6ES5 760-1AA11

Siemens 6ES5 760-1AA11 – IM314 Terminating Connector

The 6ES5 760-1AA11 is a 50-pole terminating connector for SIMATIC S5 expansion connections. Within the S5 interface system, it is used on the last IM314 6ES5 314-3UA11 in a line. The Siemens installation diagram specifies the lower front socket X4 on the last IM314.

The central IM304 6ES5 304-3UB11 connects to expansion units through S5 connecting cables. The 760-1AA11 provides the electrical termination at the end of that line, using a Siemens-defined resistor and jumper network.

Where does the terminator fit?

Fit it to the IM314 in the last expansion unit of each line. When an additional unit extends the line, move the termination to the new endpoint. For older cabinets using an IM304-3UA11 or IM304-3UA12, check the complete module revision against its wiring diagram.

The IM304/IM314 instructions specify up to four expansion units per interface and a maximum cable length of 600 m from the central unit to the last expansion unit. Set the IM304 for the actual cable length as well.

Checking the 721 connecting cables

Examples from the 721 cable family are the 721-0BB00: 1 m, 721-0BB60: 1.6 m, 721-0BC50: 2.5 m, 721-0BD20: 3.2 m and 721-0BF00: 5 m. Record the cable order numbers and total line length when selecting spares.

The manual limits the potential difference between the central and expansion units to 7 V. Check equipotential bonding, cable connections and termination together.

Differences from similar 760 order numbers

The 6ES5 760-0AA11 is specified for an unused distributed connection on the IM301-3. The 6ES5 760-0AB11 is specified for the IM312 and an unused centralized connection on the IM301-3. The 760-1AA11 has a different pin arrangement. Check more than the housing shape.

For H/R interfaces such as the IM314H 314-3UH12 and IM314R 314-3UR11, follow the applicable system diagram. The U Periphery instructions list the 760-0HA11 separately for these configurations. Match the complete interface code, revision and termination diagram before selecting a part.

Electrical arrangement and fault checks

The connector contains resistors and direct jumpers between specific pins. Use the Siemens 760-1AA11 pin-assignment diagram for checking it. Take measurements with the connector removed and de-energized, recording the pin pairs being tested.

During PLC troubleshooting, check that the terminator is present, seated in the correct socket and free of pin damage; inspect the 721 cable as well. Review these connections before deciding to replace the SIMATIC S5 CPU or an interface module. Our Siemens S5 PLC overview explains the general system structure.

Editor’s note

This small plug is easy to overlook in an older cabinet. Before a lengthy fault-finding session, check the last IM314 in the line. The terminator may have been removed during cleaning or dismantling and left aside.

Read the complete 1AA11 suffix before selecting a spare. Photographs of both the label and the pin side make comparison much easier when similar connectors are on the bench.

If pins are bent, take time to examine the connector and its mating socket before attempting to fit it. A small contact problem is worth finding before a serviceable interface is replaced.

A resistor fitted between arbitrary pins is not a dependable repair. The complete connection pattern matters. Compare measurements with the correct diagram and work through it patiently.

For a used spare, ask for clear photographs of the housing, contacts and fastening parts. A trial on your own line is useful when practical. Keep the original plug labelled until the checks are complete.

OtomasyonAVM resources and PDFs

+ S5 interface modules and S5 cables and connectors: components used in the connection.

+ About Siemens S5 PLC: an overview of central and expansion configurations.

+ Siemens S5 PDF archive: system manuals. For the 760-1AA11, see Section 7.4.2, Figure 7-16 of the S5-135U/155U manual below. For its X4 position, see page 3-22 of the S5-115U manual.

Related topics

+ 314-3UA11 · 304-3UB11: the IM304/IM314 interface pair.

+ 760-0AA11 · 760-0AB11 · 760-0HA11: different terminating connectors.

+ 721-0BB00 · 721-0BC50 · 721-0BF00: related connecting cables.

Browse SIMATIC S5

S5 interface modules · S5 cables and connectors · Siemens S5 PLC · Used Siemens equipment

Siemens and external references

+ Siemens S5-135U/155U System Manual – English, C79000-G8576-C199-07; 7-23, terminator pin assignments.

+ Siemens S5-115U Manual – English, EWA 4NEB 811 6130-02b; 3-22, X4 on the last IM314.

+ Siemens U Periphery – English, third-party archive copy; IM304/IM314 instructions C79000-B8576-C716-02.