6ES5 460-4UA12
6ES5 460-4UA12 – 8-Channel Isolated Analog Input Module
Siemens 6ES5 460-4UA12 is a compact U-format SIMATIC S5 module with eight analog inputs requiring measuring-range submodules. It handles voltage, current or Pt100 measurements in systems such as the S5-135U and S5-155U. This S5 analog module accepts two four-channel 498 range submodules; the submodules and hardware settings together determine the signals passed to the Siemens S5 PLC.
Do not connect a signal merely because the front label says “460.” The analog signal type must match the range submodule, 50/500 mV base setting and gain. Voltage/current inputs are isolated from each other and the system reference; the same channel-to-channel isolation does not apply to Pt100 inputs.
498 submodules and input ranges
6ES5 498-1AA11 is the continuity-type submodule used, with the appropriate settings, for ±50 mV, ±500 mV and Pt100. Selecting ×4 gain in the 50 mV setting provides the ±12.5 mV range. When comparing the module with the 460-4UA11, check the 4UA12 gain setting separately.
With the appropriate 500 mV base setting and ×1 gain, 498-1AA21 provides ±1 V, 498-1AA31 ±10 V, 498-1AA61 ±5 V, and 498-1AA41 ±20 mA. Selecting ×4 gain with the same shunt submodule provides ±5 mA.
Use 498-1AA51 for a 4–20 mA two-wire transducer, or 498-1AA71 for an externally powered four-wire transducer. Different range submodules may serve the two groups of four inputs, but the shared base-range and gain settings must suit both groups.
Power, enable circuit and front connector
The digital section receives 5 V from the SIMATIC S5 bus; the analog section requires a 24 V DC field supply. Front-connector assignments are 1: F+, 2: F− for enable, and 3: L+, 21: L− for the analog supply. Check the power and enable circuits separately.
Voltage/current channel terminals are Ch.0: 4+/6−, Ch.1: 8+/10−, Ch.2: 13+/15−, Ch.3: 17+/19−, Ch.4: 25+/27−, Ch.5: 29+/31−, Ch.6: 34+/36−, Ch.7: 38+/40−. Compare the front connector and wiring with the exact-order-number diagram. Pt100 connections use a separate wiring arrangement.
The Siemens documentation supplement requires the common reference of the relevant inputs to be connected to L− when using two-wire transducers. This removes the galvanic isolation between the channels and the L+/L− field supply. Account for this requirement when checking grounding and potential differences.
Mode switches, addressing and conversion time
Mode switches I and II select single/cyclic scanning, 50/60 Hz, data format, base range, gain and suitable open-circuit monitoring. Integration time is 20 ms / 16⅔ ms; coding time per channel is 60 ms / 50 ms. Eight nominal measurements take approximately 0.48 seconds at 50 Hz; this differs from the PLC scan time.
The module’s address switch sets its starting address. Eight inputs use 16 address bytes, with two bytes per channel. In the STEP 5 program, channel words follow n, n+2, …, n+14. The slot number alone does not define the input address.
Select either 13-bit two’s complement or 12-bit magnitude plus sign. The nominal bipolar range corresponds to ±2048 units; the specified nominal scale for the appropriate 4–20 mA configuration is 512–2560 units. During troubleshooting and scaling checks, evaluate the measurement together with the T busy, F fault and overflow bits.
Editor’s note
Before buying this card, ask for clear photographs of both range submodules. In an S5 system, a healthy main board is only part of the job: the 498 codes must match your sensors. Check the label, submodules and switch positions together, then make the decision with confidence.
Do not transfer the wiring unchanged just because a 460-4UA13 or 465-4UA12 looks familiar. In particular, channel count, isolation and gain need checking. A photograph of the original installation is much more useful than trying to remember its settings later.
Read 460-7LA12 and 4UA12 as different order numbers. Match the complete code, connector and system requirements before purchasing. Membership of the same “460” family is not enough to approve a replacement.
If every channel appears dead, give the card a fair check first. Verify the 24 V analog supply, F+/F− enable circuit and starting address. Then test the two input groups separately with a suitable source. A missing connection should not put a serviceable board on the scrap pile.
Do not assume that disconnecting a current loop must produce a wire-break alarm. The 1AA41, 1AA51 and 1AA71 shunt inputs do not provide that diagnosis in the same way. On this 4UA12, stopping the test current also requires more than changing a switch: with open-circuit monitoring disabled, the manual specifies +24 V at pin 24 and 0 V at L− pin 21. Check the diagram carefully and keep these terminals separate from the measurement inputs.
OtomasyonAVM resources and PDFs
+ S5 analog input, output and measuring-range modules.
+ About Siemens S5 PLCs: system and maintenance information.
+ S5 PDF archive: system and module manuals. Detailed wiring and settings for this model are in section 5.2 of the Siemens U Periphery manual linked below.
Related topics
+ 6ES5 460-4UA11: earlier 460 input module.
+ 6ES5 460-4UA13: later-version model page.
+ 6ES5 465-4UA12: alternative 16/8-input analog module.
Browse SIMATIC S5
S5 analog modules · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page