6ES5 700-8MA11

Siemens 6ES5 700-8MA11 SIMATIC S5 screw-terminal bus unit

The 6ES5 700-8MA11 is a SIGUT screw-terminal bus unit that connects two plug-in I/O modules to the SIMATIC S5 serial bus. Siemens documents it for S5-90U, S5-95U and the S5-100U family, including the CPU 103. The Siemens data sheet also lists ET 100U and ET 200U. In a remote I/O station, check the full order number of the ET 100U interface or ET 200U interface in use. The S5-90U uses the IM 90 for the external I/O chain.

Slots, terminals and mounting

The unit has two module slots with ten screw terminals per slot. It measures 91.5 × 162 × 39 mm (W × H × D) and weighs approximately 300 g. The Siemens drawing specifies a 35 × 15 mm mounting rail. The base typically draws 1 mA from the CPU’s internal +9 V rail. The S5-100U manual lists up to 16 bus units per controller. Check the actual configuration limit for the CPU and I/O layout in use.

Siemens lists 0.5–1.5 mm² for stranded conductors with ferrules and 0.5–2.5 mm² for solid conductors. Use the fitted module’s wiring diagram to identify field terminals for digital inputs, digital outputs, analog I/O or combined digital I/O. A flat ribbon cable links neighboring units on the serial bus.

Related bases and interfaces

The 8FA11 also uses screw terminals. The 8MA21 and 8MA22 use crimp contacts. Compare the full order number, terminal style and cabinet clearance when selecting a spare. For hardware interrupt positions, the S5-100U manual lists the 8MB11 screw-terminal and 8MB21 crimp variants separately. Match the existing base code and the slot arrangement in the manual if the system uses interrupts.

For safety-related installations such as the S5-95F, assess the replacement against the approved project and the applicable Siemens manual. Match the order numbers of the IM 316 F and standard IM 316 against the drawing. If an entire tier is down, include the S5 interface modules, any IM 315 connection and the S5 cables and connectors between tiers in the inspection plan.

Editor’s note

1. Record the wiring before removal. Have qualified personnel isolate the PLC and field supplies and verify that power is off. Photograph both module labels, their slot order and the terminal numbering.

2. If several downstream modules fail together, trace the bus. Inspect the ribbon plug at the first affected base and its mating socket on the previous unit. A loose plug, crushed ribbon or bent pin helps narrow down the fault.

3. For one failed channel, inspect its screw terminal. Verify the terminal number on the module diagram. Look for a loose conductor, broken strands or discoloration. Follow the module and terminal instructions when tightening the connection.

4. If a card will not seat, compare the mechanical coding. With power isolated, check the coding element in the slot against the code on the card. The correct match lets the card sit squarely in its guides.

5. Ask for both slots to be tested on a used unit. Request close-up photos of the 8MA11 label, terminal screws, ribbon plug and rail latch. Ask the seller to confirm that the test detected the cards in both slots and the next unit in the bus chain.

To offer a used base for sale, send the full part number, quantity, condition, label and terminal photos, and asking price to otomasyonavm@gmail.com.

Siemens PDF documentation

6ES5 700-8MA11 data sheet (EN) · S5-100U technical table, p. 14-10 (EN) · S5-90U/95U technical table, p. 15-6 (EN) · OtomasyonAVM SIMATIC S5 PDF archive