6ES5 308-3UC21
Siemens 6ES5 308-3UC21 – IM308-C PROFIBUS-DP Master Interface
The 6ES5 308-3UC21 is an IM308-C interface module connecting S5-115U, S5-135U and S5-155U controllers to PROFIBUS-DP in the SIMATIC S5 family. Part of the S5 interface module range, it exchanges data between the central CPU and distributed field stations. Alongside its DP master function, it supports DP slave operation with the appropriate configuration.
The maximum transmission rate is 12 Mbit/s, with up to 122 DP slaves. It connects suitable ET 200 stations and other PROFIBUS-DP devices. The interface uses a 9-pin female Sub-D connector; select a suitable PROFIBUS connector. The module takes its 5 V DC supply from the backplane and occupies one slot.
Memory Card and 5 V programming requirement
Select the configuration Memory Card carefully. The Siemens data sheet states that only 5 V-programmable cards can be programmed in the 3UC21 and lists the 6ES5 374-1KH21 as a separately ordered item. Check the programming voltage and contents as well as the card's physical fit.
When comparing the 308-3UC11 and 308-3UC21, assess the hardware revision, Memory Card and existing project together. The 308-3UA12 is a separate model for the ET 100U serial connection arrangement. Specify the complete code and card arrangement when ordering a spare.
COM PROFIBUS and address mapping
Station addresses, bus parameters and I/O configuration are prepared in the COM PROFIBUS project. Addresses in the PLC program must match the slave's digital input, digital output and analog module configuration. Preserve the project and a backup of the Memory Card contents before replacement.
Projects using ET 200U interfaces such as the 318-8MB12 or 318-8MC12 require checking the exact station model and its supported rates. A master rated for 12 Mbit/s does not mean every connected slave supports that rate. Select a common rate supported by the devices and cable arrangement.
Cabling, shielding and termination
Check cable connections, shield continuity and grounding. Set termination according to the actual ends of the bus segment. Unplugging connectors or changing termination without checking the topology can also interrupt communication with other stations.
Replacement and diagnosis
During troubleshooting, assess the IM308-C indicators, CPU diagnostics and COM PROFIBUS station status together. Disconnect the supply before removing the module from its S5 rack or removing the Memory Card. On restart, confirm station detection, then verify that actual I/O data updates at the correct addresses.
Editor’s note
The Memory Card is part of the job alongside the module. Ask whether a spare includes a card, what code it carries and what it contains. A bare interface and an arrangement carrying the machine's configuration are different deliveries.
Leave a working Memory Card untouched until you have found the project and its backup. Reconstructing a lost configuration in an older system can take far longer than changing the module.
When moving from a 3UC11 to a 3UC21, check the card's programming requirements. Take Siemens' 5 V programming restriction seriously; physical fit alone does not settle the question.
For a bus fault, start with connectors and segment ends. A loose shield connection or changed termination can make a healthy master look faulty. Make one change, check the result, then move to the next.
For a used spare, ask for more than illuminated indicators. Where practical, request a connection and I/O data-transfer trial with a suitable slave. Keep the original module and card separately labelled until the replacement arrangement is verified.
OtomasyonAVM resources and PDFs
+ S5 interface modules and Siemens ET 200: masters and field stations.
+ 374-1KH21 Memory Card and PROFIBUS connectors: memory and connection parts.
+ Siemens ET 200 manuals and Siemens S5 PDF archive: our documentation pages. The exact-code 3UC21 data sheet is listed below; the ET 200 System Manual explains IM308-C family configuration and diagnosis.
Related topics
+ 308-3UC11 · 308-3UA12 · 374-1KH21: version, connection function and Memory Card selection.
+ 318-8MB12 · 318-8MC12 · What is PROFIBUS?
Browse SIMATIC S5
S5 interface modules · Siemens ET 200 · PROFIBUS connectors · Siemens S5 PLC · Used Siemens equipment
Siemens and external references
+ Siemens 6ES5308-3UC21 data sheet – English, 2017: exact code, master/slave function, 12 Mbit/s, 122 slaves and 5 V Memory Card programming requirement; third-party archive copy of a Siemens publication.
+ Siemens ET 200 Distributed I/O System – English, 2806161-0002: Chapters 3, 8 and 9; IM308-C, Memory Card, COM PROFIBUS and diagnosis. Its scope table lists the 3UC11; use the exact-code data sheet for the 3UC21-specific card requirement.
+ Siemens IK PI · 2005 PROFIBUS catalogue – English, pp. 5/93 and 5/171–5/172: IM308-C and COM PROFIBUS; third-party archive copy of a Siemens publication.