6ES5 460-4UA13

Siemens 6ES5 460-4UA13 — 8-Channel Isolated Analog Input Module

The Siemens 6ES5 460-4UA13 is an eight-input, galvanically isolated analog measurement module for S5-135U/155U systems in the SIMATIC S5 family. Voltage, current and Pt100 operation depend on the installed 498 measuring range cards and the module’s mode settings. This S5 analog module has two range-card slots, with each card serving four channels.

The module converts field analog signals into digital values for the PLC. Depending on the hardware configuration, it accepts mV, V, mA or Pt100 resistance sensors. Data representation is selectable as 13-bit two’s complement or 12-bit magnitude plus sign. The main module’s order number alone does not establish its configured input range.

498 range cards and input ranges

The 6ES5 498-1AA11 supports ±50 mV, ±500 mV and Pt100 measurements. The ±12.5 mV range requires the appropriate 50 mV mode and ×4 gain. Standard and extended Pt100 modes use different value representations.

With the 500 mV base mode and normal ×1 gain, the 6ES5 498-1AA21 provides ±1 V, the 6ES5 498-1AA61 provides ±5 V, and the 6ES5 498-1AA31 provides ±10 V measurement.

The 6ES5 498-1AA41 is used for ±20 mA at the normal setting. Use the 6ES5 498-1AA51 for 4–20 mA two-wire transmitters and the 6ES5 498-1AA71 for separately powered four-wire transmitters. Their transmitter wiring arrangements are different.

One range card serves Ch0–Ch3 and the other serves Ch4–Ch7. Different range cards can be combined when they are compatible with the main module’s common base mode and gain setting. The eight channels do not each have an independently selectable range.

Power supply, enable input and front connector

The digital section receives 5 V from the system bus; the analog section requires an external 24 V DC supply. The permissible L+ range is 20–30 V DC. Front connector terminals are 22 = L+, 23 = L−; 1 = F+, 2 = F−. Check the 42-pin front connector and terminal numbering when inspecting S5 cables and connectors.

With the enable jumper fitted, 24 V must be applied across F+/F−. Without that voltage the module does not acknowledge access, which can cause a QVZ timeout in the CPU. Removing the enable jumper disables this input. The L+/L− analog supply and F+/F− enable supply have separate functions.

Voltage/current measuring terminal pairs are Ch0: 3+/4−; Ch1: 6+/8−; Ch2: 10+/13−; Ch3: 15+/17−; Ch4: 29+/31−; Ch5: 34+/36−; Ch6: 38+/40−; Ch7: 41+/42−. Pt100 wiring also uses the constant-current terminals 25 = IC+, 27 = IC−; follow the manual’s complete sensor circuit.

The inputs are isolated from M, Mext and L+/L−. Assess signal references, two-wire transmitter connections and the grounding arrangement together. The manual also specifies permissible potential differences between sensor references and between sensors and the module.

Mode settings and measurement speed

Mode switches I and II select the base range, ×1/×4 gain, data format, selective/cyclic scanning, 50/60 Hz and wire-break monitoring where supported by the measurement type. The supply-frequency setting matters for noise immunity: integration time is 20 ms at 50 Hz or approximately 16.67 ms at 60 Hz.

Encoding time per measured value is 60 ms at 50 Hz or 50 ms at 60 Hz. For eight measurements at 2048-unit resolution, the manual gives a scan time of approximately 0.48 seconds at 50 Hz. This is separate from the PLC program’s scan time.

Value representation and diagnostics

Normal voltage/current ranges use ±2048 measurement units at nominal full scale. For 4–20 mA, the values are 512 units at 4 mA and 2560 units at 20 mA. In PLC programming, account for the selected data format, range card and lower status bits.

In standard Pt100 mode, 100 Ω corresponds to approximately 1024 units, representing the Pt100 0 °C point. Extended Pt100 mode compensates the 100 Ω base resistance on the module and changes the zero reference. Reading resistance values directly as temperature gives incorrect results.

During PLC debugging, check the enable voltage, analog supply, module address and A, E and OV status bits together. Wire-break monitoring depends on the measurement type. In 4–20 mA mode, low current must be assessed in software rather than relying on a direct wire-break indication.

Related models and replacement checks

When replacing a 6ES5 460-4UA12, check the installed range cards and enable behaviour. The 6ES5 465-4UA13 has a different channel count and non-isolated design; the 6ES5 463-4UA12 is a different four-input module. These models are not automatically interchangeable.

Editor’s note

When buying this module, look beyond the main label and ask for the codes on both small 498 range cards. Two identical 460 modules may be equipped for different signals. Finding a missing range card afterwards can turn a straightforward replacement into a longer job.

If the module does not respond, give the enable jumper and F+/F− voltage a check before calling it faulty. Having the main supply present does not establish that the enable condition has been met. Sometimes that is the whole problem.

If the reading is out by a factor of four, check ×1/×4 gain first. A photograph of the old module’s side switches can save a great deal of time. A serviceable card can look faulty when tested with the wrong setting.

A value of 1024 on a Pt100 channel is not, by itself, a fault. In standard mode it can represent 100 Ω, or approximately 0 °C. Establish the selected Pt100 mode and the program’s scale before drawing conclusions.

For a used-module check, test both range-card groups and all eight inputs. Review the S5 system layout, address and existing program together. Clear labels, switch photographs and recorded measurements make the final decision much easier.

OtomasyonAVM resources and PDFs

+ Browse S5 analog modules and About Siemens S5 PLCs for related module and system information.

+ The OtomasyonAVM S5 PDF archive is the starting point for our manual resources. The detailed manufacturer reference for this model is the S5-135U/155U System Manual, Section 9.3, particularly printed pages 9-5 and 9-23–9-34. The manufacturer documents below are in English.

Related topics

+ 498-1AA31 — ±10 V range card · 498-1AA41 — ±20 mA range card.

+ 498-1AA51 — two-wire 4–20 mA · 498-1AA71 — four-wire 4–20 mA · 498-1AA11 — mV and Pt100.

Browse SIMATIC S5

+ S5 analog modules · SIMATIC S5 systems · Siemens S5 main page.

+ Used Siemens automation equipment.

Siemens and external references

+ Siemens S5-135U/155U System Manual — C79000-G8576-C199-07, English: Section 9.3, specifications for the exact 6ES5 460-4UA13 model, range cards and wiring diagrams.

+ Siemens U Periphery Manual — 6ES5 998-0PC22 and documentation supplement, English: earlier 4UA11/12 versions, analog input wiring and supplementary information covering 4UA13.

+ Siemens ST 50, 1998 catalog — archived English copy: specifications, ordering data and front connector diagrams on printed pages 4/43–4/49.