measurements.
Rack compatibility and related order numbers
The U-Periphery manual lists the 3LC12 for the 6ES5 183-3UA12 expansion unit. If you are comparing the 3LC14, check the manual for the installed rack. The later S5-135U/155U system manual pairs the 6ES5 188-3UA12 central rack with the 3LC42. Match an 18 A replacement against the rack number, supply number and terminal diagram.
Where several racks are linked through S5 interface modules, use the IM 304 and IM 314 connections to identify the affected expansion rack. Record the order numbers from the rack and its installed supply.
Fan faults and external 24 V monitoring
The unit signals a stopped fan through an LED and a relay. With the F-R jumper closed, a fault on either fan shuts down the supply outputs. In installations with F-R open, Siemens specifies an external circuit that disconnects the supply within 60 seconds of a fan fault.
The Voltage Monitor input monitors the external 24 V DC load supply. If a low-voltage warning appears, trace that circuit using the rack’s wiring and connector layout. If several S5 digital outputs drop together, record the rack’s 5 V supply, external load voltage and BASP status in the same fault report.
Editor’s note
Photograph the rack and supply labels together. Include a clear photo of the front terminals with the 3LC13 label. This lets the supplier compare the replacement connections with the installed unit.
Record the voltage selector position. Once the incoming supply has been isolated and verified de-energised, check whether the selector is set to 115 V or 230 V. Compare the setting with the cabinet supply before returning the rack to service.
Capture the fan warning before resetting. Note the fault LED, the condition of any filter and when the shutdown occurred. If the unit starts from cold and stops as the cabinet warms up, record the time to the first shutdown.
Confirm the program backup before removal. Check that the STEP 5 backup is current. If the S5 memory configuration relies on battery-backed RAM, record the status of the backup supply as well.
Ask for test results under load. When comparing used PLC power supplies, look for a report that states the AC input voltage, the load on the 5 V rail, the measured 24 V output and whether both fans operated.
OtomasyonAVM resources and PDFs
About Siemens SIMATIC S5 PLCs · 6ES5 185-3UA11 EG 185U expansion unit
OtomasyonAVM SIMATIC S5 PDF archive · Manuals published for the S5 family.
Related topics
6ES5 955-3LC12 · 6ES5 955-3LC14 · 6ES5 955-3NC12 with 24 V DC input
Browse this family
Siemens S5 PLCs → SIMATIC S5 → S5 power supplies
External references
Siemens U-Periphery manual — EG 185U, 3LC13 ratings and fan monitoring (Russian)
Siemens U-Periphery manual — 3LC13 terminal diagram (Russian)
Siemens U-Periphery manual — minimum load on the 5 V rail (Russian)
Siemens S5-135U CPU 921/922 manual — 3LC13 spare-parts listing (Russian)