6ES5 752-0LA52

Siemens 6ES5 752-0LA52 — CPU 945 PG Interface Module, 20 mA TTY

6ES5 752-0LA52 is a PG interface submodule for the second serial interface, SI2, of the CPU 945 in Siemens SIMATIC S5 systems. It provides a 15-pin D-sub/Cannon socket, 20 mA TTY current-loop signalling and a fixed 9,600 bit/s transmission rate. Within the S5 interface module range, it connects a programming device or suitable operator panel to the CPU.

The Siemens ST 50 catalog lists it as a programming device module alongside the 6ES5 945-7UA13 and 6ES5 945-7UA23 CPU 945 options. It adds a connection beside the CPU’s fixed first interface; it is an internal CPU submodule rather than an external PC converter.

Programming and service access

The module allows a PG to establish an online connection through SI2 for PLC programming and service work. Select compatible programming software, the appropriate STEP 5 environment and the correct physical cable together. Transferring a program through the PG connection and programming an S5 memory card are different operations; this module is not a memory-card programmer.

Besides PG access, the CPU 945 manual permits an ASCII driver and a 3964(R) computer link through the programmer module. The relevant CPU communications function must be configured accordingly. Installing the submodule does not automatically enable every serial protocol.

TTY signalling and cable selection

TTY uses a 20 mA current loop. It is electrically different from RS-232. Consider the differences between RS-232, RS-422 and RS-485 when selecting connection equipment. Matching connector shapes or converter names are insufficient evidence of compatibility. An ordinary USB-to-RS232 converter alone does not provide this TTY connection.

The Siemens programmer-module pin table identifies pin 2 as −RxD, 9 as +RxD, 6 as +TxD, and 7 as −TxD. When choosing S5 programming cables and connectors, check the connector viewing direction, partner wiring and loop arrangement together. In the documented PG 7xx connection, the programming device supplies the loop current.

Using both CPU interfaces

PG or operator-panel connections can be used through SI1 and SI2 together, but some simultaneous PG function requests can conflict. The CPU operating system can interrupt a conflicting request and report that the interface function is disabled. During troubleshooting, do not interpret that message alone as proof of a defective submodule.

In a SIMATIC S5 installation, a panel operating on one interface may affect a service request made through the other. Record which device is connected to each port and which operation fails. Review the Siemens S5 system architecture alongside the CPU’s existing communications configuration.

Differences between similar 752 codes

The 6ES5 752-0LA12 is the 25-pin TTY option for CPU 945; its connector arrangement differs from the 15-pin PG interface of the 0LA52. The 6ES5 752-0LA62 is the SINEC L1 option. Select the cable and communications function by the exact module type.

Similar PG modules, including 6ES5 752-0AA52 and 6ES5 752-0AA53, also require an exact order-code and host-CPU check. Do not treat the 0AA and 0LA suffixes as interchangeable. A similar connector does not establish CPU compatibility.

Installation and used-module inspection

Insert or remove the module only with power off. Remove the SI2 receptacle cover, seat the module correctly and secure it with its screws. Avoid straining the socket, mounting points or board connection. Record the existing jumper arrangement before making changes.

Editor’s note

If the PG will not connect, give the cable and settings a fair check before blaming this small board. Start with an S5 programming cable known to work on the same CPU type. Working through the cable, converter and software one at a time can save replacing a healthy module.

A 15-pin plug is not enough reason to connect an unfamiliar cable. Other interfaces, such as RS-422, can use similar connectors. Confirm the electrical interface and cable diagram first. A plug that fits is only a mechanical match.

If the first port works and the second does not, that is a useful clue rather than a complete diagnosis. Check the SI2 module type, contacts, jumpers and assigned communications task. Taking a little care here usually saves a second round of fault-finding.

When buying used Siemens equipment, ask for a readable label photo, a close view of the socket and a clear description of the connection test. “Installed in a CPU” and “established an online STEP 5 connection” are different checks. A tested function is more useful than a general claim that the board works.

Once the connection is working, back up the existing program and accessible data before making changes. Do not download a test program or perform an overall reset simply to check the connection on a working machine. Preserve what is there first, then decide what needs changing.

OtomasyonAVM resources and PDFs

+ Review the S5 interface modules and S5 cables and connectors pages together when selecting the submodule and connection hardware.

+ OtomasyonAVM S5 PDF archive and system manuals. For this model, use CPU 945 manual sections 12.7 and 12.7.1, the programmer-module pin table and the PG cable diagram. The documents below are in English.

Related topics

+ 6ES5 945-7UA13 CPU 945 · 6ES5 945-7UA23 CPU 945 · 6ES5 752-0LA12 TTY module · 6ES5 752-0LA62 SINEC L1 module.

Browse SIMATIC S5

+ S5 interface modules · S5 cables and connectors · SIMATIC S5 · Siemens S5 PLCs · Siemens second-hand equipment.

Siemens and external references

+ Siemens S5-115U CPU 945 Manual — 6ES5 998-3UF21, Edition 06; pp. 12-97–12-102: module selection, PG interface, pin assignments, jumpers and cables.

+ Same manual, p. 12-120: fixed 9,600 bit/s transmission rate and 15-pin programmer-module socket.

+ Siemens ST 50, 1998 — archived copy of the English manufacturer catalog; p. 3/24: exact 6ES5 752-0LA52 order code and CPU 945 options.