6ES5 465-4UA13
6ES5 465-4UA13 Siemens SIMATIC S5 Analog Input Module
The Siemens 6ES5 465-4UA13 is a compact U-design, non-isolated analog input module with 16 voltage/current inputs or 8 Pt100 inputs for SIMATIC S5-135U/155U systems. This S5 analog module requires 6ES5 498 measuring-range cards and the appropriate mode-switch settings. Measured values can use 13-bit two’s complement or 12 bits plus sign.
The module converts analog input signals from sensors and transducers into values the PLC can process. Suitable range cards support ±50/±500 mV, ±1/±5/±10 V, ±20 mA, 4–20 mA and Pt100 applications. The installed range cards and switch settings determine how the base module is used.
Choosing the measuring-range cards
The 6ES5 498-1AA11 through-connection card supports ±50 mV, ±500 mV or Pt100, depending on the base module’s mode. With the base module set to 500 mV, 498-1AA21 provides ±1 V, 498-1AA61 provides ±5 V and 498-1AA31 provides ±10 V. Each range card serves a group of four inputs; the module’s common 50/500 mV setting must also be considered.
The 498-1AA41 is for ±20 mA, the 498-1AA51 for two-wire 4–20 mA transducers and the 498-1AA71 for separately powered four-wire 4–20 mA transducers. For current measurement, input resistance is 25 Ω on the ±20 mA range and 31.25 Ω on the 4–20 mA range. Two-wire and four-wire installations use different power connections.
For voltage measurement, input resistance is at least 10 MΩ on the direct mV/Pt100 input, 90 kΩ on ±1 V and 50 kΩ on ±5/±10 V. Changing a software label does not make 0–20 mA and 4–20 mA interchangeable: the range card and scaling must match the signal.
Power, reference potentials and sensor wiring
The digital section takes 5 V DC ±5%, typically 150 mA, from the system bus. The analog section uses 24 V DC load power, with a permitted range of 20–30 V DC. The module is non-isolated. Potential differences between sensor references and the module reference, and between sensors, must remain within ±1 V. The grounding and reference arrangement must satisfy this limit.
The 42-contact front connector uses pin 1: F+, 2: F−, 3: L+ and 42: L−. For voltage/current operation, channel 0 uses pin 4: M+ and pin 5: M−. When the F+/F− enable circuit is active, it requires 24 V DC, approximately 5 mA; loss of enable prevents acknowledgement and can cause QVZ. Match the S5 cable and connector to the actual pin assignment.
Pt100 measurement uses a four-wire circuit and a 2.5 mA constant-current source, supporting up to 8 resistance inputs. Select the 500 mV/Pt100 mode. When Pt100 measurement is used, channels 12–15 are unavailable as independent measuring inputs; wire the current-source terminals according to the resistance-measurement diagram.
Addressing, measurement speed and scaling
The front address switch sets the start address, while the side switches select the channel mode. The module occupies 32 bytes in 16-channel mode or 16 bytes in 8-channel mode. Start addresses must be multiples of 32 or 16, respectively. A channel’s word address is start address + 2 × channel number. In the PLC program, a 16-channel module starting at 160 uses word address 190 for its last channel; the next free start address is 192.
The module uses an integrating measurement method. At the 50 Hz setting, integration takes 20 ms and encoding takes 60 ms per measured value; an eight-value cycle takes approximately 0.48 seconds. At 60 Hz, encoding takes 50 ms per value. Both continuous cyclic scanning and CPU-triggered selective scanning are available.
The nominal bipolar range corresponds to ±2048 measurement units. For 4–20 mA, 4 mA corresponds to 512 and 20 mA to 2560 units. To obtain a 0–2048 representation, subtract 512 in software. These are measurement units after separating the status bits, not the unprocessed input word or a direct engineering-unit reading.
The input word also carries A: conversion active, E: error and OV: overflow. Hardware broken-wire monitoring is intended for the 498-1AA11 in the appropriate mV/Pt100 modes; it does not operate identically with every range card. Evaluate low current in a 4–20 mA loop in software. During PLC troubleshooting, check enable voltage, measurement mode, status bits and the actual field signal together.
Editor’s note
Match more than the base-module number. When comparing a spare with a 6ES5 465-4UA12, record all four range-card codes, both mode switches and the address setting. The Siemens supplement states that 4UA13 and 4UA12 versions share their functions and technical data; the installed configuration still needs to match.
Test with known inputs. Use a suitable signal source and multimeter to check the lower, middle and upper points of the selected range. Useful test points are −10/0/+10 V for a ±10 V application or 4/12/20 mA for a 4–20 mA application.
If several channels drift together, check reference potentials. This module has no galvanic isolation. An error appearing after several sensors are connected calls for a review of sensor potential differences and shield connections before the board is judged faulty.
Include the range cards in a used analog module enquiry. Request the full code, quantity, label photographs, operating/fault condition and test results. The offer should identify which 498 cards are supplied with the base module.
Do not treat the Pt100 reading as a direct temperature value. In a Siemens S5 application, check sensor wiring and the program’s resistance-to-temperature conversion together. Approximately 0.25 °C resolution does not establish the accuracy of the complete measurement system.
OtomasyonAVM resources and PDFs
Identify the family through our S5 analog modules and About Siemens S5 PLC pages.
Other S5 documentation is available in the OtomasyonAVM S5 PDF archive. For this module, use Section 9.5 of the English S5-135U/155U system manual and the U Periphery documentation supplement linked below.
Related topics
+ 6ES5 465-4UA12: a version in the same compact U analog-input family; compare its range cards and mode settings together.
+ 6ES5 498-1AA51 and 6ES5 498-1AA71: the distinction between two-wire and four-wire 4–20 mA connections.
+ What is Pt100?: resistance-based temperature measurement and sensor wiring.
Browse SIMATIC S5
SIMATIC S5 · S5 analog modules · Siemens S5 PLC · Siemens second-hand main page
Siemens and external references
Same manual — specifications, mode settings and front connector, pp. 9-72–9-76