6ES5 430-8MD11
Siemens 6ES5 430-8MD11 — 4-Channel 230 V AC/DC Digital Input Module
6ES5 430-8MD11 is a 4-channel, 230 V AC/DC digital input module documented for S5-100U and ET 100U systems in the Siemens SIMATIC S5 family. Its optocoupler digital inputs form one galvanically isolated group of four. The channels are not individually isolated.
It transfers high-voltage relay, contactor auxiliary-contact and interposing-relay states to the PLC in SIMATIC S5 installations. Typical logic-1 input current is 16 mA at 230 V AC or 2.5 mA at 230 V DC. These figures describe current drawn by the input circuit, not an output or load-driving capacity.
Signal thresholds and input delay
Logic 0 is defined as 0–70 V and logic 1 as 170–264 V. 70–170 V is not a guaranteed logic state. The AC frequency range is 47–63 Hz. A standard 24 V DC sensor output cannot directly provide logic 1 to this input.
Typical inherent delay is 10 ms from 0 to 1 and 20 ms from 1 to 0. Assess input delay, data transfer and CPU scan time together when evaluating short pulses. This card should not be treated as a high-speed counter input.
AC wiring diagram and bus unit
The Siemens AC wiring diagram identifies terminal 1 as L1 and terminal 2 as N. Contact pairs for the four inputs are 3–4, 5–6, 7–8 and 9–10, respectively. Do not confuse this four-channel arrangement with the terminal order of an eight-input card.
Field cables connect to the bus unit’s terminal block. The 700-8MA11 screw-terminal bus unit and 700-8MA22 crimp bus unit use different connection methods. When inspecting S5 cables and connections, check terminal contacts, module seating and mechanical coding together.
Addressing and paired channel markings
On S5-100U, a digital module’s byte address is its slot number. Only .0, .1, .2 and .3 are used on this four-channel card. For example, inputs in slot 3 are addressed as I 3.0–I 3.3. Front-panel markings .4–.7 apply to ET 100U; they do not indicate eight physical inputs.
Compare the PLC program and input/output assignment with the actual installation. In ET 100U, assess addressing through the relevant interface module and distributed expansion arrangement; do not transfer the S5-100U slot example directly to that system.
Sensor, cable and temperature conditions
The specified maximum unshielded field-cable length is 100 m. Suitable two-wire BERO proximity switches can be connected; the manual specifies a 5 mA residual-current value. Check sensor AC/DC suitability, off-state current and input thresholds together.
Permissible ambient temperature is 0–60 °C with horizontal arrangement or 0–40 °C with vertical arrangement. Typical consumption from the internal +9 V bus supply is 16 mA, and typical module power loss is 2.5 W. The internal bus supply and field signal voltage belong to separate circuits.
During fault diagnosis, inspect actual input voltage, common supply/return connections, terminal block and the program bit state together. An LED alone does not establish that every connection is healthy. Establish safe machine conditions before measurements.
Differences between related modules
430-8MC11 has four 115 V inputs, while 430-8MB11 has four 24–60 V DC inputs. 431-8MD11 has eight 230 V inputs and 431-8MA11 has eight 24 V DC inputs. Compare channel count, signal voltage and terminal arrangement together.
450-8MD11 is a digital output module. The shared 8MD11 suffix does not establish the same function or direct interchangeability with the 430 input card.
Editor’s note
Do not let paired markings such as .0/.4 make this look like an eight-input card. 430-8MD11 has four inputs. S5-100U uses .0–.3; the other markings relate to ET 100U addressing. Clear up that distinction before choosing a spare.
Check the 230 V signal class first. A 115 V 430-8MC11 or a 24–60 V DC 430-8MB11 may look similar. Reading the label before replacement can prevent a straightforward maintenance job from becoming another fault.
If all four channels fail together, inspect the common L1/N connections, terminal block and module seating on the bus unit first. Checking shared points is often a better starting point than assuming several independent channel faults.
If an input remains on with a sensor off, look beyond the LED before replacing the card. Check sensor residual current and actual input voltage. A voltage between defined ranges or an unsuitable sensor can make a healthy card look faulty.
For a used card, check all four channels individually with suitable signals, including both switching directions. In a vertical installation, remember the 40 °C ambient limit. Photograph the label, terminals and slot information before removal so the next maintenance visit starts with clear records.
OtomasyonAVM resources and PDF files
+ S5 PDF files and user manuals · About Siemens S5 PLCs. In the S5-100U Manual, EWA 4NEB 812 6120-02b, specifications and wiring appear on 14-21 / PDF 371, with addressing on 6-4 / PDF 106. The same model’s 230 V AC/DC rating and DC input current are explicitly stated in the ET 100U Manual, EWA 4NEB 812 6040-02a, 2-19 / PDF 33. Both documents are in English.