6ES5 955-7NC11

Siemens 6ES5 955-7NC11 — S5-155H Power Supply Module

The Siemens 6ES5 955-7NC11 is a PS 955 power supply for the S5-155H central controller rack (CC 155H) in the SIMATIC S5 range. Designed specifically for that rack, it runs from a 24 V DC nominal input and supplies 5 V DC at 14 A and 24 V DC at 1 A for the rack.

The 155H rack has two independent subunits, each with its own power supply. The 7NC11 feeds the CPU and other modules in its subunit through the backplane. On a rack fitted with a CPU 948R, such as the 6ES5 948-3UR21, check the rack supply before tracing a fault to the processor. Use the cabinet drawings to identify the separate supply for field sensors and actuators.

24 V input and backplane outputs

Siemens specifies an input operating range of 18–33 V DC and requires a safely isolated 24 V DC feed. The 7NC11 itself does not provide that safety isolation between input and output. The hardware manual specifies up to 7 A input current per module at rated load and nominal input voltage. Check both the voltage range and the isolation requirement when selecting the cabinet’s 24 V DC power supply.

The detailed specifications give 5.1 V DC for the 5 V rail. The 5 V and 24 V backplane outputs share a common return. Treat the field-side supplies for digital input modules, digital output modules and analog modules separately from the backplane outputs.

Which rack takes the 7NC11?

Similar-looking S5 racks can require different power supplies. Siemens specifies the 7NC11 for the CC 155H only. For example, the 6ES5 188-3UA32 is an S5-135U/155U central controller and the 6ES5 185-3UA11 is a 185U expansion unit. Choose a power supply for an expansion unit by its own rack order number.

The 6ES5 955-7NC12 is also listed for the 155H family with the same main output rating. Treat the suffixes as separate order numbers and confirm any proposed substitution against the Siemens documentation. The 6ES5 955-3NC42 and 6ES5 955-3NF42 belong to the same 955 series but are listed for other racks, with 18 A and 40 A main outputs respectively.

The 6ES5 955-3NA12 is a 135U model with a 24 V DC input and a 10 A rating on the 5 V rail. The 6ES5 955-3LC42 takes 120/230 V AC. Check the input supply and the full order number together when ordering a replacement.

Front-panel indicators, test point and battery backup

DC LINE (1–2) is the module’s 24 V input. DC 24 V OUTPUT (3–4) supplies the I/O enable circuit. V MON. (11–12) is a separate input for monitoring the field load voltage.

The green DC 5V and DC 24V LEDs indicate the status of their respective outputs. Siemens provides a short-duration test point for the 5 V rail current with a scale of 3 V = 14 A. Trace the supply conductors separately from the S5 signal and interconnect cables on the cabinet drawings to identify the correct test location.

The front compartment takes one or two optional 3.6 V, 1.9 Ah AA lithium backup batteries. Siemens specifies 6ES7 971-0BA00. If only one battery is fitted, Siemens specifies the left-hand position. The batteries retain RAM contents when the supply fails. Check the maintenance records for a separate program copy on an S5 memory card or on the programming device.

Editor’s note

Check both labels first. Look for the 7NC11 suffix on the power supply and the CC 155H designation on the rack. The 955 marking alone is insufficient to identify a spare.

Record the 5 V and 24 V LED states separately. A dark LED is a starting point for diagnosis. Have qualified maintenance staff check the affected unit’s 24 V feed, terminals and enable circuit against the wiring diagram. The status of the S5 interface modules can also help narrow down which side of the system is affected.

Record the settings before swapping units. Note the terminal labels and wire numbers. Once the power supply has been isolated and removed, record the configuration switch positions. Compare the battery monitoring settings before fitting the replacement.

Identify which battery has raised the alarm. The left and right batteries have separate indicators. Check battery condition, which compartments are populated, and which positions are monitored. The Siemens S5 PLC overview provides context for the rest of the system.

Ask for a load test when buying used. When comparing used PLC power supplies, ask for a readable label photo, a condition check of the battery contacts and a load test of both outputs in the proper rack. An open-circuit voltage reading only confirms part of the picture.

OtomasyonAVM resources and PDFs

See the Siemens S5 PLC overview for hardware groups and the CPU 948R model page for an example of a 155H processor.

The SIMATIC S5 manuals and PDF archive brings together the S5 documents published on the site. For the 7NC11 itself, use the power supply chapter of the Siemens 155H manual linked below.

Related topics

The 6ES5 955-7NC12 power supply is a separate order number in the 155H family. The 6ES5 955-3NC42 provides a comparison with a 24 V DC 955 model designed for other S5 racks.

Browse SIMATIC S5

SIMATIC S5 family · Siemens S5 PLCs and modules

External references

Siemens S5-155H central controller manual — Part IV, Chapter 3, 7NC11 power supply.

Terminals and test points · Battery compartment and monitoring settings · Input and output specifications.

Siemens ST 50 catalogue — pp. 4/136 and 4/156, 955 power supplies and 155H spares.