6ES5 267-8MA11
Siemens 6ES5 267-8MA11 SIMATIC S5 IP 267 stepper motor control module
The 6ES5 267-8MA11 is the SIMATIC S5 IP 267 positioning module. It sends step pulses and a direction level to an external stepper drive. The drive’s power stage supplies the motor phase current. The IP 267 uses the PLC command to generate the pulse count and speed ramp. Its distance-to-go feedback reports the remaining commanded pulses.
CPU, slot and supply
In an S5-100U, the module fits slots 0–7 and uses the analog address area. The IP 267 manual lists 6ES5 100-8MA02 for CPU 100, as well as CPU 102 and CPU 103. The joint system manual lists up to two IP 267 modules in slots 0–5 for S5-90U and up to six in slots 0–7 for S5-95U. These limits depend on current consumption.
The module draws about 150 mA from the internal 9 V S5 bus. Check the terminal layout on the fitted 8MA11 screw-terminal or 8MA22 crimp-terminal bus unit. In a multi-tier system, include the IM 315 and expansion link in the inspection. For a station with an ET 200U interface, use the IP 267 section of the ET 200U manual.
DB9 outputs and field inputs
DB9 pins 2 and 4 carry step and inverted step. Pins 7 and 8 carry direction and inverted direction. Pin 9 is the signal reference. The front selector switches between internal 5 V and external US at 5–30 V. Assess this signal supply separately from the drive’s power supply. Match the S5 connecting cable and connectors to the drive input diagram.
The maximum pulse rate is 204 kHz. Siemens specifies up to 50 m at 50 kHz with twisted pairs. I+, I−, REF, STOP and PD are local 24 V inputs. Check the limit switches and the inductive reference sensor against the IP 267 terminal diagram. If the cabinet also uses separate PLC input modules, label both terminal groups.
Among S5 positioning modules, the IP 265, IP 266, IP 240 and IP 241 have different order numbers. Compare the function and drive interface when choosing a spare. Record the slot address and command format when replacing S5 function modules in an existing project.
1. Record the 5 V/US selector before removal. After qualified personnel isolate power, photograph the selector, DB9 plug and field terminals. Confirm the signal level expected by the drive before putting the replacement into service.
2. If RDY is off, check the readiness conditions. Start with the PD input state, CPU slot address and whether a valid configuration message reaches the module.
3. If ACT is on and the motor stays still, trace the signal chain. Under safe test conditions, have a technician check step and direction at the DB9, the cable and the drive enable input in sequence.
4. If ABT is on, identify the interruption. Check whether the PD limit operated. The manual requires reconfiguration after a PD trip. Follow the machine’s reference approach procedure before resuming motion.
5. Ask for a positioning test on a used module. Inspect the label, DB9 socket and selector. Request a test record showing RDY, ACT, the selected output level and step signals checked in both directions.
To offer an IP 267 for sale, send the full part number, quantity, condition, label photo and asking price to otomasyonavm@gmail.com.
Siemens PDF documentation
+ IP 267 operating manual (EN)
+ IP 267 DB9 pin assignments, p. 3-9 (EN)
+ IP 267 operating manual (DE)
+ S5-100U IP 267 technical table, p. 15-59 (EN)
+ S5-90U/95U, IP 267 slot limits, p. 16-62 (EN)
+ ET 200U system manual, section 9.12 (EN)