6ES5 470-4UA11
Siemens 6ES5 470-4UA11 – 8-Channel ±10 V / 0–20 mA Analog Output Module
6ES5 470-4UA11 is an eight-channel analog output module in the compact U design for Siemens SIMATIC S5 systems, including S5-135U/155U installations. Each channel provides ±10 V voltage and 0–20 mA current outputs. This S5 analog module converts the PLC’s digital command into a continuous reference signal for field equipment.
Typical loads include compatible variable frequency drives, servo systems and process actuators with the required analog signal input. An output calculated by a PID controller is one example of a command that can be passed to the module. A channel’s voltage and current terminals follow the same command value; they do not provide two independently adjustable setpoints.
Output ranges and load requirements
For analog I/O matching, identify the 4UA11 as a ±10 V / 0–20 mA version. The 4UB voltage-only version and the 4UC 1–5 V / 4–20 mA version have different ranges. When comparing voltage and current signal standards, remember that this module’s native current range is 0–20 mA.
The voltage output requires a load resistance of at least 3.3 kΩ. Maximum continuous QV load current is 3 mA, and total capacitive load, including the cable, must remain below 100 nF. Compare the receiving device’s analog input specification with these limits.
For the current output, the combined receiver and cable resistance must be 300 Ω or less. A receiver with a 250 Ω input therefore leaves 50 Ω for the cable and any other series components. Include the complete loop when assessing the load.
Isolation and the 42-pin front connector
The output group is galvanically isolated from the system reference, while all eight channels share MANA. They are not individually isolated from one another. Check the grounding arrangement against the wiring diagram and distinguish analog common, the L− supply return and protective earth.
The 42-pin front connector uses 3: L+ / 21: L− for the field supply, 1: F+ / 2: F− for enable and 42: MANA for analog common. Channel 0 uses 4: QV0, 5: S+0, 6: S−0 and 7: QI0. Select S5 cables and connectors using the diagram for the complete module number.
The analog section requires a 24 V DC field supply; the digital section receives 5 V from the system bus. S+ and S− provide voltage feedback from the load. For a current-only channel, or an unused voltage output, fit the specified QV–S+ and S−–MANA jumpers. Unused current outputs may remain open.
STEP 5 scaling and addressing
The nominal digital-to-analog conversion scale is −1024 / 0 / +1024 → −10 / 0 / +10 V for voltage and 0 / 512 / 1024 → 0 / 10 / 20 mA for current. In PLC programming, distinguish these normalized units from the raw peripheral word.
Data uses a 12-bit, left-justified two’s-complement representation. With the lower four bits cleared, −10 V / 0 / +10 V correspond to C000h / 0000h / 4000h; +5 V or 10 mA corresponds to 2000h. The PLC address map must reserve two bytes per channel and 16 bytes per module. For base address n, channel k starts at n + 2k.
The specified delay between data transfer and the analog output update is 1 ms maximum. Overall loop response also depends on the CPU scan, the rate at which the program writes the output and the receiving device’s response.
Enable, CPU state and fault checks
Access from the SIMATIC S5 bus requires a 24 V enable signal at F+/F−. Removing enable stops new data exchange, and the last analog value can remain stored. The removable jumper that bypasses the enable function is documented for 4U.12 versions; do not apply that feature to the 4UA11.
On a 4U.11 module, CPKL = 1 writes zero to the output memory. The module does not evaluate BASP. Check the machine’s actual stop sequence instead of assuming that its behavior matches S5 digital output modules; verify it with the installed CPU and field circuit.
When debugging the PLC, check the field supply, F+/F− voltage, address switch and raw output word first. Disconnecting the field cable and measuring with a suitable test load helps distinguish a module fault from a cable or receiver fault. If an analog signal converter is fitted, verify its input and output ranges as well.
Editor’s note
Check the full part number. For a used module, request a clear photograph showing 6ES5 470-4UA11 and the hardware revision. Reviewing the Siemens S5 system background helps keep the different suffixes and enable arrangements separate.
Test all eight channels. Check −10, 0 and +10 V, then 0, 10 and 20 mA with appropriate loads. One functioning channel does not establish that the complete module is serviceable.
Check the voltage jumpers during current testing. Verify QV–S+ and S−–MANA on the same channel before judging the QI output.
Do not treat 0 mA alone as an open-loop indication. Zero current is a valid command on this version. Check the raw value, loop continuity and receiver range separately.
Do not assume that loss of enable forces zero output. Stopping data exchange and retaining a value are different from the CPKL-controlled zeroing behavior.
Assess performance under the intended load. If the result changes when the receiver and cable are connected, investigate load limits and the common reference. For analog signal applications, define acceptance criteria around the machine’s actual requirements.