6ES5 951-7LD11

Siemens 6ES5 951-7LD11 SIMATIC S5 PS 951 Power Supply

The Siemens 6ES5 951-7LD11 is a PS 951 rack power supply for SIMATIC S5-115U and S5-115H systems. The catalogue lists a 115/230 V AC input. The main 5 V DC output is rated at 7 A without a fan and 15 A with the appropriate fan assembly. The catalogue lists the unit as supplied without a backup battery.

The PS 951 powers the SIMATIC S5 CPU and the control circuits of the modules in the S5 rack. The exact order number appears in an S5-115U hardware list for the CPU 942 and in a Siemens IP 252 closed-loop control application. If your machine uses the IP 252 6ES5 252-3AA11, use the current rating of the fitted module when calculating the rack load.

AC input and the three DC outputs

The photographed unit is marked 115/220 V AC on the front panel, while the catalogue record lists 115/230 V AC. Before commissioning, check the nameplate on the actual unit, the voltage selector position and the machine wiring diagram together.

The exact product record lists 5.2 V DC at 2.5 A and 24 V DC at 0.35 A in addition to the main 5 V DC rail. If the rack runs but the field outputs stay off, trace the I/O load supply separately on the machine drawing.

When is a fan assembly required?

Siemens requires a fan assembly when the load exceeds 7 A or when high-power modules are fitted. Include the actual 5 V current draw of all fitted modules, such as a CPU 944, CPU 945 or S5 interface modules, in the rack load calculation.

Select the fan by the full chassis order number, for example CR 700-2 6ES5 700-2LA11 or 6ES5 700-2LA12. Among the long-rack accessories, the 6ES5 981-0HA11 fan assembly takes AC and the 6ES5 981-0HA21 takes DC. Verify the correct mounting kit and fan supply for the rack.

How does the 7LD11 differ from similar PS 951 models?

The 6ES5 951-7LB13 is an AC-input 5 V / 3 A model. The 6ES5 951-7ND12 and 6ES5 951-7ND32 take 24 V DC. If you are considering a 6ES5 951-7LD12 or 6ES5 951-7LD21 as a replacement, check the mains settings, battery backup arrangement and front connections for that exact order number.

Editor’s note

Photograph the label and the selector. Record the original unit’s full 7LD11 order number, input marking and selector position on the same service ticket.

Check load and cooling together. If the rack drops out after warming up, record the indicators when the fault occurs. After safe isolation, inspect the fan, airflow path and any fitted filter.

Verify the program backup before removal. Record the S5 memory card type and the condition of the backup battery. Confirm that the program and required machine data can be restored.

Identify the cables by function. After safe isolation, match the mains input, protective earth and any external backup supply to the drawing before disconnecting the S5 cables and connectors.

Establish which rack lost power. If the central rack still runs and only the ER 701-2 expansion rack is down, check the expansion supply and the inter-rack link separately.

OtomasyonAVM resources and PDFs

See About Siemens S5 PLCs for a family overview and S5-90U/115U central controllers for rack and CPU models.

SIMATIC S5-115H system manual, fan assembly section (English, page 17-62, exact 7LD11 fan requirement) · Siemens S5 PDF archive.

Related topics

PS 951 7LD12 · PS 951 7LD21 · 115/230 V AC long-rack fan

S5 navigation

Siemens S5 PLCs · S5 power supplies · S5 racks

Siemens and other external references

Siemens IP 252 and COMREG manual, section 3.2.1 (Exact 7LD11 order number and 15 A maximum in an S5-115U application)

ADEGIS 6ES5951-7LD11 catalogue record (115/230 V AC and supply without a backup battery)

PLC Hardware 6ES5951-7LD11 technical record and label photographs (Front-panel marking and output ratings)