6ES5 470-4UA13
6ES5 470-4UA13 Siemens SIMATIC S5 8-Channel Analog Output Module
The Siemens 6ES5 470-4UA13 is an 8-channel analog output module with ±10 V and 0–20 mA outputs for SIMATIC S5-135U/155U systems. This compact U-design S5 analog module provides voltage and current terminals for each channel; both follow the same digital channel value. Values use a 12-bit two’s-complement representation.
The module performs digital-to-analog conversion to send the PLC command to a receiving device’s analog input. Applications include a speed reference for a compatible variable frequency drive or a setpoint for a process actuator. There are eight command channels; the voltage and current terminals do not provide 16 independent setpoints.
Output ranges and permitted loads
The nominal voltage output range is −10 to +10 V; the current output range is 0–20 mA. The voltage receiver must have an input resistance of at least 3.3 kΩ. Total current-loop resistance, including the cable, must be no greater than 300 Ω. The delay from data transfer until the analog output reaches more than 99% of its value is 5 ms maximum.
Check the suffix when choosing analog signal ranges: the 6ES5 470-4UB13 is the ±10 V voltage-only version, while the 6ES5 470-4UC13 supplies 1–5 V / 4–20 mA. A 4UA13’s 0–20 mA output requires a review of software scaling and receiver settings before use in an installation expecting 4–20 mA.
Power, isolation and front connector
The digital section takes 5 V DC ±5%, approximately 250 mA, from the system bus. The analog section requires an external 24 V DC supply, 200–400 mA. The eight outputs are isolated as a group from the system and supply references and share MANA. This does not provide separate isolation between channels. Review the grounding and reference connections accordingly.
The 42-contact front connector uses pin 1: F+, 2: F−, 3: L+, 21: L− and 42: MANA. Channel 0 uses 4: QV0, 5: S+0, 6: S−0 and 7: QI0. When selecting S5 cables and connectors, check the pin assignment, mechanical keying and rack cooling arrangement.
Where voltage-drop compensation is needed, route the S+ and S− sense leads to the load. For negligible cable drop, S+ can be jumpered to QV and S− to MANA at the connector. These jumpers are also required when the voltage output is unused, including current-only operation. An unused current output may remain open. Correct analog signal levels depend on the sense wiring as well as the command value.
Addressing, scaling and output retention
The module’s address switch sets the start address. Eight channels occupy 16 bytes, with the start address set to a multiple of 16. A channel’s word address is start address + 2 × channel number. With a start address of 160, channel 0 uses word address 160 and channel 7 uses 174; the next free start address is 176. The PLC program must match this switch setting.
For voltage, −1024 / 0 / +1024 units correspond to −10 / 0 / +10 V. For current, 0 / 512 / 1024 units correspond to 0 / 10 / 20 mA. With the four low-order bits set to zero in the directly transferred word, +1024 units is 4000h and −1024 units is C000h. During PLC programming, keep this representation separate from the scaling conventions of other controller families.
The F+/F− enable input requires 24 V DC, approximately 7 mA. The upper enable jumper activates this input when fitted; without enable voltage, the module does not acknowledge and a QVZ timeout can occur. The module also ignores BASP output inhibit and retains its last output value. During PLC troubleshooting, check CPU state, the enable circuit and load power separately.
Before connecting a servo drive or another analog I/O circuit, verify its input range, reference connection and required stop response. Do not assume that stopping the CPU resets the analog output to zero. If bus power disappears while the analog 24 V supply remains on, the output value can drift.
Editor’s note
Confirm the complete 4UA13 code. When comparing it with a 4UA12, record the address switch, enable jumper and existing front-connector wiring. A similar front panel alone does not establish replacement suitability.
Test with a suitable load. Use an appropriate multimeter to check −10/0/+10 V on the voltage output and 0/10/20 mA on the current output. Measure current in series and keep total loop resistance within 300 Ω.
Check the jumpers before condemning a current output. Even with only QI in use, the matching QV–S+ and S−–MANA connections are required. Missing jumpers can make a wiring problem look like a module failure.
Request results for all eight channels when buying a used analog module. A successful measurement on one channel does not verify the entire board. Ask for the full code, quantity, label photographs, operating/fault condition and test-load details.
Review the stop sequence before fitting a spare. In a Siemens S5 installation, CPU STOP, loss of F+/F− and loss of 24 V are different events. Establish which machine action could continue while the module retains its last value.
OtomasyonAVM resources and PDFs
Start with our S5 analog modules and About Siemens S5 PLC pages to identify the module family.
For other S5 documentation, browse the OtomasyonAVM S5 PDF archive. For 470-4UA13 wiring and specifications, use Section 9.7 of the English S5-135U/155U system manual linked below.
Related topics
+ 6ES5 470-4UA12: an earlier version in the ±10 V / 0–20 mA family; check hardware and wiring before replacement.
+ 6ES5 470-4UB13: eight-channel ±10 V voltage-output version.
+ 6ES5 470-4UC13: eight-channel 1–5 V / 4–20 mA version.