6ES5 762-2CS11
Siemens 6ES5 762-2CS11 ET 200C Power Supply Connector
Siemens 6ES5 762-2CS11 is the ET 200C power supply connector for Siemens ET 200 installations used with SIMATIC S5. It feeds an external 24 V DC supply into the same cable as PROFIBUS DP (SINEC L2-DP). The permitted supply range is 20.4–30.2 V DC and the connector carries up to 4 A. It has two 12-pin sockets and one 6-pin male connector and is rated IP66/IP67 when installed as specified.
In the field, this is where 24 V enters the shared cable in an ET 200 power distribution layout. An external DC power supply provides the voltage. The connector passes it and the DP signal to the next station on the shared cable. Among ET 200 connection modules, the separate 6-pin supply inlet identifies this part.
What connects to each port?
The 12-pin input socket takes the incoming DP bus, the 6-pin male connector takes external 24 V DC and the 12-pin output socket carries both. When tracing S5 cables and connectors, use the port markings to distinguish the two 12-pin sockets. Siemens lists the 6ES5 760-2CB11 12-pin male connector for cable assembly. Check the pin assignment when selecting PROFIBUS connectors and connect protective earth to the housing’s PE screw.
The 4 A limit and shared cable length
Use the individual module specifications to calculate the current drawn on the shared cable by digital inputs, digital outputs and analog inputs. For stations with a separate load supply, such as the 6ES7 143-0BL00-0XB0 mixed I/O module, account for output load current on its own supply branch. The connector has no galvanic isolation or built-in short-circuit protection.
With bus and supply in the same cable, Siemens Table 2-4 gives these maximum distances from the connector to the last station. Allow up to 80 m below 1 A, 40 m below 2 A or 20 m below 4 A. These figures apply to the shared power and data cable. Check the DP segment length separately against the selected bus rate.
Bus rates, addressing and termination
The connector has no DP station address. Siemens lists 9.6 / 19.2 / 93.75 / 187.5 / 500 kbaud and 1.5 / 3 / 6 / 12 Mbaud. Operation at 3, 6 or 12 Mbaud requires an IM 308-C DP master and ET 200C digital modules. When choosing ET 200 network hardware, use a rate supported by both the master and the connected stations.
In Siemens’ layout with the 6ES5 762-2CT11 T connector, the bus stays connected to the remaining stations when one station is disconnected. Check the installation drawing for the ET 200C bus ends and the position of the 6ES5 755-2CA11 terminating resistor.
Editor’s note
When ordering a spare, match the 2CS11 suffix, the two 12-pin sockets and the 6-pin male inlet to the existing part.
Label the incoming and outgoing cables before removal. Photograph the port markings and the PE connection.
If several stations drop out together, start at the 24 V source for the ET 200 supply circuit and check the shared cable.
If the stations still have power, use the PROFIBUS troubleshooting guide to check the master diagnostics, data pair and termination.
Inspect used parts for damaged pins, threads and seals. If you also need a used DC power supply, match it as a separate item.
OtomasyonAVM resources and PDFs
Siemens ET 200 system overview and Siemens ET 200 manuals and PDF archive.
SIMATIC ET 200C distributed I/O system manual (PDF) · §2.1.3, current and cable length.
Related topics
6ES5 762-2CT11 T connector, 6ES5 755-2CA11 terminating resistor and 6ES5 760-2CB11 12-pin cable plug.
Browse the range
Siemens ET 200 · ET 200 connection modules · SIMATIC S5
Siemens and external references
Siemens ET 200C manual · §3.9, port layout · §13.2, technical specifications