6ES5 417-7AA21
Siemens 6ES5 417-7AA21 – 8-Channel Relay Output Module for S5-110
The 6ES5 417-7AA21 is an eight-channel relay output module for SIMATIC S5 S5-110A and S5-110S/B systems. Part of the S5 digital output range, it switches relay contacts under CPU control. Galvanic isolation is arranged in groups of four outputs. The relays require an additional 24 V DC supply.
The contacts have a 5 A continuous-current rating, which does not permit 5 A switching with every load. Siemens specifies 250 V AC / 5 A or 30 V DC / 2.5 A for resistive loads. When choosing a spare from the S5-90/110 module range, check the complete code, system type and AC/DC load characteristics together.
Relay supply and system connections
Nominal relay supply voltage is 24 V DC, with a permissible range of 20–30 V DC. Include this supply in the power supply calculation separately from the field loads switched by the contacts. Distinguish the 930 CPU supply from the additional relay supply. Check the rack and wiring assembly against the existing S5-110 diagram.
Four-channel isolation groups do not provide individual isolation for all eight channels. Preserve the grounding and reference arrangement. Siemens limits the total current at a common connection point to 5 A. Add the currents of the loads sharing that point; individual channel ratings do not override the common-connection limit.
Resistive and inductive load ratings
For inductive loads, Siemens specifies 250 V AC / 1.5 A (AC 11) and 30 V DC / 0.5 A (DC 11). When selecting an interface relay or contactor, check the coil's inrush and switching rate. Select fuses and circuit protection for the actual load; a contact-current rating does not replace short-circuit protection.
Temperature and simultaneous relay operation
The S5-110A manual's 7AA21 curve permits eight outputs operating simultaneously up to 40 °C, or four at 55 °C. This limits the number of relays operating together. Load-dependent contact ratings and the 5 A common-connection limit still apply.
Maximum switching frequency is 10 Hz for resistive loads and 2 Hz for inductive loads. Contact life depends on the load and operating rate; these frequency limits do not guarantee the same life with every load.
Green indicators and actual contact state
Siemens states that the green indicators show signal status in the 5 V control circuit. An illuminated LED alone does not confirm the additional 24 V relay supply or successful load switching. Compare the PLC program command with the actual load response and any digital input feedback. During troubleshooting, check the supply, contacts and field wiring separately.
Addressing and similar modules
Verify the actual output address from the S5-110 rack position and address markings. S5-110A programming uses system-specific interfaces such as the 500-7AA11. Check the S5-110S/B's own manual for its connection arrangement.
The 410-7AA11 uses transistor outputs, while the 415-7AB11 and 415-7AB21 use different AC solid-state output arrangements. The 451-8MR12 has relay outputs but belongs to another S5 module family. Matching the output count or relay technology alone is insufficient for replacement selection. Specify the complete 6ES5 417-7AA21 code and provide a wiring photograph. Disconnect system, relay and load supplies before removal or installation.
Editor’s note
Start with the relays' 24 V supply. A program command and an illuminated indicator cannot make up for a missing relay supply. A simple voltage check can save an unnecessary replacement.
Do not apply the 5 A marking to every load. At 30 V DC, the resistive switching limit is 2.5 A and the inductive limit is 0.5 A. Check the actual load before choosing a card, especially with DC coils.
If several loads share a common connection, measure their combined current. Individually modest loads can become demanding when they operate together. Remembering the 5 A common-point limit helps protect older connections too.
A relay click or illuminated LED does not prove that the contact is healthy. Worn contacts may produce a voltage drop under load; welded contacts may fail to open when the command ends. Complete the check by observing the actual load response.
Where practical, have all eight outputs checked with suitable loads. Inspect discoloured or loose connections and confirm that the relays release correctly. Keep photographs of the label and wiring for the day the spare needs fitting.
OtomasyonAVM resources and PDFs
+ Our S5-90 PDF page: other S5 documentation. The technical sources for the 417-7AA21 are the S5-110A and S5-110S/B manuals below.
+ S5-90/110 modules · S5 digital output modules · S5 cable types
Related topics
+ 410-7AA11 · 415-7AB11 · 415-7AB21 · 451-8MR12: output technology and system comparisons.
+ 500-7AA11 programming interface · Relays and sockets · PLC troubleshooting
Browse SIMATIC S5
S5-90/110 modules · S5 digital output modules · Siemens S5 PLC · Used Siemens equipment
Siemens and external references
+ Siemens S5-110A Operating Instructions – English, GWA 4NEB 807 0690-02: exact-code specifications and simultaneity curve, printed p. 1.13 / PDF 17; additional supply and common-point limit, p. 1.7 / PDF 11; wiring, p. 2.7 / PDF 26; indicators, p. 3.1 / PDF 28. Third-party archive copy of a Siemens publication.
+ Siemens S5-110S/B Operating Instructions – English, GWA 4NEB 807 2121-02: printed p. 10 / PDF 12; continuous contact current, AC/DC switching ratings, four-channel isolation groups and additional 24 V relay supply.