6ES5 457-7LA11
Siemens 6ES5 457-7LA11 – 32-Channel Digital Output Module, 5–24 V DC / 100 mA
The 6ES5 457-7LA11 is a 32-channel, open-collector transistor output module for S5-115U/H in the SIMATIC S5 family. Part of the S5 digital output range, it converts CPU commands into control of low-current DC loads. Its outputs sink current towards M and carry a maximum of 100 mA per channel.
Load supplies of 5/12/24 V DC are supported within a permissible range of 4.75–30 V DC. The outputs have optocoupler isolation in four groups of eight. Check group wiring when assessing PLC and load power supplies; installing the module in an S5 rack does not remove the need for a suitable field-load supply.
Open-collector connection
Connect the load between the positive supply and the output terminal; current flows towards M when the output conducts. Do not wire this cable arrangement as if the output supplied positive voltage. Check each group's M reference and grounding against the Siemens diagram. An unloaded voltage reading alone is not a channel test.
100 mA limit and short-circuit protection
The module has no internal short-circuit protection. Check load inrush as well as continuous current, and design suitable fusing and current limitation for the output stage. Use an appropriate interface relay or driver for higher-current loads; its input must also remain within the 100 mA channel limit.
The maximum switching frequency is 10 Hz for resistive loads and 2 Hz for inductive loads. Check suppression components and polarity on coil loads. These ratings do not make the module a high-speed pulse or high-frequency PWM output.
46-pole front connector
The module uses a 46-pole 490-series front connector. Options include the screw-terminal 490-7LB21 and crimp versions 490-7LA11 and 490-7LA21. Check whether crimp contacts are included and confirm the existing wiring assembly's connection type.
Addressing and channel checks
The 32 outputs occupy four output bytes. Match PLC program addresses to the actual rack and slot arrangement. During testing, check the output command, the real load response and any digital input feedback together. During troubleshooting, distinguish an individual channel fault from a shared group-supply fault.
Comparison with related modules
The 451-7LA12, 454-7LA12 and 458-7LA11 use different current ratings or output technologies. Compare output count, switching direction, load current and connector layout before selecting an alternative.
Preserve the suffix when reviewing other 457-family codes such as the 457-4UA12 or 457-8EA12. Specify the complete 6ES5 457-7LA11 code, label photograph and front wiring arrangement when requesting a spare. Disconnect system and load supplies before removing the module or front connector.
Editor’s note
Start by understanding the output circuit. An active channel pulls the load towards M. Before deciding that “there is no 24 V at the output, so the card is faulty,” check the load connection. An unloaded measurement can be misleading here.
100 mA is enough for the right load, but a 24 V label alone does not make a relay or valve suitable for direct connection. Check its continuous current, inrush and suppression arrangement together.
This module does not protect itself against short circuits. Checking the field cable and load before testing is easier than replacing another card. Find the cause of the original failure before connecting a replacement to the same circuit.
If every output in one group stops working, start with that group's supply and M connection. Treating eight missing signals as eight separate failures wastes time. One shared connection can affect the whole group.
Where practical, assess a used card with suitable loads and all 32 channels tested. Ask whether the front connector is included. Photographing and labelling the wiring before removal makes installation much easier.
OtomasyonAVM resources and PDFs
+ Siemens S5-115U PDF archive: our manual page. The exact model's technical table is on page 15-40 of the S5-115U Manual.
+ S5 digital output modules · S5 racks · S5 cable types
Related topics
+ 490-7LB21 · 490-7LA11 · 490-7LA21: 46-pole front connector options.
+ 451-7LA12 · 454-7LA12 · 458-7LA11: load-rating and output-technology comparisons.
Browse SIMATIC S5
S5 digital output modules · S5 CPU models · Siemens S5 PLC · Used Siemens equipment
Siemens and external references
+ Siemens S5-115U Manual – English, EWA 4NEB 811 6130-02b, p. 15-40: exact 457-7LA11 code; 32 outputs, isolation in groups of eight, 100 mA, open-collector wiring diagram, absence of short-circuit protection and switching frequencies.
+ Siemens ST 50 · 1998 catalogue – English, pp. 3/35–3/40: technical comparison, 46-pole front connector, ordering codes and wiring diagram; third-party archive copy of a Siemens publication.