6ES5 454-4UA12

Siemens 6ES5 454-4UA12 — 16-Channel 24 V DC / 2 A Digital Output Module

6ES5 454-4UA12 is a 16-channel, 24 V DC digital output module rated at 2 A per channel for Siemens SIMATIC S5 systems. Its electronic digital outputs switch DC loads in response to PLC commands. The load supply range is 20–30 V DC, with a specified switching current of 10 mA–2 A.

The module is designed for S5-135U, S5-150U and S5-155U controllers and their associated U-series expansion units within the SIMATIC S5 family. All 16 outputs form one galvanically isolated group; individual channels are not isolated from each other. Check the installed S5 rack and the complete module order code together.

Channel current and combined load

The combined current of each four-output group must not exceed 4 A. Siemens also specifies a 50% diversity factor. Multiplying 16 × 2 A does not establish a continuous 32 A module rating. When selecting relays and contactors, check both the individual coil current and the combined load within its four-channel group.

Maximum switching frequency is 100 Hz for resistive loads; for inductive loads it is 0.2 Hz at 1 A or 0.1 Hz at 2 A. Maximum off-state leakage is 1 mA, and the lamp-load limit is 0.45 A / 10 W. Check pickup and release conditions carefully for small interposing relay coils.

Load supply and F+/F− enable input

Field loads require a suitable 24 V DC load supply; distinguish this from the function of the S5 system power supply. The F+/F− enable input is rated at 24 V DC, with a logic-1 range of 13–33 V and a rated input current of 5 mA.

The 4UA12 version has a jumper for selecting the enable mode; the enable input is active in the factory setting. If an output does not operate, check the load supply, enable voltage and jumper position together. In expansion units, also check the interface connection and controller fault state.

Front connector and fault diagnosis

Siemens lists the 40 mm wide, 25-pole screw-terminal 6ES5 497-4UB22 front connector for the 454. When comparing it with the 42-pole 497-4UB12, check the pole count and existing wiring arrangement. The original diagram shows F+: 1, F−: 2, L−: 21, H+: 22; the four load feeds are 1L+: 3, 2L+: 20, 3L+: 24, 4L+: 41.

There is one 6.3 A slow-blow fuse per four outputs. Green LEDs display channel status; red LEDs indicate a short circuit within a four-output group. The H+ short-circuit signaling output requires a supply at 1L+. Comparing the PLC program command with the output channel’s voltage under load helps fault diagnosis; carry out tests with safe machine conditions established.

Differences between nearby order codes

The suffixes in 454-4UA11, 454-4UA13 and 454-4UA14 matter. Siemens’ supplement states that 4UA13 and 4UA12 have the same functions and technical data. The later system manual specifies a 7 A fast fuse and a different mounting width for 4UA14; those values must not be transferred to 4UA12.

The 454-7LA12, 456-4UA12 and 458-7LC11 pages help compare different systems, voltages or output arrangements. Similar numbers and matching channel counts do not establish direct interchangeability.

Editor’s note

Start with the label and read 454-4UA12 right through to the final digit. A small difference in an old S5 order code can turn into a long afternoon at the cabinet.

Do not fill every channel to 2 A just because that figure is on the specification. Four channels share a 4 A limit. Write down which coils belong to each group; it makes later maintenance easier.

If the program commands an output but nothing moves, give the card a fair check before replacing it. Start with the load feeds, F+/F− enable voltage and jumper setting. A healthy module can look faulty when one of these is missing.

If a fuse opens, inspect the cable and coil before fitting another. This version specifies a 6.3 A slow-blow fuse; do not borrow the fuse rating from a different card.

For a used card, LEDs alone are not enough; test all 16 channels individually with suitable loads. Photograph the label, address setting and front wiring before removing the original module. Those pictures are useful when the job gets busy.

OtomasyonAVM resources and PDF files

+ S5 PDF files and user manuals · About Siemens S5 PLCs. The primary reference is Siemens U Periphery, Section 5.12: specifications on printed page 59 and the wiring diagram on printed page 61. The document is in English.

Related topics

+ 454-4UA11 · 454-4UA13 · 454-4UA14 · 497-4UB22 front connector · PLC fault diagnosis.

Browse SIMATIC S5

+ S5 digital output modules · S5 racks · S5 interface modules · Siemens S5 PLC · Siemens second-hand equipment.

Siemens and external references

+ Siemens U Periphery — Section 5.12, printed pages 59–61 (PDF 262–264): 454-4UA11/4UA12 specifications and wiring. Front connector table: printed page 28 (PDF 231). English.

+ Siemens S5-135U/155U System Manual, C79000-G8576-C199-07 — Section 8.4.12, page 8-54: fuse and mounting-width differences between 454-4UA13 and 4UA14. English.