6ES5 470-8MC11

Siemens SIMATIC S5 6ES5 470-8MC11 · 2 × 4–20 mA Analog Output Module

The Siemens 6ES5 470-8MC11 is a two-channel, galvanically isolated analog output module for SIMATIC S5 systems, including S5-100U and ET 200U. It converts PLC output words into 4–20 mA command signals. The module takes an external 24 V DC supply and supports a 300 Ω maximum load per channel. The maximum conversion time is 0.1 ms.

In a PID loop, the module sends a 4–20 mA command to a valve positioner or to a drive configured for a current reference. For example, a 464-8ME11 input module can read a pressure transmitter while the 470-8MC11 positions the valve. The two modules use the same current range for different sides of the analog I/O path.

Supported systems and model revisions

Siemens lists the 8MC11 for the S5-100U CPU 103 configuration in its closed-loop control manual. The earlier S5-90U/S5-95U manual also shows the 8MC11 wiring diagram. Match the installed S5 I/O modules and CPU revision against the system manual. The ET 100U manual’s ordering table specifies the 470-8MC12 for 4–20 mA output.

In the ET 200U table, the 8MC11 occupies four bytes in the analog address area. Its identifier is 2AQ / 021 for DP-Siemens and 2AQ / 097 for standard DP. The 8MC12 has the same 4–20 mA range. The table lists a delay of 0.15 ms for the 8MC12 and 0.1 ms for the 8MC11.

24 V supply and two-wire current outputs

The S5 wiring layout uses terminal 1 for L+ and terminal 2 for M. The permitted supply range is 20–30 V DC, including ripple. On a 700-8MA11 screw-terminal or 700-8MA21 crimp-terminal bus unit, read the terminal numbers for the slot holding the module.

Wire the channel 0 load across 4 (QI) and 6 (MANA) and the channel 1 load across 8 (QI) and 10 (MANA). Include the receiving input and any series devices when checking the 300 Ω load limit. Leave unused outputs open and follow the cabinet diagram for grounding.

STEP 5 output words and current scaling

Each channel uses one output word. On the 8MC11, 0, 512 and 1024 scale units correspond to 4, 12 and 20 mA. For direct word writes, the value bits sit four places to the left. With the four low bits cleared, those points correspond to 0000h, 2000h and 4000h.

In the STEP 5 project, record the channel’s output address and the block or network that writes the analog signal. If a function block takes a scaled command, check its interface for the required data format.

Related output ranges and similar order numbers

The 470-8MB11 outputs ±20 mA, the 470-8MD11 outputs 1–5 V, and the 470-8MA11 outputs ±10 V. The 464-8MC11 and 466-8MC11 share the 8MC11 suffix and are analog input modules. Check the 470 prefix and the suffix together.

Editor’s note

Before removal, photograph the full label, bus unit and slot. Record both channel addresses from the STEP 5 project.

If both channels lose output, check the 24 V DC supply across terminals 1 and 2 with the load connected, then check the PLC output words.

If one channel reads low, check that the receiving input is set to current mode and the total load stays within 300 Ω. Measure the current in series.

With the machine in a safe condition for testing, check both channels at 4, 12 and 20 mA. The 12 mA point checks the middle of the scale.

For a used module, ask for a photo of the 8MC11 label and current readings for both channels under load. Have the seller record the test load and supply voltage.

OtomasyonAVM resources and PDFs

+ SIMATIC S5 analog modules · S5-90/95/100U module family

+ SIMATIC S5 PDF archive · S5-100U manual page

Related topics

+ 6ES5 470-8MC12 · 2 × 4–20 mA · 6ES5 470-8MB11 · 2 × ±20 mA

+ 6ES5 470-8MD11 · 2 × 1–5 V · 6ES5 464-8ME11 · 4–20 mA analog input

S5 navigation

+ S5-90/95/100U module family · S5 analog modules · SIMATIC S5

External references

+ Siemens S5-100U legacy manual · 8MC11 wiring, scaling and specifications, pp. 6-94–6-96 (RU)

+ Siemens ET 200U manual · analog output addressing and delay, p. 4-11

+ Siemens ET 200U manual · 8MC11 two-wire connection, Figure 7-10

+ Siemens S5-100U closed-loop control manual · 8MC11 ordering data, p. 2-6

+ Siemens S5-90U/S5-95U legacy manual excerpt · 8MC11 wiring, Figure 12-11

+ Siemens ET 100U manual · 8MC12 ordering data, p. 2-3