6ES5 482-8MA13
6ES5 482-8MA13 – SIMATIC S5 16-Input / 16-Output 24 V DC Digital I/O Module
Siemens 6ES5 482-8MA13 is a non-isolated combined digital I/O module with sixteen 24 V DC inputs and sixteen 24 V DC / 0.5 A outputs for S5-90U, S5-95U, supported S5-100U versions and ET 100U/ET 200U systems. Within the S5 digital input/output module range, it provides both signal directions in one housing. The 32 × 24 V DC marking on this Siemens S5 module refers to sixteen input points plus sixteen output points.
It reads sensor and contactor auxiliary contact states while switching suitable DC loads. Key features include a 40-pin front connector, n/n+1 channel arrangement, separate input/output fault indications and addressing within the analog-module address area.
Input levels and delay
Rated input voltage is 24 V DC. Specified levels are 0–5 V for logic 0 and 13–30 V for logic 1. Active input current is typically 4.5 mA. Check the power supply and NPN/PNP output configuration against these thresholds and the module’s M reference.
Input delay is typically 4 ms for 0→1 and 3 ms for 1→0. Two-wire BERO switches can be connected; the manual specifies a 1.5 mA residual-current value. Include off-state leakage when selecting an inductive sensor or photocell.
Output current and load supply
Rated output load supply is 24 V DC, with a continuous permissible range of 20–30 V DC. Each output is rated at 0.5 A; the permissible total output current is 6 A. Both the individual-channel and total-current limits must be satisfied.
The outputs have short-circuit protection. Specified switching frequency is 100 Hz for resistive loads and 2 Hz for inductive loads; maximum lamp load is 5 W. An illuminated digital output LED alone does not establish that the load receives the required voltage and current.
Non-isolated construction and fault indicators
Both the input and output sections are non-isolated. Do not interpret the two eight-output supply groups as independent galvanic isolation groups. Check M connections, field power and the grounding arrangement together.
The red F indicator on the IN side signals loss of L+/M supply; output-side fault indicators signal an output short circuit. Begin troubleshooting by identifying the affected side rather than treating an input-supply fault and an output-load fault as the same condition.
40-pin front connector
The manufacturer lists 6ES5 490-8MA13 / 6ES5 490-8MA03 crimp connectors and the 6ES5 490-8MB11 screw connector, all with 40 pins. When selecting S5 cables and connection hardware, check terminal construction and whether the connector is supplied with contacts.
The diagram assigns OUT-column pins 1 and 11 to L+, and 10 and 20 to M. On the IN column, pin 1 is L+, pin 20 is M, and pins 10 and 11 are NC. Pins 2–9 and 12–19 carry eight signals each on both sides. The upper group is marked n+1 and the lower group n; do not infer addressing solely from physical order.
S5-100U addressing and CPU version
In the S5-100U, this digital module uses the same address space as an analog module and can be installed only in slots 0–7. It uses the first two of eight reserved bytes; input and output byte numbers are identical. The PLC program’s I/Q areas represent the separate signal directions.
For example, slot 0 uses inputs I64.0–I65.7 and outputs Q64.0–Q65.7. German notation is E64.0–E65.7 / A64.0–A65.7. Do not apply this example unchanged to every SIMATIC S5 system or ET station; use the actual CPU and station configuration.
The S5-100U manual’s addressing coverage applies to CPU versions 8MA02 and higher, plus CPU 102 version 8MA01, revision 5 and higher. Use the appropriate system manual for S5-90U and S5-95U installations. Do not transfer an ordinary digital input module’s slot address directly to this combined module.
Cable length, power loss and physical checks
Maximum unshielded field-cable length is 100 m. Typical module power loss is 4.5 W; approximate weight is 190 g. Output-section consumption from L+ without load is typically 100 mA. Inspect bus-unit contacts, front-connector locking and load-supply connections together during replacement.
Editor’s note
Establish the channel count first on this S5 module: sixteen inputs and sixteen outputs. The “32 × 24 V” marking does not mean 32 inputs, and an old 8/8 listing does not define the hardware. Read the complete label alongside the manufacturer’s table.
A 0.5 A channel rating does not permit loading all sixteen channels to a combined 8 A. The module’s total limit is 6 A. Add up the operating currents of solenoids, relays and lamps before connecting the full load.
When a red indicator appears, first distinguish IN F from OUT F. Check L+/M on the input side and the load circuit on the output side. Replacing the module without resolving the cause can expose a healthy spare to the same fault.
Before disconnecting the front connector, photograph the OUT/IN sides, both output L+ supplies and the n/n+1 labels. If only eight outputs are affected, check the corresponding supply group. Do not automatically treat the upper row as the first byte.
For a used Siemens module, request tests of all sixteen inputs in both logic states and all sixteen outputs under suitable loads. Confirm addressing and CPU version too. Isolate power before replacement; correct supply wiring and addressing often resolve more than another board swap.
OtomasyonAVM resources and PDFs
+ S5 digital input/output modules · S5 cables and connectors · S5-90U main page.
+ S5-90U / S5-95U PDF files. The exact 482-8MA13 circuit and specification table appear on printed pages 15-34–15-35 / PDF pages 398–399 of the English system manual.
+ Shared PDF archive for other S5 systems. In the S5-100U manual, the circuit and table are on 14-36–14-37 / PDF 386–387, with addressing on 6-7 / PDF 109. The ET 100U manual covers the circuit and specifications on 2-34–2-35 / PDF 48–49.
Related topics
+ 482-8MA11 · 482-8MA12 · 490-8MA13 connector · 490-8MB11 connector. Check revision and system compatibility separately for earlier module codes.
+ S5 digital inputs · S5 digital outputs · PLC troubleshooting.
Browse SIMATIC S5
S5 combined digital I/O modules · S5-90U · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page.