6ES5 951-7LB13
The Siemens 6ES5 951-7LB13 is a PS 951 power supply for the SIMATIC S5-115U. It takes a 115/230 V AC input and supplies the rack with 5 V DC at 3 A. The catalogue lists this order number without a backup battery.
In a SIMATIC S5 installation, the rack supply powers the processor and the internal circuits of the fitted modules. When selecting a spare for a CR 700-3 central rack fitted with a CPU 942, for example, check the rack designation, the cards actually installed and their combined 5 V load.
AC input and 5 V rack load
Before applying power, check the input nameplate and voltage selector position against the cabinet supply. The 3 A rating applies to the internal 5 V output. When adding a module to an S5 rack, include the CPU and the existing cards in the load calculation.
If the entire rack goes down, investigate any voltage drop at the cabinet input separately from the internal 5 V rail. If the fault affects only a group of digital inputs, digital outputs or analog channels, trace that group’s field power supply in the cabinet drawings.
Checking DSI requirements for IP and CP cards
The Siemens S5-115U manual names the 6ES5 951-7LB14 and 6ES5 951-7NB13 in its DSI warning. If a rack fitted with a 7LB13 contains an IP positioning module or a CP communications processor, verify the card’s DSI requirement and the exact power supply revision separately.
The same manual excludes the CP 524 and CP 525 from 3 A supplies because of their current draw. Check signal requirements and the 5 V load budget separately when selecting cards.
Related PS 951 order numbers
The 6ES5 951-7LB12 is also listed in the 115/230 V AC, 3 A class. Siemens specifies a 120/230 V AC input and a 5 V DC, 3 A output for the 6ES5 951-7LB21. The 6ES5 951-7LD12 is in the 7/15 A class. Match a spare against the complete order number and rack configuration.
Editor’s note
Photograph the nameplate and voltage selector. Capture the 7LB13 suffix and the selector position as found so both are on record before the unit is removed.
Inventory the cards in the rack. An IP or CP added during an earlier repair may be missing from the drawings. Base the load and compatibility checks on the hardware you find.
Check the program backup before isolating the cabinet. Establish how the CPU retains RAM and record the order number of any fitted S5 memory card.
Record which rack failed first. If the central controller stays up while one expansion unit drops out, check the local supply and inter-rack connection for that unit.
Ask what load was used for the test. When buying a used PLC power supply, ask which input setting and output load were used when the 5 V rail was measured.
OtomasyonAVM references and PDF archive
Browse our Siemens S5 PLC section for model pages and our S5 PDF page for published manuals. The S5-115H system manual (English PDF) covers 115H racks and the supplies documented for them, including the 7LB21.
Related topics
The S5 CPU 90U–115U index provides further processor and central-unit references.
Site navigation
Siemens Automation › Siemens S5 PLC › S5 power supplies
External references
Siemens SIMATIC S5-115U system manual (English PDF) · Installation guidance for PS 951 supplies and module selection.
ADEGIS 6ES5951-7LB13 product record · Exact order number, S5-115U application and input and output ratings.