6ES5 760-0AA11
6ES5 760-0AA11 – IM 310 Line Terminating Connector
Siemens 6ES5 760-0AA11 is a 50-pole passive terminating connector containing a resistor and jumper network for SIMATIC S5 expansion connections. It terminates the end of an IM 310 distributed connection built with S5 interface modules. Its role in the Siemens S5 PLC system is to provide the termination specified for that connection.
In a chain using the 6ES5 310-3AB11 IM 310, terminate the continuation connection at the final expansion unit. The S5-135U/155U manual also specifies 760-0AA11 for an unused distributed connection on the IM 301-3. On the IM 301-3 family, distinguish a centralized connection from a distributed connection before choosing the plug.
Where is it installed?
Follow the 721 connecting cable through the installation and identify the actual end of the chain. In a SIMATIC S5 configuration, fit the connector to the unused continuation socket identified for termination in the wiring diagram. Replacing an intermediate cable with a terminator disconnects the units beyond that point.
Figure 3-26 in the Siemens S5-115H manual shows an AS 301/AS 310 configuration and the 760-0AA11 on the final AS 310. The same drawing distinguishes the separate connection point using 760-0AB11.
Differences from 760-0AB11, 760-1AA11 and 760-0HA11
The manufacturer specifies 6ES5 760-0AB11 for the IM 312 and an unused centralized connection on the IM 301-3. Finding an IM 312-family module such as the 312-3AB11 or 312-3AB12 does not establish that 0AA11 belongs on the same port. Check the port function and complete module code together.
6ES5 760-1AA11 is a different termination for the last IM 314. Assess a connection built with IM 314 and IM 304 modules according to its own termination diagram, separately from an IM 310 chain.
The S5-115H manual specifies 6ES5 760-0HA11 for the lower front connection of the last IM 314R. Similar housings do not establish identical internal circuits. Changes to grounding or shielding cannot make an incorrect termination code suitable.
Internal circuit and inspection
Siemens Figure 7-16 shows 180 Ω resistors and defined pin jumpers for the 760-0AA11. Check each measured pin pair against that circuit; testing two arbitrary pins for a single resistance is insufficient. Perform resistance checks with the connector removed and the equipment de-energized.
During fault finding, inspect bent contacts, corrosion, loose fastening and cable continuity through to the last unit. This is a passive terminator; it has no separate PLC I/O address or program download procedure.
Editor’s note
Do not overlook this small plug. A missing terminator in an older S5 system can lead to a lengthy fault search. Read the 760-0AA11 marking first, then establish where the cable chain ends. Asking for “a 760” leaves too much room for a wrong choice.
If the cabinet also contains centralized interface modules such as the IM 300, trace the cables from end to end. Different connection branches may share a cabinet. Do not fill every unused socket with the same plug; the installation diagram identifies the correct location.
When encountering another interface family, such as the 304-3UA11, do not move a terminator across by habit. A familiar housing can be misleading. Request photographs of the label and internal pin circuit before ordering; it saves a return trip with the wrong part.
If communication stops, check the cable, termination and connector seating before changing the PLC program. A simple contact problem should not turn a working program into another troubleshooting variable.
A tidy cover on a used connector is encouraging, but check the contacts, fastening and resistor/jumper connections against the diagram as well. Where possible, compare it with a known-good connector bearing the same code. Do not put a healthy interface module at risk by adding improvised bridges.
OtomasyonAVM resources and PDFs
+ S5 interface modules and connection accessories.
+ S5 PDF archive: system and connection manuals.
Related topics
+ 6ES5 310-3AB11: IM 310 interface module.
+ 6ES5 760-0AB11: centralized-connection terminator.
+ 6ES5 760-1AA11: IM 314 terminator.
+ 6ES5 760-0HA11: termination for the IM 314R connection.