6ES5 465-7LA13
Siemens 6ES5 465-7LA13 – 16 Analog Inputs / 8 Pt100 Inputs
6ES5 465-7LA13 is a non-isolated analog input module for the S5-115U in the Siemens SIMATIC S5 family. It supports 16 voltage/current inputs or eight four-wire Pt100 inputs. The measuring ranges of this S5 analog module are determined by its 6ES5 498 range cards and function selector settings.
The analog inputs convert analog signals from sensors and transmitters into values that the CPU can process. Supported nominal ranges include ±50 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA and 4–20 mA, together with Pt100 resistance measurement. When buying a used unit, establish which range cards are included.
498 series measuring range cards
With the base selector set to 500 mV/mA/Pt100, the 6ES5 498-1AA11 through-connection card is used for ±500 mV and Pt100. Voltage divider cards provide ±1 V with 498-1AA21, ±10 V with 498-1AA31 and ±5 V with 498-1AA61. Matching the card and base setting establishes the correct gain for the voltage signal.
For current signals, 498-1AA41 provides the ±20 mA range. Use 498-1AA51 for a 4–20 mA two-wire transmitter, or 498-1AA71 for a 4–20 mA four-wire transmitter. These two transmitter arrangements have different supply wiring.
Range cards serve groups of four inputs; four card positions configure the full set of 16 voltage/current inputs. Document the 50 mV or 500 mV base setting as part of the analog I/O configuration. Some divider and shunt cards offer different ranges in the 50 mV setting, with increased measurement error as specified in the manual.
Non-isolated inputs and reference potential
The 465-7LA13 inputs are not galvanically isolated. The permitted difference between the reference potential of a non-isolated sensor and the central system grounding point is ±1 V maximum. Check grounding and supply reference differences when a healthy sensor produces an unexpected reading.
Input resistance is 10 MΩ for ±50/±500 mV and Pt100, 90 kΩ for ±1 V and 50 kΩ for ±5/±10 V. Current input burden is 25 Ω for ±20 mA and 31.25 Ω for 4–20 mA. Confirm that the signal source can drive the specified load.
Pt100 wiring and function selectors
Pt100 measurement uses four-wire connections and eight-channel operation. The manual specifies the 500 mV base range with reference junction compensation disabled. The module supplies a 2.5 mA constant current through the sensor, using separate current and voltage sensing connections.
In voltage/current operation, channel 0 uses 3: M0+ / 4: M0−. For the first Pt100, this pair is used together with 27: S0+ / 28: S0−. The Mext terminals at 13 and 37 connect to the controller’s central grounding point. Follow the Siemens diagram for the selected measurement mode.
Measurement timing and STEP 5 data
The module uses an integrating, dual-slope voltage-to-time conversion method. At 50 Hz, integration takes 20 ms and a single conversion takes 60 ms maximum. A complete scan takes approximately 0.48 seconds for eight inputs or 0.96 seconds for 16 inputs. Include these times when assessing a PID control application.
At 60 Hz, integration takes approximately 16.67 ms and a single conversion takes 50 ms maximum. Suitable shielding and correct S5 cable and connector wiring are particularly relevant to low-level mV measurements. Select the actual installation frequency for effective mains interference rejection.
Measurement data can be configured as 12 bits plus sign or 13-bit two’s complement, with 2048 units at nominal full scale for bipolar measurements. The 4–20 mA range corresponds to 512–2560 units; subtract 512 in software for a 0–2048 representation. In PLC programming, handle the selected representation, measurement range and status bits together. Voltage/current scaling must not be interpreted as a Pt100 temperature value.
The PLC channel arrangement must agree with the function selectors’ eight- or 16-channel setting. Cyclic and selective sampling settings also affect how measurements are refreshed. Record the program addresses, representation and sampling arrangement before changing a range card or switch setting.
Supply, wirebreak detection and unused inputs
The digital section draws power from the 5 V system bus. A 24 V DC connection is required for the functions specified in the manual, such as two-wire transmitter operation or disabling the wirebreak test current. The specified permissible range for that supply is 20–30 V DC; it is not a voltage rating to apply to measurement terminals.
When troubleshooting, check the range cards, DIP switches, sensor reference and CPU reading first. Wirebreak detection is configurable for 50 mV, 500 mV and Pt100 ranges; it is not an automatic feature of every current input. Unused inputs fitted with a 1AA11 through-connection card must be short-circuited. Other unused inputs require the specified divider or shunt card termination.
Editor’s note
Buy the correct range cards with the module. A photograph of the main board alone does not identify its configured ranges. Request the full numbers of the cards in all four positions.
Record the hardware configuration first. Photograph the selectors before removal and note the 50/500 mV setting, channel count, data representation and wirebreak selections.
Measure the reference difference. On a non-isolated module, inspect the potential difference between a remote sensor’s common and the cabinet reference. Measuring only across the signal pair can miss this problem.
Test Pt100 operation with known resistance. Start with a suitable four-wire 100 Ω reference, then check a second resistance point and the temperature conversion used by the program.
Terminate unused inputs correctly. Follow the jumper and termination instructions, particularly with 1AA11 cards. Open unused inputs can make a serviceable module appear faulty.
Match the module to the process speed. A 16-channel scan approaching one second must be considered when tracking rapid changes. Review the Siemens S5 system arrangement together with the rate at which the program uses the measurements.
OtomasyonAVM resources and PDFs
+ S5 analog modules and model pages
+ Siemens S5 shared PDF archive and manual page
Related topics
+ 498-1AA11 through-connection card and Pt100 applications
+ 498-1AA51: two-wire 4–20 mA transmitters
+ 498-1AA71: four-wire 4–20 mA transmitters