6ES5 951-7ND12
Siemens 6ES5 951-7ND12 — S5-115U/H PS 951 Power Supply
The Siemens 6ES5 951-7ND12 is a SIMATIC S5 PS 951 rack power supply for the S5-115U and S5-115H. It takes a 24 V DC input and supplies 5 V DC to the backplane. The main output is rated at 7 A without a fan or 15 A with the specified fan assembly operating. The order number is listed without a backup battery.
The module converts the cabinet’s 24 V supply into operating power for the CPU and modules in the S5 rack. On a rack such as the CR 700-1, check the input and backplane supplies before tracing faults to a CPU 942 or CPU 944. Where interface modules link the central controller to expansion units, check the power arrangement for each rack.
Input, outputs and field power
The nominal input is 24 V DC, with a published operating range of 19.2–30 V DC for this order number. The Siemens S5-115H installation manual identifies the 7ND12 as having no galvanic isolation between the 24 V input and the 5 V output. Check the cabinet’s 24 V DC power supply return and chassis connections against the wiring diagram.
In addition to the 5 V backplane output, the unit provides a 5.2 V DC, 2.5 A PG/OP supply and a 24 V DC, 0.35 A auxiliary output. Trace the field power for digital input, digital output and analog modules separately on the cabinet drawings. Follow power wiring and S5 signal and interconnect cables separately to identify the correct test point.
When the 15 A rating applies
Add up the 5 V current draw of the CPU and all modules powered by the backplane. For example, include the CPU 945 along with the other modules in its rack. For a load above 7 A, the 15 A rating depends on the Siemens-specified fan assembly and installation conditions.
Comparing similar PS 951 models
The 6ES5 951-7NB13 is a 24 V DC input model rated at 3 A. The 6ES5 951-7LD12 is a 7/15 A model with a 120/230 V AC input. The 6ES5 951-7ND21 is a 7 A model listed for the S5-115F.
The 6ES5 951-7ND31 is listed as a galvanically isolated version. For the 6ES5 951-7ND41 and 6ES5 951-7ND51, consult the hardware documentation for the exact order number. Match the rack, isolation, battery arrangement and cooling requirements when selecting a replacement.
Editor’s note
Check the 24 V input under load first. If it dips as the PLC starts, check the cabinet supply, fuse and terminals. Once the input is confirmed, check the 5 V backplane supply.
Check the fan and airflow together. On a 15 A installation, confirm that the fan is correct for the rack, runs reliably and has a clear air path.
Check the hardware revision if IP 244 is fitted. For specified modules such as the IP 244 6ES5 244-3AA13 and 6ES5 244-3AA21 in an S5-115U, Siemens calls for 7ND12 hardware revision 4 or later and a battery-backed slot.
Check the battery and program backup separately. The unit is listed without a battery, so confirm what is fitted. Before removal, check for a current program copy on an S5 memory card or programming device.
Ask how a used unit was tested. When comparing used PLC power supplies, ask for a photo of the full label and revision. Ask what load and fan arrangement were used to check the 5 V output.
OtomasyonAVM resources and PDFs
Siemens S5 PLC overview · CR 700-1 central controller rack · IP 244 temperature controller
SIMATIC S5-115H system manual (English PDF) · SIMATIC S5 PDF archive
Related topics
7ND31 — isolated 7/15 A model · 7LD12 — AC input, 7/15 A output model
Browse SIMATIC S5
SIMATIC S5 range · S5 CPU and rack models
External references
Siemens S5-115H installation manual (German) · Siemens IP 244 manual — hardware revision and slot requirements, p. 2-14
7ND12 ordering record · 7ND12 input and output specifications